Required Minimum Specifications.pdf
PDF 124 KB Posted
- Attached to
- Turbine Chilled Water Coils Federal contract opportunity
- Solicitation number
- 12505B21Q0205
View the file
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Turbine Chilled Water Coils
Required Minimum Specifications
The USDA Facilities Engineering Unit (FEU) has a requirement for 2 each turbine chilled water coils for use in the USDA turbine.
The coils required must adhere to the following specifications:
A. Unit fins must be 0.010 thick aluminum B. Unit headers must be 4” type M copper.
C. Unit connections must be 4” steel 150 lb RFSO flanges D. Unit casing coils must be 304L SST. Weld nuts 18-8 SST hardware 18-8 SST E. Unit joints must be Silver Brazed F. Unit designed pressure and temperature must be 200psi/375 F G. Unit welds must all be passivated.
H. Unit header enclosure must be 16 ga. 304L SST w/ .125 x .750 Poron Gasket I. Unit must be air tight to 10” WC J. Unit must have 5/8’ CU tubes K. Unit shall include warranty L. Qty – 2 each
The coils must be delivered onsite within 90 days of date of award.
Deliver to: USDA 1920 Dayton Avenue Bldg. 24 Ames, IA 50010
| The USDA Facilities Engineering Unit (FEU) has a requirement for 2 each turbine chilled water coils for use in the USDA turbine. |
| The coils required must adhere to the following specifications: |
File details come from the government source that posted it. Updated .