S02 - Attach Narrative Set 1 of 3.pdf

PDF 5 MB Posted

Attached to
Replace Electrical Panel Board in OR Federal contract opportunity
Solicitation number
36C24823R0073
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8

About this file

This sources sought notice requests capability statements from contractors interested in replacing an electrical panel board in an operating room at the Miami VA Medical Center. Contractors are asked to provide information on their company, bonding capacity, relevant past performance on comparable projects valued between $1 million and $5 million, and an assessment of whether the scope can be completed within the target price ceiling. Responses are due by December 20th and should not exceed eight pages. The project is to be awarded as a firm-fixed-price contract under FAR Part 15 to the responsible offeror whose proposal conforms to the solicitation and is most advantageous to the government considering technical merit and price. The North American Industry Classification System code for electrical contractors applies.

View the file

Other files for this federal contract opportunity

Other files attached to Replace Electrical Panel Board in OR, newest first.
File Type Posted
S02 - Attach Set of Drawings 4 of 4.pdf PDF
S02 - Attach Narrative Set 2 of 3.pdf PDF
S02 - Attach Set of Drawings 1 of 4.pdf PDF
S02 - Attach Set of Drawings 2 of 4.pdf PDF
S02 - Attach Set of Drawings 3 of 4.pdf PDF
P09 - Replace Electrical Panel Boards in OR with Dual Feed.docx DOCX document
S02 - Attach Narrative Set 3 of 3.pdf PDF
Attachment - Site Plan.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Isolated Power Planning Guide System Options for Isolated Power in Healthcare Facilities

32 3

Standards such as NFPA 99 and CSA Z32 require isolated power systems in all areas deemed “wet procedure locations” in healthcare facilities.

allows for critical systems to remain online in a latest standards and code requirements.

Bender provides advanced electrical safety technology to the healthcare industry, including:

to help reduce downtime and increase operational the system remains online customization and installation

PROTECT PATIENTS AND STAFF

With isolated power solutions from the leader in electrical safety.

SERVICES FOR ISOLATED POWER SYSTEMS

BENDER Services offer a wide range of benefits to ensure optimal performance of your Isolated Power Systems including:

Complete

System Centers for

The Joint documentation of Isolated Power Systems equipment factory trained and authorized technicians calculations of system impedence surfaces torques

Testing & Evaluation of your Isolated Power Systems includes:

BENDER’s Isolated Power System (IPS) Panel

BENDER’s LIM2010 Line Isolation Monitor

BENDER’s LT3000, An industry-leading testing instrument

4 5

Basic Configuration Includes required equipment for NFPA 99 compliance

Load Monitoring Includes capability of monitoring transformer load

Standard isolated power panel

System notes:

Minimum equipment required for compliance with NFPA 99 when panel is not installed

Panel configuration:

Sample part numbers:

Additional equipment:

d d i l t P

L1 L2

MK2000P-G1 remote indicator

Key system components:

Isolation transformer

MK2000CBM digital remote indicator

STW3 current transformer

Transformer load monitoring

L1 L2

Key additional components:System notes:

remote former load

Panel configuration:

Sample part numbers:

Additional equipment:

MK2000CBM remote indicator

6 7

Branch ground fault location Includes automatic indication of individual branches with ground faults

Branch load monitoring Adds load monitoring for individual branch loads

Fault location expansion kit

System notes:

Modular current transformer sizes allow for simple installation panel module systems / panels other rooms and central nurses'

Addition of ground fault location and digital remote station

MK2430 remote indicating station

Branch current monitoring expansion kit

Addition of branch load current monitoring

Key additional components:

System notes:

Automatically detects and with other equipment

ON

L1 L2

Key system components:

Included in panel beyond standard:

hardware

Sample part numbers:

Additional equipment:

ON

L1 L2

Included in panel beyond standard:

modules

Sample part numbers:

Additional equipment:

8 9

Central monitoring station Provides a central point for monitoring system alarms

Technician visualization & remote integration Includes advanced technical visualizations & communication

MK800RS (as shown) remote station

Addition of central monitoring station at nurses' desk

Communication expansion kit

Addition of technician monitoring station for all systems

Key additional components:

System notes:

from a centralized point

Key system components:

Included in panel beyond standard:

and hardware

Sample part numbers:

ON

L1 L2

System notes:

of systems point

CP907 HMI Station

ON

L1 L2

10 11

Complete systems for multiple rooms A complete solution for multiple operating rooms, centrally monitored

Sample part numbers:

Other equipment:

System notes:

personnel for all systems

L1 L2 L2 L1 L2

Modbus/TCP network

ON ON

ON

OR 1 OR 2 ICU 1 Nurse Desk Central Maintenance

14.3H.REV.0 | 11.2019 | © Bender Inc. All Rights Reserved.

Bender is located in 70 countries around the world

USA • Exton, PA +1 800.356.4266 • info@benderinc.com www.benderinc.com

México • Ciudad de México +55 7916.2799 • info@bender.com.mx www.bender.com.mx

Canada • Missisauga, ON +1 800.243.2438 • info@bender-ca.com www.bender-ca.com

Chile • Santiago de Chile +56 2.2933.4211 • info@bender-cl.com www.bender-cl.com

South America, Central America, Caribbean +1 484.288.7434 • info@bender-latinamerica.com www.bender-latinamerica.com

Spain • San Sebastián de los Reyes +34 9.1375.1202 • info@bender.es www.bender.es

Isolated Power Panels With LIM2010 Line Isolation Monitor

For Hospitals and Critical Care Areas

Technical Bulletin

NAE2092010 / 01.2012

Introduction

BENDER Isolated Power Panels are designed to provide isolated power to electrical systems in operating rooms and other critical areas. Designed in strict compliance with UL 1047, UL 1022, and UL 50, BENDER isolated power panels offer the most up-to-date technology for all isolated power distribution requirements.

Standard Features

Standard isolation power panels typically include:

Additional Features

Additional features available include:

Refer to the following pages for more information on these options.

Backbox

Front Trim surface-mounted panel boards, the front trim has the same dimensions as the enclosure.

Isolation Transformer

Isolation transformers are available with various primary and secondary single-phase volt-ages. See ordering information for available primary and secondary voltages.

Line Isolation Monitor of capacitive and resistive faults, including balanced, unbalanced, and hybrid faults. A self-test and self-calibration function is included.

BENDER EDS series module to create a ground fault location system. For more information, Loadcenter

Isolated Power Panels Isolated Power System with Line Isolation Monitor for hospitals and other critical care areas

Standard Isolated Power Panel

Features

Power Distribution: Loadcenter avail-able for either plug-in and bolt-on circuit

Mounting: Available for flush- or surface-mounted applications

Advanced technology:

isolation monitor features self-testing, self-calibration, and a wide variety of alarms including voltage, overload, and overtemperature monitoring

Outlets: Optional arrangement of recep-

Controller: Optional combination of PLC and remote / local controls for up to 12

Standards: Listed to UL 1047, the stan-dard for isolated power system equip-ment

Warranty: Industry-first 5 year warranty

1 - Stainless steel front trim

2 -

3 -

4 -

5 -

6 -

7 -

8 -

9 -

10 -

11 - Loadcenter

12 - Isolation transformer, single-phase

13 -

14 - LIM connector plate

15 -

Sample Outline: Standard Isolated Power Panel

Wiring Diagram: Standard Isolated Power Panel

IP Panels

A

B

C

C

A

D E

F

TOP

FRONT SIDE

A

B

C

C

A

D

F

E

TOP

FRONT SIDE

1 - Stainless steel front trim

2 -

3 -

4 -

5 -

6 -

7 -

8 -

9 -

10 -

11 - Loadcenter

12 - Isolation transformer, single-phase

13 -

14 - LIM connector plate

15 -

16 -

17 -

18 - Receptacle hat station

Isolated Power Panels with Receptacles and Ground Jacks

BENDER isolated power panels may have provisions for hospital grade power receptacles

Sample Outline: Isolated Power Panel with Optional Receptacles and Ground Jacks

IP Panels

1 - Stainless steel front trim

2 -

3 -

4 -

5 -

6 -

7 -

8 -

9 -

10 -

11 -

12 - Isolation transformer, single-phase

13 -

14 - LIM connector plate

15 - Control transformer

16 -

17 -

18 -

19 - Circuit contactors, 2P

20 -

Isolated Power Panels for X-Ray / Laser Equipment

Programmable Logic Controller (PLC) configured to a particular system‘s requirements. Control wiring from push-buttons, door switches, etc. are permanently wired into the input section. Signals or contact closures from the output section may be used to actuate contactors and to apply power to the

BENDER type XRM receptacle modules are recommended for use with this panel

Sample Outline: Isolated Power Panel with Circuit Control

IP Panels

A

B

C

D

F

E

C

A

TOP

FRONT SIDE

A complete ground fault location system for hospitals

L1

L2

Power Supply Class 2

GF Location Module EDS Series

MK2000 Series

>˚F

Line Isolation Monitor

LIM2010

MK2430

The BENDER Advantage remains online displays at both the location device and remote indicators

System Functions retro-fitting/upgrading available in many different shapes and types of ungrounded systems

Complete system including LIM, EDS ground fault location, and remote indication

Advantages:

location device and remote indicators

System functions:

Function a complete ground fault location system. After an alarm is device generates a test signal for a set period of time. Its the location of the ground fault. Current transformers placed of the fault is displayed on the EDS series via either a digital dis-play or an LED bar graph. Special remote indicators connected to the system may also display the location of the fault.

1 -w/ Vibration Mounts

2 -

3 -

4 -

5 -

6 - Sub-feed Lug

7 -

8 -

9 - Load Center

10 - Connector Plate, LIM

11 -

12 -

13 -

14 - EDS Units

15 -

Sample Outline: Panel w/ Load Monitoring and Integrated Fault Location System

IP Panels w/ Integrated Fault Location

Ground Fault Location Module an installed ground fault location system for ungrounded AC and DC systems. Once a ground fault is detected, the test pulse generated by the LIM2010 is scanned by the transformers may be connected to the device. A total of 90 EDS devices may be intercon-isolated power system can be identified within seconds.

EDS461-D

Module Types

Type Display Type Outputs EDS461-D LCD display 1 DPDT contact EDS461-L LED indication 1 DPDT contact

Ordering Information

BENDER’s complete Isolated Power Panels are comprise of four assembly types:

NOTE -

1 - Panel Interior kVA rating

2 - Panel Interior Primary voltage rating

3 - Panel Interior Secondary voltage rating

4 - Loadcenter/Panelboard Manufacturer

SB: Square D, Bolt-On

CB: Cutler-Hammer, Bolt-On

Option 1A:

5 - Quantity of ground jacks (0-8)

6 - Type of receptacle

7 - Quantity of receptacles

Option 1B:

8 - Type of control and indication individual receptacle modules with in-use lamps station located remotely

9 - Amperage per circuit*

10 - TOTAL quantity of controlled circuits (01-12)

11 - Quantity of SIMULTANEOUSLY Active circuits*

H1: One H4: Four

I P

1 5 A- A 2 3

S P 4 5

S R 6 7

P N- A 2

Option 1A Option 1B

0 5 H 2

STEP 1: Interior

Base Information (required):

Select EITHER Option 1A,1B OR 1C (leave blank if not required):

Note*: For Option 1B, the amperage per circuit and number of simultaneously hot circuits must be rated properly in accordance with the secondary vol-

IP Panels

LM-

10 11 12 13

OPTION 1: Interior Options

Option 1C Option 2

Option 1C:

12 - Fault Location System (EDS) Type

X M

0 5 B A 2 3

Backbox / Front Trim Combinations for IP Panels kVA Backbox Size (H x W x D)

Front Trim Size (H x W) Mounting Supports

Option 1A Supports Option 1B

Supports

EDS

Backbox Part Number

Front Trim Part Number

3, 5 43" x 24" x 6" 45" x 26" Flush No No No B432406 T4526

7.5, 10 43" x 24" x 8" 45" x 26" Flush No No No B432408 T4526

15 51" x 30" x 12" 53" x 32" Flush No Yes No B513012 T5332

25 51" x 30" x 14" 53" x 32" Flush No Yes No B513014 T5332

3, 5, 7.5, 10 48" x 24" x 8" 50" x 26" Flush Yes No No B482408 T5026R

3, 5, 7.5, 10 48“ x 24“ x 8“ 50“ x 26“ Flush No No Yes B482408 T5026E

3, 5 43" x 24" x 6" 43" x 24" Surface No No No B432406S T4324

7.5, 10 43" x 24" x 8" 43" x 24" Surface No No No B432408S T4324

15 51" x 30" x 12" 51" x 30" Surface No Yes No B513012S T5130

25 51" x 30" x 14" 51" x 30" Surface No Yes No B513014S T5130

3, 5, 7.5, 10 48" x 24" x 8" 48" x 24" Surface Yes No No B482408S T4824R

3, 5, 7.5, 10 48“ x 24“ x 8“ 50“ x 26“ Surface No No Yes B482408S T4824E

STEP 2: Transformer Contact your local BENDER sales office for additional or custom configurations.

2 - Primary voltage of transformer

3 - Secondary voltage of transformer1 - kVA of transformer

OPTION 2: Additional Monitoring Features

13 - Transformer Load Monitoring

[ ]: Feature not required

*Note:

IP Panels

STEPS 3 & 4: Backbox and Front Trim

Dual Isolated Power Panels Dual Voltage and Dual System Isolated Power Panels for hospitals and other critical care areas

Dual Output Voltage Isolated Power Panel

Introduction

BENDER’s dual voltage isolated power panels provide two different output voltages

Ideally suited for:

receptacles

Standard Features: Dual Output Voltage Panel

Dual output voltage isolated power panels provide two separate voltage outputs using a single isolation transformer. A standard dual output voltage panel consists of the following:

Standard Features: Dual System Panel

Dual system panels provide two separate voltage outputs from two isolation transformers.

enclosure. A standard dual system panel consists of the following:

Features

Power Distribution: Loadcenters available for either plug-in or bolt-on cir-

Mounting: Available for flush- or surface-mounted applications

Advanced technology:

isolation monitor features self-testing, self-calibration, and a wide variety of alarms including voltage, overload, and overtemperature monitoring

Standards: Listed to UL 1047, the standard for isolated power system equipment

Warranty: Industry-first 5 year warranty

Dual System Isolated Power Panel

File details come from the government source that posted it. Updated .