IRTH_RFI_Amendment_4.pdf

PDF 197 KB Posted

Attached to
Indoor Running Track Heaters Federal contract opportunity
Solicitation number
Solicitation_FA2550-17-R-1020
Issued by
Department of the Air Force Space Command

About this file

Amendment #4 RFI responses

View the file

Other files for this federal contract opportunity

Other files attached to Indoor Running Track Heaters, newest first.
File Type Posted
B122_Grading_Plan.pdf PDF
IRTH_RFI_Amendment_5.pdf PDF
IRTH_RFI_Amendment_3.pdf PDF
IRTH_RFI_Questions_and_Responses.pdf PDF
Site_Visit_9-5-17.pdf PDF
1_FA2550-17-R-1020_1442.docx.pdf PDF
4_Install_Heaters,_B122_Drawing.pdf PDF
3_Cable_Installation_Guide_0911B.pdf PDF
PROPOSAL_DUE_DATES.pdf PDF
5_ENV_SPEC_SECTION_-_V1_2_Dec_14.pdf PDF
6_Install_Heaters,_B122_AF_Form_66.pdf PDF
2_SOW_Install_Heaters,_B122.pdf PDF
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FA2550-17-R-1020 Indoor Running Track Heaters Amendment #4

FA2550-17-R-1020

RFI Questions and Responses

1. For the installation of the new gas line will HDPE gas piping be allowed?

a. Government Response: Yes, HDPE gas line is allowed for the underground portion. The portion above ground tapping into the existing steel gas line after the meter at B120 shall be steel pipe.

2. Will directional boring be allowed from the east end to the gas point of connection?

a. Government Response: Yes, directional boring is allowed as long as it doesn’t damage existing underground utilities in the area.

3. Will house keeping pads be required or can the new Heating Unit be placed on a raised platform?

a. Government Response: Concrete pads is called out to place the heating units on.

Heating units may be placed on raised platforms on top of the concrete pads. If raised platform is used ensure the heater units are at a comfortable height for ease of access for maintenance.

4. Will 120 vac connivance receptacles be required at each of the lockable disconnects for each Heating Unit?

a. Government Response: The government prefers to have the receptacles but not an absolute requirement.

5. Please provide contact information for HSQ controls contractor.

a. Government Response: polissky@HSQ.COM 1-800-486-6684

6. Will the government require a PE stamp for the design and as-built for the new heating system?

a. Government Response: No PE stamp is required, but heater units shall be certified by the manufacturer.

7. Can the new gas line be opened trenched along the back side of the structure going from

Heating Unit-1 to Heating Unit-2?

a. Government Response: Yes, open trench is allowed for installing gas line between heater units. Ensure locates are done prior to trenching to prevent damage to existing underground utilities, if any is in the area.

8. Will the government provide the contractors with utilities drawing and locates?

a. Government Response: Government will provide what drawings we have available, but the contractor is responsible for completing the Form 103 (utility locates request). 50 CES shops will complete a locate for existing underground utilities in the area. It is the contractor’s responsibility to maintain the locates for the duration of the contract.

9. For bidding purposes will the government provide a grading plan for the drainage control work at the east end of the structure as discussed at the site survey?

a. Government Response: Yes, the government will provide a grading plan for the

NW and SE corners of B122, where the heater units are proposed to be installed.

mailto:polissky@HSQ.COM

FA2550-17-R-1020 Indoor Running Track Heaters Amendment #4

10. Is any data available for the soils condition for the concrete slab-on-grade at each Heating

Unit?

a. Government Response: No, no soil data is available at the locations where the heater units will be installed. The ground must be compacted prior to pouring the concrete pads. Subbase for the purpose of stabilizing the compacted ground may be used, if needed.

11. Will the new Heating Units be a direct fire unit with 100% outside air or an Indirect fired

Make up air unit with return/outside mix air and ducting.

a. Government Response: The government prefers the indirect fired make-up air unit with return/outside mix air and ducting heaters.