SO-1858 Gardner School Chiller Replacement Addendum 1.pdf

PDF 4 MB Posted

Attached to
SO-1858 Gardner School Chiller Replacement State and local contract opportunity
Solicitation number
RFP LSD 260000002049 4
Issued by
Grand Traverse County, Michigan

About this file

This is Addendum No. 1 to a chiller replacement project issued by the Lansing School District, with engineering services provided by Matrix Consulting Engineers. The addendum, dated May 19, 2026, modifies and clarifies the original contract documents for the Gardner Elementary School chiller replacement project located at 333 Dahlia Drive, Lansing, Michigan. The addendum takes precedence over original contract documents and must be acknowledged by all bidders on the proposal form. The modifications are limited to electrical specifications and drawings, with no changes to project scope, timeline, or delivery requirements mentioned in this document.

The addendum includes four re-issued electrical sheets (E-300, E-500, E-600, and E-601) that add existing electrical panel information, remove outdated keynotes, add circuit tags to equipment including exhaust fans (EF-1, EF-2) and a combination starter (P-HC-1), and revise the location of the P-4 combination starter. The modifications establish base bid and alternate bid options for contractors regarding the treatment of existing conduit and equipment, including provisions for disconnecting and removing existing chillers with associated wire and conduit management. The electrical work includes connections to multiple panels, variable frequency drives (VFDs), combination starters rated between 5 and 480 horsepower, and control systems integrated with the building automation system. No pricing information, contract award dates, or specific response deadlines are included in this addendum document.

View the file

Other files for this state and local contract opportunity

Other files attached to SO-1858 Gardner School Chiller Replacement, newest first.
File Type Posted
Addendum 02 - Matrix.pdf PDF
SO-1858 Gardner School Chiller Replacement.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

544 Cherbourg Drive, LANSING, MI 48917

PHONE: (517) 487-2511

FAX: (517) 487-2544

ADDENDUM NO. 1

LSD Gardner Elementary Chiller Replacement

Date:05/19/2026 Job Number: 260150.00

OWNER: ENGINEER:

Lansing School District Matrix Consulting Engineers 333 Dahlia Dr 544 Cherbourg Drive Lansing, MI 48911 Lansing, MI 48917

This Addendum is issued for the purpose of modifying and/or clarifying the original Contract Documents and shall take precedence over them.

All work included herein shall be in accordance with the original drawings and specifications except as specifically noted herein. All incidental items required to provide the following modifications shall be included even though not specifically described.

This addendum is being sent to all bidders receiving plans and specifications. Receipt of this Addendum shall be noted on the Proposal Form in the appropriate location.

Electrical

1. Sheet E-300 (Sheet Re-issued):

a. Added existing panel.

2. Sheet E-500 (Sheet Re-issued):

a. Added existing panel.

b. Removed keynote.

c. Added circuit tags to equipment (EF-1, EF-2, P-HC-1).

d. Revised location of P-4 combination starter.

3. Sheet E-600 (Sheet Re-issued):

a. Added existing panel schedule.

4. Sheet E-601 (Sheet Re-issued):

a. Added revised panel schedule.

END OF ADDENDUM

X-CH-2

X-P X-P

X-P X-P

GENERATOR

X-B X-B

X-DWH

X-COMPRESSOR

X-P-5

X-DDC CONTROL PANELS

X-P-1 VFD X-P-2 VFD

X-P-4

X-CH-1

X-P-3

X-P-6

X-P-1

X-P-2

1 1

1 2

1 1

2 2 1 1 1

J CONTROL

PANEL

35KVAR

J

9KVAR4KVAR

"EMPD-01"

PNL "PP-02"

PNL "PP-4"

TS

FACP

PNL "EXCP-01"

T7

PNL "XFAP-01"

65KVAR

J

J CONTROL

PANEL

1 2

TU

PNL "EBCP-01"

EXISTING EQUIPMENT TO REMAIN.

BASE BID:

DISCONNECT AND REMOVE EXISTING EQUIPMENT. ASSOCIATED CONDUIT

TO REMAIN FOR CONNECTION TO NEW EQUIPMENT. REMOVE ASSOCIATED

WIRE BACK TO SOURCE.

ADD ALTERNATE:

DISCONNECT AND REMOVE EXISTING EQUIPMENT. ASSOCIATED CONDUIT

TO BE CAPPED ABOVE FINISHED FLOOR. REMOVE ASSOCIATED WIRE BACK

TO SOURCE.

BASE BID:

EXISTING EQUIPMENT TO REMAIN. ASSOCIATED CONDUIT TO REMAIN FOR

CONNECTION TO NEW EQUIPMENT. REMOVE ASSOCIATED WIRE BACK TO

SOURCE.

ADD ALTERNATE:

EXISTING EQUIPMENT TO REMAIN. ASSOCIATED CONDUIT TO BE

TERMINATED TO PULL BOX. REMOVE ASSOCIATED WIRE BACK TO SOURCE.

DISCONNECT AND REMOVE EXISTING CAPACITOR FOR REMOVAL OF

CHILLER. RE-CONNECT CAPACITOR TO NEW CHILLER.

DEMOLITION NOTES

M A

T R

I X

N MECHANICAL ROOM PLAN - DEMOLITION

SCALE: 1/4" = 1'-0"

0 1 5 10

AutoCAD SHX Text

PROJECT NUMBER

AutoCAD SHX Text

SHEET NUMBER

AutoCAD SHX Text

SHEET DESCRIPTION

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROJECT

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

CONSULTING ENGINEERS, INC

AutoCAD SHX Text

PHONE: (517) 487-2511

AutoCAD SHX Text Lansing, MI 48917

AutoCAD SHX Text 544 Cherbourg Drive

AutoCAD SHX Text administrator@matrixceinc.com

AutoCAD SHX Text 260150.00

AutoCAD SHX Text 05/18/2026

AutoCAD SHX Text

GARDNER INTERNATIONAL MAGNET SCHOOL

AutoCAD SHX Text

CHILLER REPLACEMENT

AutoCAD SHX Text

333 DAHLIA DR, LANSING, MI

AutoCAD SHX Text

ADDENDUM #1

AutoCAD SHX Text 05/19/2026

AutoCAD SHX Text

100% BID SET

AutoCAD SHX Text 05/18/2026

AutoCAD SHX Text Matrix Project No. 260150.00

AutoCAD SHX Text E-300

AutoCAD SHX Text

MECHANICAL

AutoCAD SHX Text

ROOM PLAN

AutoCAD SHX Text

DEMOLITION

AutoCAD SHX Text

BTT

AutoCAD SHX Text

JFS

X-CH-2

X-P X-P

X-P X-P

X-B X-B

X-DWH

X-COMPRESSOR

X-P-5

X-DDC CONTROL PANELS

P-2 VFD

P-1

480V-3Ø, 50HP

GENERATOR

T

J

4KVAR

EXIST.

"EMPD-01"

EXIST.

PNL "PP-02"

EXIST.

PNL "PP-4"

TS

FACP

EXIST.

PNL "EXCP-01"

T7

EXIST.

PNL "XFAP-01"

65KVAR

J

J CONTROL

PANEL

P-2

480V-3Ø, 50HPP-6

480V-3Ø, 10HP

P-3

480V-3Ø, 10HP

CH-1

480V-3Ø, 272.9A

J CONTROL

PANEL

35KVAR

EX

EX

EX

EX

EX

EX

EX

EX

EX EX

EX

VFD

VFD

P-1 VFD

(3) #10

(1) #10 GND

3/4" CND

PP-02-1PP-02-3 (3) #4

(1) #8 GND

1-1/4" CND(3) #4

(1) #8 GND

1-1/4" CND

(3) #10

(1) #10 GND

3/4" CND PP-02-5

PP-02-7

PP-02-9

EMPD-01-10

(4) #350KCMIL

(1) #4 GND

3-1/2" CND

P-6 COMBINATION STARTER

P-4 COMBINATION STARTER

P-3 COMBINATION STARTER

EF-1

120V-1Ø, 6.6 FLA

P-HC-1

120V-1Ø, 1/6HP

EF-2

120V-1Ø, 16.0 FLA

EX

EX EX

EX

U

EBCP-01-3

EBCP-01-18

EBCP-01-17

PNL "EBCP-01"

1 (3) #10

(1) #10 GND

3/4" CND

P-4

480V-3Ø, 5HP

ELECTRICAL KEY NOTES

BASE BID:

REUSE EXISTING CONDUIT FOR CONNECTION TO NEW EQUIPMENT. PROVIDE

AND INSTALL NEW WIRE.

ADD ALTERNATE:

PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR CONNECTION TO NEW

EQUIPMENT.

BASE BID:

REUSE EXISTING CONDUIT TO PULL BOX FOR CONNECTION TO NEW

EQUIPMENT. PROVIDE AND INSTALL NEW CONDUIT FROM PULL BOX TO

CHILLER. PROVIDE AND INSTALL NEW WIRE IN ENTIRETY.

ADD ALTERNATE:

PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR CONNECTION TO NEW

EQUIPMENT.

RE-CONNECT CAPACITOR TO NEW CHILLER.

EXISTING CIRCUIT IS UNKNOWN, NEW CIRCUIT NUMBER IS SHOWN FOR

LOAD PURPOSES. CONTRACTOR SHALL FIELD VERIFY EXISTING CIRCUIT,

FOR POTENTIAL RE-CONNECTION.

EXHAUST FAN TO RUN CONTINUOUSLY.

EXHAUST FAN SHALL BE CONTROLLED BY REFRIGERANT MONITOR. ROUTE

CIRCUIT THROUGH RIB RELAY CONTROLLED BY BAS SYSTEM. PROVIDE ALL

WIRE AND CONDUIT FOR A COMPLETE INSTALLATION.

M A

T R

I X

N MECHANICAL ROOM PLAN - POWER

SCALE: 1/4" = 1'-0"

0 1 5 10

AutoCAD SHX Text M

AutoCAD SHX Text S

AutoCAD SHX Text M

AutoCAD SHX Text S

AutoCAD SHX Text M

AutoCAD SHX Text S

AutoCAD SHX Text

PROJECT NUMBER

AutoCAD SHX Text

SHEET NUMBER

AutoCAD SHX Text

SHEET DESCRIPTION

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROJECT

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

CONSULTING ENGINEERS, INC

AutoCAD SHX Text

PHONE: (517) 487-2511

AutoCAD SHX Text Lansing, MI 48917

AutoCAD SHX Text 544 Cherbourg Drive

AutoCAD SHX Text administrator@matrixceinc.com

AutoCAD SHX Text 260150.00

AutoCAD SHX Text 05/18/2026

AutoCAD SHX Text

GARDNER INTERNATIONAL MAGNET SCHOOL

AutoCAD SHX Text

CHILLER REPLACEMENT

AutoCAD SHX Text

333 DAHLIA DR, LANSING, MI

AutoCAD SHX Text

ADDENDUM #1

AutoCAD SHX Text 05/19/2026

AutoCAD SHX Text

100% BID SET

AutoCAD SHX Text 05/18/2026

AutoCAD SHX Text Matrix Project No. 260150.00

AutoCAD SHX Text E-500

AutoCAD SHX Text

MECHANICAL

AutoCAD SHX Text

ROOM PLAN

AutoCAD SHX Text

POWER

AutoCAD SHX Text

BTT

GROUND BUS

PARTIAL RISER DIAGRAM - EXISTING

SCALE: N.T.S.

EXISTING "EMPD-01"

277/480V, 3Ø, 4W 3000A

3000A-3P

MAINUTILITY CO.

1000KVA M

UTILITY CO.

FROM UTILITY

0A

-3 P

PANEL

EXISTING

"PP-5"

277/480V 3Ø, 4W

300A, MLO

0A

-3 P

5A

-3 P

T

0A

-3 P

PANEL

EXISTING

"PP-2"

277/480V 3Ø, 4W

200A, MLO

0A

-3 P

PANEL

EXISTING

"PP-1"

277/480V 3Ø, 4W

200A, MLO

0A

-3 P

T

0A

-3 P

PANEL

EXISTING

"PP-4"

277/480V 3Ø, 3W

400A, MLO

0A

-3 P

PANEL

EXISTING

"PP-3"

277/480V 3Ø, 4W

600A, MLO

0A

-3 P

0A

-3 P

GROUND BUS

EXISTING "PP-02"

277/480V, 3Ø, 3W 400A

0A

-3 P

0A

-3 P

A-

3P

A-

3P

SPARE

A-

3P

SPARE

A-

3P

SPARE

0A

-3 P

0A

-3 P

A-

3P

SPARE

A-

3P

SPARE

A-

3P

SPARE

A-

3P

SPARE

G

KW

GENERATOR

TRANSFER SW.

30A/3P

3PH 4W

FUSED

KVA

T

PANEL

EXISTING

"EXCP-01"

120/208V 3Ø, 4W

100A, MLO

AUTOMATIC

30A

NORMAL

SOURCE

P-2

WEST COOLING

TOWER PUMP P-1 P-5 P-6

WEST

CHILLER-2

EAST

CHILLER-16

DISCONNECT AND REMOVE EXISTING EQUIPMENT. MODIFY ASSOCIATED

CONDUIT AND WIRE FOR NEW EQUIPMENT.

REMOVE EXISTING BREAKER, AND TURN OVER TO OWNER.

DEMOLITION NOTES

1 1 1

2 2 2

EXEX

EX

M A

T R

I X

AutoCAD SHX Text

PROJECT NUMBER

AutoCAD SHX Text

SHEET NUMBER

AutoCAD SHX Text

SHEET DESCRIPTION

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROJECT

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

CONSULTING ENGINEERS, INC

AutoCAD SHX Text

PHONE: (517) 487-2511

AutoCAD SHX Text Lansing, MI 48917

AutoCAD SHX Text 544 Cherbourg Drive

AutoCAD SHX Text administrator@matrixceinc.com

AutoCAD SHX Text 260150.00

AutoCAD SHX Text 05/18/2026

AutoCAD SHX Text

GARDNER INTERNATIONAL MAGNET SCHOOL

AutoCAD SHX Text

CHILLER REPLACEMENT

AutoCAD SHX Text

333 DAHLIA DR, LANSING, MI

AutoCAD SHX Text

ADDENDUM #1

AutoCAD SHX Text 05/19/2026

AutoCAD SHX Text

100% BID SET

AutoCAD SHX Text 05/18/2026

AutoCAD SHX Text Matrix Project No. 260150.00

AutoCAD SHX Text E-600

AutoCAD SHX Text

EXISTING RISER

AutoCAD SHX Text

DIAGRAM AND

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

SCHEDULES

AutoCAD SHX Text

BTT

GROUND BUS

PARTIAL RISER DIAGRAM - REVISED

SCALE: N.T.S.

EXISTING "EMPD-01"

277/480V, 3Ø, 4W 3000A

3000A-3P

MAINUTILITY CO.

1000KVA M

UTILITY CO.

FROM UTILITY

0A

-3 P

PANEL

EXISTING

"PP-5"

277/480V 3Ø, 4W

300A, MLO

0A

-3 P

5A

-3 P

T

0A

-3 P

PANEL

EXISTING

"PP-2"

277/480V 3Ø, 4W

200A, MLO

0A

-3 P

PANEL

EXISTING

"PP-1"

277/480V 3Ø, 4W

200A, MLO

0A

-3 P

T

0A

-3 P

PANEL

EXISTING

"PP-4"

277/480V 3Ø, 3W

400A, MLO

0A

-3 P

PANEL

EXISTING

"PP-3"

277/480V 3Ø, 4W

600A, MLO

0A

-3 P

0A

-3 P

GROUND BUS

EXISTING "PP-02"

277/480V, 3Ø, 3W 400A

0A

-3 P

0A

-3 P

A-

3P

A-

3P

A-

3P

A-

3P

SPARE

0A

-3 P

0A

-3 P

A-

3P

SPARE

A-

3P

SPARE

A-

3P

SPARE

A-

3P

SPARE

G

KW

GENERATOR

TRANSFER SW.

30A/3P

3PH 4W

FUSED

KVA

T

PANEL

EXISTING

"EXCP-01"

120/208V 3Ø, 4W

100A, MLO

AUTOMATIC

30A

NORMAL

SOURCE

P-2

WEST COOLING

TOWER PUMP

P-1

P-5

P-6

WEST

CHILLER-2

EAST

CHILLER-16

VFD VFD

ELECTRICAL KEY NOTES

CONTRACTOR SHALL PROVIDE AND INSTALL NEW BREAKER, TO MATCH

EXISTING TYPE.

1 1 1

P-4 P-3

EXEX

EX

M A

T R

I X

AutoCAD SHX Text

PROJECT NUMBER

AutoCAD SHX Text

SHEET NUMBER

AutoCAD SHX Text

SHEET DESCRIPTION

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROJECT

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

CONSULTING ENGINEERS, INC

AutoCAD SHX Text

PHONE: (517) 487-2511

AutoCAD SHX Text Lansing, MI 48917

AutoCAD SHX Text 544 Cherbourg Drive

AutoCAD SHX Text administrator@matrixceinc.com

AutoCAD SHX Text 260150.00

AutoCAD SHX Text 05/18/2026

AutoCAD SHX Text

GARDNER INTERNATIONAL MAGNET SCHOOL

AutoCAD SHX Text

CHILLER REPLACEMENT

AutoCAD SHX Text

333 DAHLIA DR, LANSING, MI

AutoCAD SHX Text

ADDENDUM #1

AutoCAD SHX Text 05/19/2026

AutoCAD SHX Text

100% BID SET

AutoCAD SHX Text 05/18/2026

AutoCAD SHX Text Matrix Project No. 260150.00

AutoCAD SHX Text E-601

AutoCAD SHX Text

REVISED RISER

AutoCAD SHX Text

DIAGRAM AND

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

SCHEDULES

AutoCAD SHX Text

BTT

260150.00 - LSD Gardner Elementary Chiller Replacement - Addendum #1 - Write-Up.pdf
260150.00 - LSD Gardner Elementary Chiller Replacement - Addendum #1 - Electrical.pdf
Sheets and Views
E300-26015000-24x36
E500-26015000-24x36
E600-26015000-24x36
E601-26015000-24x36

File details come from the government source that posted it. Updated .