SALIENT CHARACTERISTICS

DESCRIPTION OF REQUIREMENTS – Hardside Expandable Mobile Shelter

Size:

- Stowed Dimensions- No less than 96”H x 77.5L” x 77.5W” (with 8 ISO Corner Fittings)

- Deployed Dimensions- No less than 96”H x 252”L x 77.5”W

Color:

- Tan or Green

Modifications:

· Cutout, Frame & Reinforce (1) Each Opening Wide For Through the Wall A/C Unit. Note: Cutout shall be in one of the Expandable Wings as to Not Void CSC Plate. A/C Unit dimensions below.

· Fabricate & Install (1) Each Hinged, Gasket Cover Plate

HVAC:

· Supply (1) Each Window Air Conditioner w/Heat. Cool/Heat Operation Mode, Electric Heating Method, 12,000 BTU Cooling, 10,700 BTU Heating, 230VAC, 6 Ft. Power Cord, 4.9 Amps, 1062 Watts, 3.5 lb./hr. Dehumidification, R-410A Refrigerant, Dimensions: No larger than 26"W x 29"D x 18"H.

Electrical & Lighting:

· Load Center: Supply & Install (1) Each 100 Amps, 240 Volts, 60Hz, 1Ø

· Circuit 1- Lighting - Supply & Install (2) 4' Long, 4,400 Lumens, 40 Watt 120-277 VAC, LED Light Fixture.

· Circuit 2 - Supply & Install (3) Each 20A Breaker

· Circuit 3 - HVAC - Supply & Install (1) Each Dedicated Receptacle, 20 Amp Breaker.

· Supply & Install (1) Each Grounding Stud to Power Entry Location.

Delivery:

- FOB Destination; Delivery to South Burlington, VT 05403