AMERICAN EMBASSY NICOSIA
UNDERGROUND FUEL STORAGE TANKS
SOLICITATION NO. S-CY600-15-R-0034
QUESTIONS AND ANSWERS NO. 3
The following questions have been asked regarding this Solicitation:
1. Please advise if cathodic protection of the tanks is needed and also monitored?
The double skin tanks should have polyurethane coating in accordance with the EN12285 standard. Therefore, external cathodic protection and monitoring is not required.
2. The external (outside the building) overfill alarm will be exposed. There will be no means of securing it?
The external overfill alarm should be weather proof. Security of the overfill alarm is not an issue.