P09 ATTACHMENT A.docx

DOCX document 42 KB Posted

Attached to
H246--Water Systems Testing and Treatment Federal contract opportunity
Solicitation number
36C24221Q0366
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

View the file

Other files for this federal contract opportunity

Other files attached to H246--Water Systems Testing and Treatment, newest first.
File Type Posted
S06 36C24221Q0366 0006.docx DOCX document
P09 Pricing Sheet NJ Water Treatment FINAL-Amend.xlsx XLSX spreadsheet
36C24221Q0366 0006_1.docx DOCX document
36C24221Q0366 0005_1.docx DOCX document
AMEND 36C24221Q0366 0005.pdf PDF
36C24221Q0366 0003.docx DOCX document
36C24221Q0366 0002.docx DOCX document
36C24221Q0366 0001.docx DOCX document
36C24221Q0366.docx DOCX document
P09 Pricing Sheet NJ Water Treatment FINAL (1).xlsx XLSX spreadsheet
SAM-DESCRIPTION.docx DOCX document
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ATTACHMENT A

I CHEMICALS

EAST ORANGE

COOLING TOWERS

1
Corrosion Inhibitor

Name

Generic Type

Active Components, % ppm Product in Circulating Water

Dosage, lbs/1000 Gallons of Bleed

Test type and limits

Delivered cost/lb

Package size

2
Biocide

Name

Generic Type - Liquid Bromine

Active Components, % ppm Product in Circulating Water

Dosage, lbs/1000 Gallons of Volume

Dosage, lbs/1000 Gallons of Bleed

Frequency of application

Test type and limits

Delivered cost/lb

Package size

3
Biocide

Name

Generic Type

Active Components, % ppm Product in Circulating Water

Dosage, lbs/1000 Gallons of Volume

Dosage, lbs/1000 Gallons of Bleed

Frequency of application

Test type and limits

Delivered cost/lb

Package size

D-1

CLOSED SYSTEMS

CHILL WATER

Corrosion Inhibitor

Name

Generic Type

Active Components, % ppm Product in Circulating Water

Dosage, lbs/1000 Gallons of Volume

Test type and limits

Delivered cost/lb

Package size

STEAM SYSTEMS

Scale Control

Generic Type

Active Components, % ppm Product per ppm Hardness ppm Product in Boiler

Dosage rate, lbs per Million lbs Feedwater

Test type and limits

Delivered cost/lb

Package size

Oxygen Scavenger

Generic Type

Active Components, % ppm Product per ppm Oxygen ppm Product per ppm Residual

Dosage rate, lbs per Million lbs Feedwater

Test type and limits

Delivered cost/lb

Package size

7
Alkali

Generic Type

Active Components, % ppm Product per ppm Boiler Alkalinity ppm Product per ppm Residual

Dosage rate, lbs per Million lbs Feedwater

Test type and limits

Delivered cost/lb

Package size

8
Neutralizing Amine

Generic Type

Active Components, % ppm Product per ppm Feedwater Alkalinity

Dosage rate, lbs per Million lbs Feedwater

Test type and limits

Delivered cost/lb

Package size

LYONS

COOLING TOWERS

9
Corrosion Inhibitor

Name

Generic Type

Active Components, % ppm Product in Circulating Water

Dosage, lbs/1000 Gallons of Bleed

Test type and limits

Delivered cost/lb

Package size

10
Biocide

Name

Generic Type - Liquid Bromine

Active Components, % ppm Product in Circulating Water

Dosage, lbs/1000 Gallons of Volume

Dosage, lbs/1000 Gallons of Bleed

Frequency of application

Test type and limits

Delivered cost/lb

Package size

11
Biocide

Name

Generic Type

Active Components, % ppm Product in Circulating Water

Dosage, lbs/1000 Gallons of Volume

Dosage, lbs/1000 Gallons of Bleed

Frequency of application

Test type and limits

Delivered cost/lb

Package size

CLOSED SYSTEMS

12
MAIN CHILL WATER

Corrosion Inhibitor

Name

Generic Type

Active Components, % ppm Product in Circulating Water

Dosage, lbs/1000 Gallons of Volume

Test type and limits

Delivered cost/lb

Package size

13
CHILL WATER

Corrosion Inhibitor

Name

Generic Type

Active Components, % ppm Product in Circulating Water

Dosage, lbs/1000 Gallons of Volume

Test type and limits

Delivered cost/lb

Package size

14
HOT WATER

Corrosion Inhibitor

Name

Generic Type

Active Components, % ppm Product in Circulating Water

Dosage, lbs/1000 Gallons of Volume

Test type and limits

Delivered cost/lb

Package size

STEAM SYSTEMS

15
Scale Control

Generic Type

Active Components, % ppm Product per ppm Hardness ppm Product in Boiler

Dosage rate, lbs per Million lbs Feedwater

Test type and limits

Delivered cost/lb

Package size

16
Oxygen Scavenger

Generic Type

Active Components, % ppm Product per ppm Oxygen ppm Product per ppm Residual

Dosage rate, lbs per Million lbs Feedwater

Test type and limits

Delivered cost/lb

Package size

17
Alkali

Generic Type

Active Components, % ppm Product per ppm Boiler Alkalinity ppm Product per ppm Residual

Dosage rate, lbs per Million lbs Feedwater

Test type and limits

Delivered cost/lb

Package size

18
Neutralizing Amine

Generic Type

Active Components, % ppm Product per ppm Feedwater Alkalinity

Dosage rate, lbs per Million lbs Feedwater

Test type and limits

Delivered cost/lb

Package size

II BASIS FOR CALCULATIONS

East Orange

Lyons

Tons
3,650

3,300

Recirc Rate, gpm
10,950

9,900

Bleedoff Rate, gpy
2,200,000

1,500,000

Cycles

Winter Volume, gal
20,000
Summer Volume, gal
23,000

10,000

CLOSED SYSTEMS

Chill volume, gal
53,600

110,000

Chill makeup, gpy
6,100

350,000

Hot volume, gal

7,450

Hot makeup, gpy

3,725

STEAM SYSTEMS

Steam produced, lbs/yr
107,000,000

137,200,000

Makeup, gal/yr
6,423,000

8,768,000

% Makeup
50
Makeup Temperature, o F
212+

212+

Feedwater hardness, ppm
< 1

< 1

Cycles
25
Operating period, days
365

III CONTROL LIMITS

OPEN COOLING WATER SYSTEMS

East Orange
Lyons

Total Hardness, ppm as CaCO3

Calcium Hardness, ppm as CaCO3

Total Alkalinity, ppm as CaCO3

Conductivity, micromhos

Inhibitor, ppm as Constituent pH

Total Plate Count, Colonies/ml
< 10,000
< 10,000
Corrosion Rate, mpy
< 1 MS, <.2 Cu
< 1 MS, <.2 Cu
Lonelier Index (LSI)
<3
<3

Cycles

Other

HOT WATER SYSTEMS

Total Alkalinity, ppm as CaCO3

Conductivity, micromhos

Inhibitor, ppm as Constituent

Corrosion Rate, mpy
<1 MS, <.1 Cu
<1 MS, <.1 Cu

CHILL WATER SYSTEMS

Total Alkalinity, ppm as CaCO3

Conductivity, micromhos

Inhibitor, ppm as Constituent

Corrosion Rate, mpy
<1 MS, <.1 Cu
<1 MS, <.1 Cu
Total Plate Count, Colonies/m1
<1,000
<1,000
Anaerobic Bacteria
Nil
Nil

STEAM SYSTEMS

Manhattan
St. Albans
Softener Hardness, ppm as CaCO3
< 0.05
< 0.05
Softener Conductivity, micromhos
< 5
< 5
Condensate pH
7.6-8.6
7.6-8.6
Condensate Conductivity, micromhos
< 20
< 20
Feedwater Hardness, ppm as CaCO3
< 0.1
< 0.1
Feedwater Iron, ppm as Fe
< 0.02
< 0.02
Feedwater Copper, ppm as Cu
< 0.015
< 0.015
Feedwater pH
8.8-9.6
8.8-9.6

Boiler Water

M Alkalinity, ppm as CaCO3
200-800
200-800
Phosphate, ppm as PO4
30-50
30-50

Polymer. Ppm

Sulfite, ppm as SO3
30-50
30-50
Conductivity, micromhos (unneutralized)
5000-6000
5000-6000

Conductivity, micromhos (neutralized)

Cycles on Makeup/Feedwater
25-50
25-50

IV RAW WATER ANALYSIS

Newark
East Orange
East Orange Tower Makeup
Lyons

Total Hardness as CaCO3

Calcium Hardness as CaCO3

Total Alkalinity as CaCO3

Conductivity, micromhos

Silica, as SiO2

Sulfate as SO4

Chloride as NaCl

Other

V

Year 1
Year 2
Year 3
Year 4
Year 5

East Orange

Tower Inhibitor

Biocide

Biocide

Chill Water Inhibitor

Scale Control

Oxygen scavenger

Alkali

Amine

Lyons

Tower Inhibitor

Biocide

Biocide

Main Chill Water Inhibitor

Chill Water Inhibitor

Hot Water Inhibitor

Scale Control

Oxygen scavenger

Alkali

Amine

Sub Total Chemicals

Equipment

Labor

Other

Total

File details come from the government source that posted it. Updated .