Solicitation_N66604-14-Q-2387_Q_ _A_Doc 3 .docx
DOCX document 15 KB Posted
- Attached to
- Remote Environmental Monitoring System Federal contract opportunity
- Solicitation number
- N6660414Q2387
About this file
Questions and Answers 3
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Solicitation_N66604-14-Q-2387_Q_ _A_Doc 4 .docx | DOCX document | |
| RFQ_N66604-14-Q-2387_Government_Minimum_Specification_Rev2.docx | DOCX document | |
| Solicitation_N66604-14-Q-2387_Q_ _A_Doc 2 .docx | DOCX document | |
| Solicitation_N66604-14-Q-2387_Q_ _A_Doc.docx | DOCX document | |
| RFQ_N66604-14-Q-2387_Government_Minimum_Specification_Rev1.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SOLICITATION NO. N66604-14-Q-2387
AMENDMENT 04
QUESTIONS AND ANSWERS:
1) Is there hard wired ethernet available throughout the facility?
Yes
2) Based on the four sensors listed above and the requirement for 150 sensors, is the proposal requesting monitoring in ~35 rooms?
No, the number of rooms not important, however, from our calculations you will require 30 hubs for the sensors to plug into. Each hub connects to the network with the sensor runs of 100 feet back to the hub.
3) In each room/zone do you want all four sensors or will some rooms have only one or two of the sensors?
Some rooms will only have one or two
4) If we have to wire the sensors together (no wired ethernet available) what type of construction is the building interior? When was the building built?
Ethernet is available for the hubs, each hub should have 8 to 16 or more inputs for digital and analog sensors for future growth.