16B0013AMDP0002_PG_2.pdf

PDF 14 KB Posted

Attached to
Wastewater Plant Repair Federal contract opportunity
Solicitation number
SP3300-16-B-0013
Issued by
Defense Logistics Agency Distribution

About this file

Page 2 of Amendment 00002

View the file

Other files for this federal contract opportunity

Other files attached to Wastewater Plant Repair, newest first.
File Type Posted
Tab_E-17_Public_Notice_of_Award.pdf PDF
Bid_Results_-_SP330016B0013.pdf PDF
16B0013_SF30_AMENDMENT_0003.pdf PDF
16B0013AMDP0003_PG_2.pdf PDF
16B0013_SF30_AMENDMENT_0002.pdf PDF
Attachment_13_Plate_Image.pdf PDF
Attachment_12_Site_Visit_Roster.pdf PDF
Amendment_0001.pdf PDF
Attachment_4_Schedule_of_Supplies.pdf PDF
Attachment_9_SF25_(Performance_Bond).pdf PDF
Solicitation.pdf PDF
Attachment_5_Submittal_Reg.pdf PDF
Attachment_6_Transmittal_of_Shop_Drawings.pdf PDF
Attachment_8_SF24_-_Bid_Bond.pdf PDF
Attachment_3_Drawing_and_Photos.pdf PDF
Attachment_11_Standard_Form_1442.pdf PDF
Attachment_7_Davis_Bacon.pdf PDF
Attachment_1_SoW _Gen_Specs _and_Checklists.pdf PDF
Attachment_2_Site_Map.pdf PDF
Attachment_10_SF25A_Payment_Bond.pdf PDF
Show all 20

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SP3300-16-B-0013

AMD 00002

I. The purpose of this amendment is to provide answers to vendor questions.

II. The following Vendor Questions are hereby answered.

Question 1:

What are the Liquidated Damages?

Answer 1: $500 per day

Question 2:

Is there Good Faith Outreach requirements?

Answer 2: There are no Good Faith Outreach Requirements for this acquisition.

Question 3:

Was the pre-bid meeting mandatory?

Answer 3: No

Question 4:

M001 calls out Detail 5 on M003 for the BFV installation detail … this detail cannot be found. Can you please provide.

Answer 4: This a typo detail 5 is not required.

Question 5:

What size is the BFV?

Answer 5: 10 inches

Question 6:

What is the scope of electrical? Can you provide any more detail/drawings on what the scope of work will be?

Answer 6: Electrical work is minimal. New pumps can use existing disconnect switches located next to them. No need to run wires or conduits to exiting panel.

Question 7:

What is the scope of instrumentation/SCADA?

Answer 7: None

Question 8:

Can you additionally get me the serial numbers for the sludge pumps per scope item 2.

Answer 8: CL287

Question 9:

Please do the same for the pumps per scope item 3 Answer 9: Circulating pump name plate is provided on Attachment 13 Plate Image. No other information is available.

Contractor must verify all the field information. Govt. shall not be liable for any discrepancies found later.

Question 10: We are wondering if you could kindly provide access to e-copies of the aforementioned project?

Answer 10: See section B.2 Electronic Solicitation

III. Attachment 13 Plate Image is hereby added to this solicitation

IV. All other terms and conditions remain unchanged.

File details come from the government source that posted it. Updated .