S02_Attachment 1_PWS.xlsx

XLSX spreadsheet 22 KB Posted

Attached to
J063--Combined Synopsis Fire Suppression System Federal contract opportunity
Solicitation number
36C24122Q0187
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1

About this file

This combined synopsis/solicitation seeks quotations for fire alarm, fire suppression, and fire sprinkler system testing, maintenance, and repairs at four Department of Veterans Affairs locations in Connecticut. Required services include portable fire extinguisher inspections, kitchen wet suppression system inspections, central station monitoring, fire pump churn testing, fire and smoke damper inspections, and fire barrier inspections. Quotes are due by January 31, 2022 and the contract will be a firm-fixed price award set aside for Service-Disabled Veteran Owned Small Businesses. The solicitation includes a performance work statement, price schedule, and templates for past performance references and quality control plans.

View the file

Other files for this federal contract opportunity

Other files attached to J063--Combined Synopsis Fire Suppression System, newest first.
File Type Posted
36C24122Q0187 0003.docx DOCX document
VACTHS-Suppression Inventory.pdf PDF
VACTHS-Fire Alarm Inventories.pdf PDF
2022 IMT Contract RFI Questions with answers.docx DOCX document
36C24122Q0187 0002.docx DOCX document
VACTHS-Sprinkler Inventory.pdf PDF
36C24122Q0187 0001.docx DOCX document
S02_Attachment 4_QASP_.docx DOCX document
P09_PWS_(Rev-5).docx DOCX document
P07_Wage Determination_15-4119(Rev-18)_Newington.pdf PDF
P07_Wage Determination_15-4127(Rev-19)_West Haven_Orange.pdf PDF
S02_Attachment 3_Past Performance Worksheet.xlsx XLSX spreadsheet
S02_Price Schedule_Attachment 2_Line Items_.xlsx XLSX spreadsheet
36C24122Q0187.docx DOCX document
S02_Attachment 5_Limitation on Subcontracting.doc DOC document
Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

SimplexGrinnell Testing and Inspection Schedule Matrix - VA - Newington CT
Revised August 12, 2021
StandardDevicesOctNovDecJanFebMarAprMayJuneJulyAugSept
Sprinkler Systems
EP1Supervisory Signal DevicesQQQQ
EP2Valves tampers, Flows & PIV's (PIV's exercised annually)SASA
EP9Main DrainSASA
EP10Fire Department Equipment ConnectionsQQQQ
EP10Fire HydrantsA
EP11Fire Pump Flow TestA
NFPA25Dry Sprinkler SystemsA
Stand Pipes - Water Supply Piping ***FY2022
Fire Alarm Systems
EP3Duct Detectors/HVAC Systems ShutdownAVis
EP3Electromechanical Release Devices / Door HoldersAVis
EP3Heat DetectorsAVis
EP3Manual Fire Alarm Boxes / Pull StationsAVis
EP3Smoke DetectorsAVis
EP4Occupant Alarm Notification - A/V DevicesAVis
EP20Rolling Fire DoorsAVis
NFPA72Fire Alarm Panel incl BatteriesSASA
NFPA101Elevator Recall Smoke Detectors (lobbies and shafts)AVis
Suppression Systems
EP13Kitchen Wet Suppression System / Dry Chem SystemSASA
EP16Portable Fire ExtinguishersA
Monitoring
EP5SimplexGrinnell Central Station Monitoring *Tested Daily
Tested In-House
EP6Fire Pump Churn TestWWWWWWWWWWWW
EP18Fire & Smoke Dampers **FY22
Fire BarriersA
** Tested every four years.
*** Tested every five years.
Contractor PerformedPerformed In-House
WORK IS NOT COMPLETE UNTIL REPORTS HAVE BEEN SUBMITTED
SimplexGrinnell Testing and Inspection Schedule Matrix - VA - West Haven, CT
Revised August 12, 2021
StandardDevicesOctNovDecJanFebMarAprMayJuneJulyAugSept
Sprinkler Systems
EP1Supervisory Signal DevicesQQQQ
EP2Valves tampers, Flows & PIV's (PIV's exercised annually)SASA
EP9Main DrainSASA
EP10Fire Department Equipment ConnectionsQQQQ
EP10Fire HydrantsA
EP11Fire Pump Flow TestA
NFPA25Dry Sprinkler SystemsA
Stand Pipes - Water Supply Piping ***FY2022
Fire Alarm Systems
EP3Smoke DetectorsAVis
EP3Duct Detectors/HVAC Systems ShutdownAVis
EP3Electromechanical Release Devices / Door HoldersAVis
EP3Heat DetectorsAVis
EP3Manual Fire Alarm Boxes / Pull StationsAVis
EP4Occupant Alarm Notification - A/V DevicesAVis
EP20Rolling Fire DoorsAVis
NFPA72Fire Alarm Panel incl BatteriesSASA
NFPA101Elevator Recall Smoke Detectors (lobbies and shafts)AVis
Suppression Systems
EP13Portable Fire ExtinguishersMMMMMAMMMMMM
EP16Kitchen Wet Suppression SystemSASA
Monitoring
EP5SimplexGrinnell Central Station Monitoring *Tested Daily
Tested In-House
EP6Fire Pump Churn TestWWWWWWWWWWW
EP18Fire & Smoke Dampers **FY22
Fire BarriersA
** Tested every four years.
*** Tested every five years.
Contractor PerformedPerformed In-House
SimplexGrinnell Testing and Inspection Schedule Matrix - Orange Annex - Orange, CT
EP13Suppression Systems
EP16DevicesOctNovDecJanFebMarAprMayJuneJulyAugSept
Portable Fire ExtinguisherMMMMMAMMMMMM
Kitchen Wet Suppression SystemSASA
SimplexGrinnell Testing and Inspection Schedule Matrix - VA Errera Center - New Haven, CT
EP13Suppression Systems
EP16DevicesOctNovDecJanFebMarAprMayJuneJulyAugSept
Portable Fire ExtinguisherMMMMMAMMMMMM
Kitchen Wet Suppression SystemSASA
WORK IS NOT COMPLETE UNTIL REPORTS HAVE BEEN SUBMITTED
Notes:
A = Annual M = Monthly
SA = Semi-Annual
Q = Quarterly
W = Weekly
Vis = Visual Inspection Only
Fire Alarm Communicators (Dialers) are tested daily by Simplex Central Station Monitoring

Sheet2

Sheet3

File details come from the government source that posted it. Updated .