Specifications for a Once-Thru Class 10,000 Modular Isolation Room

The Modular Isolation Room shall be/include:

• An enclosure frame and self-supporting ceiling grid o Nominally 12’ x 14’ x 8’ o Extruded 6063-T5 aluminum o Gasketed for airtight connection

• Standard 2’ x 4’ ceiling tiles

• ABS adjustable sliding grill

• Wall panels, ceiling frames, and doors that are modular, shipped pre-assembled, and latch together for complete assembly

• Designed for single-pass (non-recirculating), positive pressure, Class 10,000 (ISO Class 7) standards

• Single swing door

• Fitted for panel inserts of non-outgassing PolySimTM

• HEPA fan filter units for Class 10,000/ISO 7

• LED lighting

Fan Filter Units (FFU) shall be/include:

• HEPA filter units 99.99% efficient on particles ≥ 0.3 μm

• Quiet operation tested to NC-40 noise rating (ANSI SI.31 – 1980 and ISO 3741-1975)

• Direct drive forward curve centrifugal design to minimize noise spectrum

• Bearing life design to 100k hours

• Electronically commutated motor (ECM) type, optimized for low energy usage

LED Lighting shall be/include:

• Class 100 T-8 energy efficient 100% sealed

• 4000K color temperature

• ≥ 90 Color Rendering Index (CRI)

• ≥ 100 lumens/W

• 80-90 foot-candles at worksurface (~ 36” above floor level)

• L80 B10 ≥ 60,000 hours

• 0 – 10V dimming compatible

In addition, the Contractor shall provide:

• Technical drawing, schematics, etc.

• Full assembly and installation

• Startup, balance, performance confirmation, cleaning, and training