Solicitation_N66604-14-Q-2387_Q_ _A_Doc.docx

DOCX document 16 KB Posted

Attached to
Remote Environmental Monitoring System Federal contract opportunity
Solicitation number
N6660414Q2387
Issued by
Department of the Navy Naval Sea Systems Command

View the file

Other files for this federal contract opportunity

Other files attached to Remote Environmental Monitoring System, newest first.
File Type Posted
Solicitation_N66604-14-Q-2387_Q_ _A_Doc 4 .docx DOCX document
Solicitation_N66604-14-Q-2387_Q_ _A_Doc 3 .docx DOCX document
RFQ_N66604-14-Q-2387_Government_Minimum_Specification_Rev2.docx DOCX document
Solicitation_N66604-14-Q-2387_Q_ _A_Doc 2 .docx DOCX document
RFQ_N66604-14-Q-2387_Government_Minimum_Specification_Rev1.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SOLICITATION NO. N66604-14-Q-2387

MODIFICATION 01

QUESTIONS AND ANSWERS:

1. QUESTIONS: Is this per location?

ANSWER: No, the system will cover three buildings and each building will cover over 10,000 square feet and multiple rooms.

2. QUESTION: What type of interface is needed for the sensors? Are there specifications with any protocols?

ANSWER: Sensors should simply be compatible with the system; we will not be providing sensors.

3. QUESTION: Are we required to provide the sensors or only provision for data inputs?

ANSWER: Yes. The system shall have web-based software that can correlate and process data from all sensors (i.e., a device manager).

4. QUESTION: What web platform has to be supported?

ANSWER: Data must be able to be viewed via a web browser - namely for us, Internet Explorer backwards compatible to version 8.0.

5. QUESTION: What kind of webserver is available or are we providing the Server as part of the application, what security and support is needed?

ANSWER: No webserver required and infrastructure is already in place. Technical support would be required to install the proposer's web applications onto the server and ensure compatibility. The system shall provide a user interface construct such that sensor data processing can be accomplished using an in-house web-based application (for later advanced use).

6. QUESTION: Is this referring to have a Web Service for communication with other applications? Would OPC be ok?

ANSWER: Yes; we would have the need to pass the data from the provided web based application or a web service to our own in house applications. The system shall be able to monitor the following via sensors: temperature, humidity, 60 Hz power availability, water presence.

7. QUESTION: Once again are we providing the sensors?

ANSWER: Yes. For the purpose of future growth, the system shall be able to monitor the following via sensors: 400 Hz power availability, air flow/pressure, water flow/pressure, customized sensors as required for future requirements.

8. QUESTION: How many inputs? What range and what sampling frequency?

ANSWER: Long term, the number of sensors could increase three fold from 150 (so around 450); as an estimate, up to a third may need to be analog. Range would be application dependent, and sampling must be continuous.