NIFC_Access_Control_115-NWS__Notes_29Mar2022.pdf
PDF 184 KB Posted
- Attached to
- NIFC 115 FWS ACCESS CONTROL Federal contract opportunity
- Solicitation number
- 140L3722R0015
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Site_Visit_Roster_0001.pdf | ||
| Sol_140L3722R0015_Amd_0001.pdf | ||
| NIFC_115_NWS_Access_Control_Questions_0001.pdf | ||
| NIFC_Access_Control_115-NWS_Prologue.pdf | ||
| SF1442_Example_Completion-Instructions.pdf | ||
| B03_WD_ID20220025_02-25-2022.pdf | ||
| NIFC_Access_Control_115-NWS_11X17_Plans.pdf | ||
| CertificationVaccination.pdf | ||
| NIFC_Access_Control_115-NWS_Bid_Schedule.pdf | ||
| NIFC_Access_Control_115-NWS_Specifications.pdf | ||
| Sol_140L3722R0015.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
United States Department of the Interior
BUREAU OF LAND MANAGEMENT
Fire and Aviation 3833 S Development Ave
Boise, Idaho 83705-5354
March 29, 2022
NIFC 115-NWS ACCESS CONTROL
ADDITIONAL ACCESS CONTROL REQUIREMENTS
The following information is included as part of the solicitation for this project.
1. Plan Sheet E001: ACCESS CONTROL NOTES shall be modified to read as follows:
WHERE NEW ACCESS CONTROL IS NOTED ON DRAWINGS, PROVIDE AND INSTALL ALL
REQUIRED COMPONENTS, CONDUIT, AND CABLING TO ADD ACCESS CONTROL AND
POSITION MONITORING FOR DOORS. ALL HARDWARE, SOFTWARE, AND FIRMWARE
SHALL BE FULLY FICAM (FEDERAL IDENTITY CREDENTIAL AND ACCESS MANAGEMENT)
CAPABLE. INCLUDING INSTALLATION, PROGRAMMING AND INTEGRATION OF PAM
(PHYSICAL ACCESS MODULE) FOR FULL FICAM COMPLIANCE.
Note 2: ACCESS CONTROL CARD READERS SHALL BE SEAMLESSLY
COMPATIBLE WITH EXISTING CENTRAL AMAG SYSTEM AND CONTROLLERS.
CARD READERS SHALL BE EITHER HID IC-RKCL40 OR VERDIT STEALTH DUAL,
PIV CLASS CONTACT/CONTACTLESS PLUS PIN, FICAM COMPLIANT, OR EQUAL.
CARD READERS SHALL BE CAPABLE OF READING PIV/CAC AND 4K MIFARE
DESIRE CARDS AND BE CAPABLE OF CARD READER COMMANDS.
Note 4: TECHNICIAN SHALL PROGRAM EXISTING CAMPUS ACCESS CONTROL
SYSTEM TO ACCEPT NEWLY CONTROLLED DOORS. COORDINATE DOOR
SCHEDULES WITH GOVERNMENT. EXISTING SYSTEM IS LAN BASED CLIENT
SERVER, AMAG SYMMETRY PROFESSIONAL HOMELAND SECURITY EDITION
VERSION 9.3.25.
2. Plan Sheet E001: DETAIL 1, ACCESS CONTROL DOOR WIRING DIAGRAM, add the following note at the card reader: MAXIMUM DISTANCE TO CENTER OF CARD READER
FROM DOOR IS 12”, MINIMUM DISTANCE TO EDGE OF CARD READER FROM DOOR
IS 6”.
3. Plan Sheet E101: PLAN NOTE 7 shall be modified to read as follows:
Note 7. DISCONNECT AND REMOVE EXISTING AMAG ACCESS CONTROL
CABINET, CONTROLER AND ASSOCIATED ACCESSORIES. PROVIDE AND
INSTALL NEW LIFESAFTEY POWER INTEGRATED POWER SUPPLY ENCLOSURE
E6A1, 12A/12V or 10A/24V CABINETRY. PROVIDE NEW AMAG DOOR ENTRY
CONTROLLER M4000-DEC4 AND PVC-PAM-BOARD TO INTEGRATE WITH
EXISITNG M4000-DBB. REINSTALL ALL EXISITNG DOOR CONTROLLERS AND
PAM BOARDS TO PROVIDE A WORKING FICAM SYSTEM.
INSTALLER TO PROVIDE ADEQUATE BATTERY BACKUP TO RUN ALL
HARDWARE CONNECTED TO EACH CONTROLLER FOR 4 HOURS, WITH
MINIMUM 2 X 8AH 12V AGM BATTERIES. CALCULATIONS TO DETERMINE
PROPER BATTERY CAPACITY ARE THE RESPONSIBILITY OF INSTALLER.
4. Plan Sheet E101: PLAN NOTE 9 shall be modified to read as follows:
Note 9. PROVIDE PLENUM-RATED CAT6 CABLE FROM ACCESS CONTROLLER
AND PAM TO LAN SWITCH. LAN SWITCHES ARE LOCATED A MAXIMUM OF
15FT FROM NODE CABINET. COORDINATE WITH GOVERNMENT FOR
TEMINATION ON PATCH PANEL.