Question and Answers regarding Solicitation KHC-SD-1381639
1. Size of rooms to determine how much cooling is needed. Room 1E-020 CT Scan Figure 1, rooms 1D-044 & 1D-045. How big are these areas?
a. See dimension of rooms below on drawings.
2. Exterior wall material?
a. Exterior wall is made of stucco.
3. It is hard to tell from the floor drawings, but is there exterior walls available on all rooms so we can run the refrigerant linesets and wiring to the wall-mounted air handlers? I have attached a picture showing how a standard ductless mini split AC is installed on an Exterior wall. If any of the zones do not have exterior walls it will make the project quite a bit more labor intensive.
a. Pharmacy system passes through one interior wall and one exterior wall before connecting to condenser. Interior wall have mesh wiring for security. Exterior wall have stucco walls. Heat exchanger must have be installed in ceiling grid. The plan is to install condenser outside on a concrete pad. See drawing attached.
Also, in the Statement of work in section 4.1 it states “d. Performance shall be rated per ARI Std 550/590 using HFC 134a refrigerant.” All of the current ductless mini split systems today utilize R410A refrigerant.. Is that going to be OK?
R410A is okay to use.
Picture shown on page 2.
Picture provided to question 3 is on page 3.
REFERENCE KEYNOTES
03300.05 - CONTINUOUS BUILDING APRON: 100 THICK, 450 WIDE
03300.08 - CONTINUOUS BUILDING APRON: 100 THICK, SEE
DRAWINGS FOR WIDTH
05811.04 - EXTERIOR ARCHITECTURAL JOINT SYSTEM
07414.01 - COMPOSITE METAL WALL PANEL SYSTEM
08331.22 - COUNTER DOOR
08411.27 - VERTICAL ALUMINUM SUN SHADE (RE: SHEET A530)
10505.01 - METAL LOCKERS, 300 X 450, TWO TIER
10522.01 - FIRE EXTINGUISHER CABINET, SEMI RECESSED WITH
EXTINGUISHER
14580.01 - PNEUMATIC TUBE STATION
14580.02 - CHASE FOR PNEUMATIC TUBE- PLENUM TO GROUND
MATCH LINE
SEE A101D
MATCH LINE
SEE A101F
M A
T C
H
L I N
E
S E
E
A
G
M A
T C
H
L I N
E
S E
E
A
B
BBF
B1
A214
C1
A214
A1
A212
B1
A212
A3
A314
A1
A315
A1
A314
A1
A314
SIM.
A1
A315
A1
A315
SIM.
SIM.
A3
A320
A1
A316
REV
ISSUE: 06.30.09 - FINAL CD'S
PROJECT NO: 07-0103.001
CAD DWG FILE: 07-0103-A101E.dwg
DRAWN BY:
CHECKED BY:
SHEET TITLE
DATE DESCRIPTION
CONSULTANTS
U. S. DEPARTMENT
OF HEALTH AND
HUMAN SERVICES
SHEET ______ OF ______
E
21 3 4 5 6
D
C
B
A
E
D
C
B
A
21 3 4 5 6
T I G
H E N N O V A R O U P
E
F
C
B
A
G
D
KEY PLAN
GENERAL SHEET NOTES
SHEET KEYNOTES
LEGEND
A. ALL UNITS ARE IN MILLIMETERS UNLESS OTHERWISE
NOTED.
B. BASED ON PROGRAM OF REQUIREMENTS DATED
05/16/2008
C. SEE SHEETS A111A THROUGH A112F FOR DIMENSIONS
AND PARTITION TYPES.
WALL TYPES
TWO HOUR WALL -
OCCUPANCY SEPARATION
PER NFPA 101 TABLE
6.1.14.4.1
SMOKE BARRIER - ONE HOUR PER IBC
SMOKE BARRIER REQUIRED BY NFPA
CHAPT. 20 PER NFPA 8.5/BARRIER TO
RESIST SMOKE, INCIDENTAL USE
AREAS PER IBC 508.2.2.1/SMOKE
PARTITION, CORRIDORS IN I-2 IBC 710
STRUCTURAL BRACE
ONE HOUR FIRE BARRIER
HIGHLOW
RATING IN MINUTES
DOOR NUMBER
OPENING ELEVATION - SEE A601-A610
DOOR TYPE
X
WINDOW TREATMENT WHERE OCCURS:
HB= HORIZONTAL LOUVER BLINDS
RS= ROLLER SHADE
SEE I610 FOR MORE INFORMATION
1. REFER TO DETAIL E3/A901 FOR TYPICAL CASEWORK
ELEVATION
2. SINK TO BE INSTALLED IN MODULAR CASEWORK. REFER
TO FURNITURE PLANS
3. SOFFIT ABOVE, SEE: A121E
4. REFER TO DETAIL E5/A901 FOR TYPICAL CASEWORK
ELEVATION
5. EXTEND RATED WALL CONDITION BY 1200MM
D. SEE SHEETS A401 - A405 FOR ENLARGED PLANS