RFI 0001
After review of this project, there is an omission in the specifications of the floor and wall tile requirements. For example: Is there waterproofing required? What are the wall tile types? How is the wall tile to be finished at top of elevation, Schluter trim/bullnose?
1. Water proofing membrane is not required
2. 12x24 large format wall tiles with 6x12 cove base tile Daltile is what we have been using. (see sheet A-5 typical wall tile layout)
3. Schluter trim to be used (see sheet A-5 typical wall tile layout)
What is the extent of the wall tile, all walls within restrooms or wet walls only? The elevation is not clear.
4. All walls to be tiled (approx. 60”)
Also, 12x24 (large format) floor tiles are not able to be sloped to existing drains unless top cut, we propose setting them flat to the drains. Please advise.
5. Flat to drains. “Slope to drains” is put in so it does not get sloped from drains.