Questions and Answers

View the file

Other files for this federal contract opportunity

Other files attached to 20 Ton Air Conditioning Unit, newest first.
File Type Posted
18-T-N017_Attachment_1_-_Technical_Capability_Certs.docx DOCX document
7342B236-50194-SFC_SOW_20_TON_AC_UNIT_1.doc DOC document
Questions_and_Answers_to_Solicitation_2.docx DOCX document
Questions_and_Answers_to_Solicitation.docx DOCX document
18-T-N017_Attachment_1_-_Technical_Capability_Certs.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions and Answers

1. Are there any pictures of the existing units so that we have something to base our selection off of? The model number JTS-DX-20-MCS-E does not really help that much since we are not sure of the manufacturer.

Are these Ground top units/rooftop units, or do they require chilled water?

A. Here are the general specifications for requested 20 Ton Air Conditioner Units:

General Specifications

20 Ton Air Conditioning Unit with Reheat

20 Ton Air Conditioner with reheat capability

* Rated airflow is 8000 CFM.

* Unit must lower air temperature to 55°F.

* Unit must be rated for 20 Ton Air Cooling (8000 CFM).

* Maximum size is 106” L x 78” W x 49” high.

* Maximum weight is 3500 lb.

* Full load amps cannot exceed 135 amps at 460V.

* Must be electric unit.

* Must be weather-tight for outdoor use.

* Electric Panel in Nema 4 metal enclosure with lockable disconnect with Camlok cords. Must have Camlok cords.

* Unit to come with two (2) – 17 ½” OD inlets and two (2) – 17 ½” OD outlets.

* Unit must be capable of being used without any recirculation of air. Must have reheat capabilities. Minimum reheat capability must be 70 kw.

* Must have forklift pockets and 4 Point Certified lift frame.

* Must have rigging sketch. Lifting and Rigging must meet NAVFAC-P-307 Standards.

* Must have stenciled gross weight on four (4) sides.

* Must be provided with two (2) – 18” dia. x 25’ long insulated flex ducts.

These are the specifications that need to be met.