001 - Clarifications and Additional Drawings 09-10-2020.pdf
PDF 20 MB Posted
- Attached to
- Design and Install Confined Space and Fall Protection Systems Federal contract opportunity
- Solicitation number
- NFFM7023-20-02934
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 02d Ref dwg SLA 10- Hatch.pdf | ||
| 03 Davis-Bacon Act WD NJ20200037 - January 31 2020.pdf | ||
| 01 RFP - NFFM7023-20-02934 Confined Space and Fall Protection Systems.pdf | ||
| 02c Ref dwg LE-114.pdf | ||
| 02a Ref dwg LC-103.pdf | ||
| 02b Ref dwg LC-109.pdf | ||
| 02e Confined Space and Fall Protection Equipment List.xlsx | XLSX spreadsheet | |
| 02 SOW - NFFM7023-20-02934 Confined Space Protection System.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Questions / Answers / Clarifications / Changes New Closing Date/Time: Tuesday, 9/15/2020 at 2:00 p.m. EST
1. The RFP appears to indicate that a new footing/pad may be necessary for the new fall protection installation(s), and that the footing/pad dimensions should be minimum 8 ft long x 4 ft wide x 8 in. (See change note) thick with welded wire mesh reinforcement and 3,500 psi cure strength. It is not clear however in the RFP or SOW where this footing would be located. Can you confirm the approximate location(s) in relation to the existing hatches and surrounding features? Seawater pump pit. Contractor to determine best location coordinated with COR for approval. From the site walk, we believe this is only going in the southeast corner of the seawater pump station but would like to be sure. For the cooling tower pump pit vault in particular, there does not appear to be enough space around the three existing hatch locations to install a new footing without modifications to either the existing mechanical/electrical equipment, or the site’s perimeter security fencing. No pad required at the cooling locations. Note: Change to Concrete Pad thickness to 10” versus 8”.
2. It doesn’t appear the necessary details are noted in the drawings provided to understand the engineering efforts especially related to anchoring. Are additional design or construction as built drawings available for the two pad/vault locations (seawater pump station & cooling tower pump pit) beyond the site layout that was provided? We see on drawing LC103 that there is a sub note to “see dwg LM104” which we believe shows more detailed information for the cooling tower pump pit vault(s). Similarly, the architectural drawing A1 for the seawater pump station indicates an architectural scale, however due to the file type/scan condition, this scale cannot be used to confirm the vault dimensions. This information may help to determine if new footings/pads will be required, or if the new fall protection base plates can be anchored to the existing pads/vaults. The thickness of the existing roof slabs is important for embedment requirements, for both the cooling tower and sea water vaults. See additional drawings LM104, LM110. LS108. Scale off the drawings at the contractors risk. See sections Part 1, 1.08 and Part 3, 3.01, 3.10.
3. The core mount sleeves noted on the material spreadsheet require 9-1/4 inch embedment depth. Please confirm if the existing concrete thickness where these sleeves will be installed is greater than 9-1/4 inches. Concrete is 8” thick. See change from core mounted sleeves to floor mount sleeve on updated equipment list (attached)
4. The RFP CLIN table indicates a licensed engineer must approve all installations to local standards, however the SOW indicates a qualified engineer must approve all installations to local standards. There are differences between qualified engineers and licensed engineers. Please clarify engineering requirements for this solicitation. Qualified engineers may be certified to design and inspect fall protection systems, however may not be licensed professional engineers with the state of New Jersey. Licensed professional engineers for this scope of work may include licensed PE for civil and/or structural engineering.
Licensed Engineer is required.
5. The SOW also indicates that the facility superintendent, safety supervisor, and COR will inspect the installations. Is the intent to have a final site walk/inspection with the noted facility personnel as well as contractor representative and engineer (pending confirmation of qualified vs. licensed)? We ask to better understand onsite visitation/inspection efforts and coordination. Government reserve the right to inspect and access at anytime during construction or installation. Final walk through shall include the general contractor.
6. Are signed/sealed professional engineer drawings required for shop drawings and/or as-builts? Will the facility require civil/survey drawings to show locations of the new fall protection equipment, areas of work, etc.? Final drawings shall require a signed /seal licensed engineers stamp. Civil/survey drawing showing locations not required.
7. The equipment spreadsheet does not appear to indicate make/model/type of anchoring hardware for the fall protection installation. Does the facility have specifications for anchoring hardware which should be used? Per the contractors engineer’s requirements and accordance to manufacture instruction.
8. The equipment spreadsheet also appears to have two columns noting different quantities for the materials. Please confirm which column should be used, and/or if the intent is to provide the sum of both columns for each item noted. See new updated Equipment List.
9. The SOW notes that the contractor needs to supply restroom facilities. There are similar solicitations for the same site which note that restroom facilities will be provided by the NOAA facility. Please confirm. Per section 1.06 Use of Premises
10. Will NOAA facility personnel require training by the selected contractor for equipment use/operation? If so, how many staff members will need to be trained, and will the training require practical training, i.e. donning/doffing safety equipment and test usage, or will review of the equipment operation and maintenance manuals suffice? Training of personnel not required. Review of equipment operation and manuals will suffice.
11. What additional coordination is required (if any) in addition to notification of intent to enter the vaults, submittal of safety plan, and execution of contractor’s confined space entry permit? Will equipment isolation/lockout/tagout be required for any of the installation locations? We understand the vaults are entered and used daily by facility personnel.
Access to the vaults may need to be limited or excluded during installation of the fall protection equipment. Are there specific time frames when access to the vaults is not required, and the selected contractor needs to schedule work for? Under normal circumstances access to the vault can be temporarily limited. Access to the vault shall not be restricted over weekends or holidays. Coordinated with COR in advance if access is anticipated to be restricted more than 24 hours.
12. In addition to the sexual assault training noted in the RFP, is any additional NOAA site training required for the selected contractor? AGO to supply link (AGO requirement)
13. The SOW notes that the storage boxes should be watertight, lockable, and mountable.
Please confirm the approximate minimize of the storage boxes. Are there any preferred materials of construction, or any materials that should not be used? Should the boxes be mountable to a vertical face/wall or to a floor/pad? And please confirm if they should be lockable. Watertight, lockable, and mountable, weather tight, corrosion resistance.
Approximately 30” D X 27” X 72”w. 1/8” Thick , military grade aluminum, semi-truck tough locks, a bulletproof full-length piano hinge, and a rugged powder coat finish that'll stand up to the weather. Similar to Dock-Boxes products or approved equal.
14. Please confirm if both the sea water vault and cooling tower vault locations have facility electric/power outlets (15 amp minimum) and water source/hose bibs within 100 feet of the work areas. Sea water vault Yes/Yes Cooling tower vault yes/yes
15. Are drawings available for the cooling tower vault and hatches which show the existing interior access, mechanical, electrical and structural features? Are drawings available which show arrangement of the hatches at both the cooling tower vault as well as the seawater vault in addition to their door open/shut orientation? No there are no available drawings depicting this.
16. The material spreadsheet appears to indicate 3-4 options for davit mast anchoring mounts.
The options are noted for use at the sea water vault and include models DH-7SS, DH- 9SS, and DH-20SS. A model DH-AP-12 is also noted for use at both the sea water vault and cooling tower vault locations. Please confirm if pricing for all materials with their noted quantities (quantity columns to be confirmed) should be included in the lump sum CLIN bid value? Please confirm which mount type should be used at each hatch location.
Individual pricing for each item is not required. See updated equipment list.
17. Drawings A1, LC109, and LE114 appear to show the 2 northern hatches at the seawater vault straddle a total of 4 vaults beneath. The RFP and SOW indicate that fall protection is to be installed in 2 locations at the seawater pump station; the first at Aeration Vault #1, and the second at Aeration Vault #2. From the drawings noted it appears that the western hatch straddles both Aeration vaults, and that the eastern hatch straddles a Decant vault and a Deaeration vault. Please confirm if the intent is to provide a single means of fall protection for both the eastern as well as western hatch, or if two means of fall protection are to be installed at just the western hatch (for the two aeration vaults). Please confirm no fall protection will be installed at the southeastern hatch at the saltwater pump station vault. See updated equipment list, additional drawings and photo’s (attached).
SANDY HOOK LOCATION SANDY HOOK SYSTEM GENERIC PART DESCRIPTION
Units to be Purchased
MILLER
PART DESCRIPTION
MILLER
PART NUMBER
MILLER
(Weight lbs)
MILLER
Proof Load Rating
(Weight lbs)
MILLER
Rated
Capacity/Working Load (Weight lbs)
Seawater Pump Station - Mechanical Vault FALL PROTECTION - Ladder Ladder Climbing Safety System 1
Miller GlideLoc Ladder Climbing Safety Kit (Rail) or Miller GlideLoc Verticle Height Access Ladder System Kit (Rail) GS0020 (Kit) 310
Seawater Pump Station - Mechanical Vault FALL PROTECTION - Ladder
Ladder Climbing Safety System:
Fall Arrester 4 Comfort2 GlideLoc Fall Arrester TBD 1350 (6kN) 310
Seawater Pump Station - Mechanical Vault FALL PROTECTION - Ladder
Ladder Climbing Safety System:
Shaft Entry Device (for use in entry/exit) 1
Millert GlideLoc Ladder Climbing Safety System (Rail): Shaft Entry Device (for use in entry/exit)
17065 (Stainless Steel) 310
Seawater Pump Station - Mechanical Vault FALL PROTECTION - Ladder
Ladder Climbing Safety System:
Shaft Entry Device Coupling (to allow use of shaft entering device) 1
Miller glideLoc Ladder Climbing Safety System (Rail): Shaft Entry Device Coupling (to allow use of shaft entering device)
16191 (Stainless Steel) 310
Seawater Pump Station - Mechanical Vault FALL PROTECTION - Ladder
Ladder Climbing Safety System:
Rotary Exit/Swivel Extension (for use in entry/exit) 1
Milller GlideLoc Ladder Climbing Safety System (Rail): Rotary Exit/Swivel Extension (for use in entry/exit) TBD 310
Seawater Pump Station - Mechanical Vault FALL PROTECTION - Ladder
Ladder Climbing Safety System:
Accessories 2
Miller GlideLoc Ladder Climbing Safety System (Rail):
Rigid End Stop 11634 310
Seawater Pump Station - Mechanical Vault CONFINED SPACE - Rescue
Davit System - Fixed Base Option (Core Mount Sleeve) 2
DuraHoist Confined Space Satety System, Fixed Base. Core Mount Sleeve
DH-9SS (304
Stainless Steel) 8
90,000 in-lbs (10,200 N.m) 450
Purchased
MILLER
PART DESCRIPTION
MILLER
PART NUMBER
MILLER
(Weight lbs)
MILLER
Proof Load Rating
(Weight lbs)
MILLER
Rated
Capacity/Working Load (Weight lbs)
Seawater Pump Station - Mechanical Vault CONFINED SPACE - Rescue
Davit System - Fixed Base Option (Floor Mount Sleeve) 7
DuraHoist Confined Space Safety System, Fixed Base. Floor Mount Sleeve
DH-7SS (304
Stainless Steel) 13.5
90,000 in-lbs (10,200 N.m) 450
ALL LOCATIONS (Seawater Pump Station Vault and Tanks, Cooling Tower Pump/Motor Vault, Make-up Water Tank, Strainer Tank) CONFINED SPACE - Rescue
Davit sytem - Fixed Base Accessory (Flush Floor Mount Sleeve, Security/Weather Cap) 12
DuraHoist Flush Floor Mount Sleeve, Security/Weather Cap
DH-10SS
(Stainless Steel) 1.2 N/A N/A
ALL LOCATIONS (Seawater Pump Station Vault and Tanks, Cooling Tower Pump/Motor Vault, Make-up Water Tank, Strainer Tank)
CONFINED SPACE - Rescue FALL PROTECTION Davit System - Fall Protection, Rescue 2
Miller DuraHoist™ One-Piece Adjustable Mast (12 inch - 29 inch Mast Offset)
DH-3
(12-in. - 29-in.
Offset) 29
3000 (13kN), 3600 (16kN), 5000 (22kN)
Depending on Pin/Winch/Hoist Position 450
Seawater Pump Station - Mechanical Vault
CONFINED SPACE - Rescue
MATERIAL HANDLING
Davit System - Fall Protection, Rescue and Material Handling 1
Miller DuraHoist™ Two-Piece Adjustable Upper Mast (30 inch - 48 inch Mast Offset)
DH-23
(30-in. – 48-in.
Offset) 29
1800 (8kN) Independent of
Pin/Winch/Hoist Position 450
ALL LOCATIONS (Seawater Pump Station Vault and Tanks, Cooling Tower Pump/Motor Vault, Make-up Water Tank, Strainer Tank)
CONFINED SPACE - Rescue
FALL PROTECTION
MATERIAL HANDLING Davit System Mast Extension 2 Miller DuraHoist™ Lower Mast Extension
DH-22/21
(21 inch extension) 14
90,000 in-lbs (10,200 N.m) 450
ALL LOCATIONS (Seawater Pump Station Vault and Tanks, Cooling Tower Pump/Motor Vault, Make-up Water Tank, Strainer Tank)
CONFINED SPACE - Rescue
FALL PROTECTION
MATERIAL HANDLING Davit System Mast Extension 1 Miller DuraHoist™ Lower Mast Extension
DH-22/33
(33 inch extention) 17
90,000 in-lbs (10,200 N.m) 450
ALL LOCATIONS (Seawater Pump Station Vault and Tanks, Cooling Tower Pump/Motor Vault, Make-up Water Tank, Strainer Tank)
CONFINED SPACE - Rescue
FALL PROTECTION
MATERIAL HANDLING Davit System Mast Extension 1 Miller DuraHoist™ Lower Mast Extension
DH-22/45
(45 inch extension) 20
90,000 in-lbs (10,200 N.m) 450
ALL LOCATIONS (Seawater Pump Station Vault and Tanks, Cooling Tower Pump/Motor Vault, Make-up Water Tank, Strainer Tank)
CONFINED SPACE - Rescue
FALL PROTECTION
MATERIAL HANDLING Davit System Mast Extension 1 Miller DuraHoist™ Lower Mast Extension
DH-22/57
(57 inch extension) 23
90,000 in-lbs (10,200 N.m) 450
Purchased
MILLER
PART DESCRIPTION
MILLER
PART NUMBER
MILLER
(Weight lbs)
MILLER
Proof Load Rating
(Weight lbs)
MILLER
Rated
Capacity/Working Load (Weight lbs)
Seawater Pump Station - Mechanical Vault and Aeration Tanks
FALL PROTECTION - Floor Opening Fall Arrest Posts 2 Miller Portable Fall Arrest Posts DH-AP-1/ 38
3250 (14.5kN), 4000 (7.7kN), 5700 (25.0kN)
Depending on Pin Positon 310
Seawater Pump Station - Mechanical Vault and Aeration Tanks
FALL PROTECTION - Floor Opening Fall Arrest Posts 1
Miller Portable Fall Arrest Post - Extension Post DH-AP-2/ 4.5 2250 (10kN) 310
Seawater Pump Station - Mechanical Vault and Aeration Tanks
FALL PROTECTION - Floor Opening Fall Arrest Post - Mounting Base 6
Miller Portable Fall Arrest Post - Bolt-on Anchor Plate For use in concrete or steel applications (portable or permanent) DH-AP-12/ 43
ALL LOCATIONS (Seawater Pump Station Vault and Tanks, Cooling Tower Pump/Motor Vault, Make-up Water Tank, Strainer Tank)
CONFINED SPACE - Rescue
FALL PROTECTION
Hoist & Winches Emergency Retrieval/Self Retracting Lifeline (SRL) 1
MighEvac Emergency Retrieval/SRL Winch
MR80K/80FT
(Kevlar Rope) 46 310
ALL LOCATIONS (Seawater Pump Station Vault and Tanks, Cooling Tower Pump/Motor Vault, Make-up Water Tank, Strainer Tank)
CONFINED SPACE - Rescue
FALL PROTECTION
Hoist & Winches Emergency Retrieval/Self Retracting Lifeline (SRL) 1
MighEvac Emergency Retrieval/SRL Winch
MR100SB-
Z7/100FT
(Stainless Steel wire) 59 310
ALL LOCATIONS (Seawater Pump Station Vault and Tanks, Cooling Tower Pump/Motor Vault, Make-up Water Tank, Strainer Tank)
CONFINED SPACE - Rescue
MATERIAL HANDLING
Hoist & Winches (Emergency Retrieval/Materials) 1
ManHandler personnel-rated hoist w/100-
ft. (30m) of 3/16-in. (4.76mm) stainless steel cable (Emergency Retrieval/Materials)
8442SS-Z7/100FT
(Stainless Steel Wire) 46 350
ALL LOCATIONS (Seawater Pump Station Vault and Tanks, Cooling Tower Pump/Motor Vault, Make-up Water Tank, Strainer Tank)
CONFINED SPACE - Rescue
FALL PROTECTION
MATERIAL HANDLING Hoist Winch Brackets/Assemblies 3
Complete Mounting Bracket Assembly for Miller Manhandler Hoist/Winch or Miller MightEvac SRL
DH-19-MILLER,
includes:
DH-19/ bracket &
DH-AB-MILLER/
bracket 3.1 5000 (22kN) 450
ALL LOCATIONS (Seawater Pump Station Vault and Tanks, Cooling Tower Pump/Motor Vault, Make-up Water Tank, Strainer Tank)
FALL PROTECTION - Floor Opening Cable Lifeline for Sharp Edge Applications 1
Miller TurboLite™ EXTREME Personal Fall Limiter MFLEC-3/9FT 4.2 420
Purchased
MILLER
PART DESCRIPTION
MILLER
PART NUMBER
MILLER
(Weight lbs)
MILLER
Proof Load Rating
(Weight lbs)
MILLER
Rated
Capacity/Working Load (Weight lbs)
ALL LOCATIONS (Seawater Pump Station Vault and Tanks, Cooling Tower Pump/Motor Vault, Make-up Water Tank, Strainer Tank)
FALL PROTECTION - Floor Opening Cable Lifeline Applications 2 Miller TurboLite™ Personal Fall Limiters MFL-1-Z7/6FT 2.5 400
Station Vault and Tanks, Cooling Tower Pump/Motor Vault, Make-up Water Tank, Strainer Tank) SECURE STORAGE
Site Storage Box:
Exterior, Water-tight, Lockable, Mountable 2
Site Storage Box:
Exterior, Water-tight, Lockable, Mountable TBD
Equipment Storage/Maintenance SECURE STORAGE Carrying Case - Mast 4 Lower Mast Carry Bags DH-22BAG/
Equipment Storage/Maintenance SECURE STORAGE Carrying Case - Davit 3 Upper Mast Carry Bags - Carrying bag for
DH-3/ DH-3BAG/
Equipment Storage/Maintenance SECURE STORAGE Carrying Case - Materia/Pers Hoist 2 Fall Protection Post Carry Bag DH-AP-1BAG/
Equipment Storage/Maintenance SECURE STORAGE Carrying Case - Materia/Pers Hoist 1 Fall Protection Post Extension Carry Bag DH-AP-2BAG/
Equipment Storage/Maintenance SECURE STORAGE Carrying Case - Emergency Evac/SRL 3 Carry Bag - MightEvac Emergency Retrieval/SLR/ ManHandler Winch TBD
| Cooling Tower Aeration Vaults with Old Davit Mounts |
| Ladder Access |
| Ref dwg LM-104 |
| NOAA Sandy Hook Fall Protection Clarifications |
| Ref Dwg LM-110 |
| CORRECTED Sandy Hook 2020 Seawater Pump Station - Cooling Tower Station Confined Space and Fall Protection Equipment List |
| Equipment Listing |
| Seawater intake vault - hatch |
| Seawater System PIT Access (Doors Open) |
| Seawater System PIT Overview_LI |
| Ref Dwg LS 108 |