This document contains test reports for field acceptance checks and tests conducted on a fiber optic cable installation project for Building 682 at MCAS Futenma in Okinawa, Japan. The reports include hi-pot testing at 600 volts of wiring for Phases A, B, C, and the neutral, as well as megger testing and fiber optic cable testing. The fiber optic cable testing was performed using an Optical Time Domain Reflectometer and showed that all six fiber optic cables met the TIA-568.3-D-1 standard with margins above 0.75 dB. The test reports document passing results for attenuation, insertion loss, and length for each cable.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Grounding System Test_signed.pdf | ||
| RFQ Cover Sheet.docx | DOCX document | |
| As-built Drawings.pdf | ||
| M6740023Q0091.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TRANSMITTAL OF SHOP DRAWINGS, EQUIPMENT DATA, MATERIAL SAMPLES, TEST REPORTS,
OR MANUFACTURER’S CERTIFICATES OF COMPLIANCE
DATE TRANSMITTAL NO.
SECTION I - TRANSMITTAL INFORMATION (To be completed by Contractor)
TO: CME : LTJG GREGORY AMARAL
FEAD CAMP BUTLER
NAVFAC Far East
FROM:
KYUNAN CO., LTD.
601-9 Shimabuku, Kitanakagusuku, Nakagami Gun, Okinawa 901-2301
CONTRACT NO.
N40084-16-D-0007
DELIVERY ORDER
NO. N4008420F4580
CHECK ONE (Use a separate form for each category):
This is a new transmittal
This is a resubmittal of transmittal
This is an addition to transmittal
SPECIFICATION SECTION NO. PROJECT TITLE AND LOCATION
DB To Install Level III Preservation System, Bldg. 682 MCAS Futenma,Okinawa, Japan (ESR 016-19)
CHECK ONE (Use a separate form for each category): This transmittal is Contractor Approved (For Information Only) for Government Approval Variation for Government Approval
ITEM
NO.
a.
SUBMITTAL DESCRIPTION (SD) NUMBER
AND TYPE
b.
DESCRIPTION OF ITEM SUBMITTED
(Name, Manufacturer’s Name, Model No., Type, Size, etc.)
c.
NO. OF
COPIES
d.
SPEC. PAR. #
OR DRAWING #
e.
ACTION CODE
Reviewer f.
FEAD
g.
CONTRACTOR REMARKS: I hereby certify that the Equipment Material Article shown and marked in this submittal is that proposed to be incorporated in the Contract identified above, is in compliance with the contract drawings and specifications, and can be installed in the allocated spaces. Proposed variations, if any, are clearly marked on each submittal, are compatible with other elements of the work, and are recommended for Government approval.
Signature of QC Manager Date
SECTION II - GOVERNMENT APPROVAL ACTION (To be completed by Designer/FEAD)
DATE RECEIVED FROM KTR: DATE SENT TO REVIEWER:
ACTION CODES: The following Action Codes are given to items submitted:
REVIEWER: A-E FEAD FE FPE OTHER A - Approved as submitted
AN - Approved as noted, resubmission not required
AR - Approved as noted, resubmission required, see Sec. II Remarks
D - Disapproved, resubmission required, see Sec. II Remarks
E - Will be returned by separate cover
F - Receipt acknowledged
FX - Receipt acknowledged, does not comply with Contract Requirements, see Sec. II Remarks
G - Other, see Sec. II Remarks
NR - Not reviewed, see Sec. II Remarks
The submittals listed above have been reviewed, and are returned with actions taken as indicated in Section I, Columns f above. Approval of the listed items does not indicate approval of variations, if any, unless the variations are clearly marked on each submittal and are supported by the contractor; furthermore, approval of items does not relieve the contractor from complying with all requirements of the contract plans and specifications.
NAME, TITLE & SIGNATURE OF REVIEWER DATE
REMARKS (Attach additional sheets as necessary):
DATE RECEIVED FROM REVIEWER NAME, TITLE & SIGNATURE OF APPROVING AUTHORITY DATE DATE RETURNED TO KTR
OICC FE 4330/3 (Rev. 4/99) Sheet of To print data, feed this direction
N1585 Text Box Hi-Pot Test
N40084-16-D-0007 DO# N4008420F4580 DB to Install Level III Preservation System, B682 MCAS Futenma, Okinawa, Japan Subject: 600 V Wiring Test
N1585 Text Box
Test Point: Phase A ( Cable 1,2, &3)
Result: Greater than 1 Giga-Ohm
Note: Breakers are closed in the MDP Panel going to the panel MDP to test the entire line.
N40084-16-D-0007 DO# N4008420F4580 DB to Install Level III Preservation System, B682 MCAS Futenma, Okinawa, Japan Subject: 600 V Wiring Test
N1585 Text Box
Test Point: Phase B ( Cable 1,2, &3)
N40084-16-D-0007 DO# N4008420F4580 DB to Install Level III Preservation System, B682 MCAS Futenma, Okinawa, Japan Subject: 600 V Wiring Test
N1585 Text Box
Test Point: Phase C ( Cable 1,2, &3)
N40084-16-D-0007 DO# N4008420F4580 DB to Install Level III Preservation System, B682 MCAS Futenma, Okinawa, Japan Subject: 600 V Wiring Test
N1585 Text Box
Test Point: Neutral ( Cable 1,2, &3)
N40084-16-D-0007 DO# N4008420F4580 DB to Install Level III Preservation System, B682 MCAS Futenma, Okinawa, Japan Subject: 600 V Wiring Test
N1585 Text Box
Test Point: Phase A, B, & C
Note: Breakers are Open on Panel MCB and Panel MDB to isolate only the Cables.
05/01/2023 05:24:47 PM Page 1 6SM FOC TEST REPORT.flw
Cable ID Summary Test Limit Length Headroom Date / Time B682 SM06 01 PASS TIA-568.3-D-1 Singlemode OSP (STD) 537 ft 0.76 dB (Loss Margin) 05/01/2023 03:50 PM B682 SM06 02 PASS TIA-568.3-D-1 Singlemode OSP (STD) 537 ft 0.96 dB (Loss Margin) 05/01/2023 03:50 PM B682 SM06 03 PASS TIA-568.3-D-1 Singlemode OSP (STD) 537 ft 1.13 dB (Loss Margin) 05/01/2023 03:51 PM B682 SM06 04 PASS TIA-568.3-D-1 Singlemode OSP (STD) 537 ft 1.00 dB (Loss Margin) 05/01/2023 03:50 PM B682 SM06 05 PASS TIA-568.3-D-1 Singlemode OSP (STD) 538 ft 1.04 dB (Loss Margin) 05/01/2023 03:51 PM B682 SM06 06 PASS TIA-568.3-D-1 Singlemode OSP (STD) 538 ft 0.94 dB (Loss Margin) 05/01/2023 03:51 PM
N1585
Fiber Optic Cable test
05/01/2023 05:24:47 PM Page 2 6SM FOC TEST REPORT.flw
Total Length: 3224 ft Number of Reports: 6 Number of Passing Reports: 6 Number of Failing Reports: 0 Number of Warning Reports: 0 Documentation Only: 0
N1585
Cable ID: B682 SM06 01 Test Summary: PASS Date / Time: 05/01/2023 03:50:30 PM n = 1.467000 (1310 nm) Backscatter Coefficient: -79.5dB (1310 nm) Cable Type: OS2 Singlemode n = 1.468000 (1550 nm) Backscatter Coefficient: -82.0dB (1550 nm)
Project: FUTENMA B682 Site: Not Set Building: Not Set Floor: Not Set Room: Not Set Rack: Not Set Patch: Not Set 6SM FOC TEST REPORT.flw Page 3
LinkWare™ PC Version 11.1
Loss (R->M)
PASS
Test Limit: TIA-568.3-D-1 Singlemode OSP
(STD)
Limits Version: 7.7 Date / Time: 05/01/2023 03:50:30 PM Operator: MASASHI FUKUCHI Main: Versiv
S/N: 21023215 Software Version: V6.8 Build 6
Module: CertiFiber Pro (CFP-QUAD) S/N: 21181384 Calibration Date: 02/08/2023
Remote: Versiv S/N: 21110369 Software Version: V6.8 Build 6
Module: CertiFiber Pro Remote (CFP-QUAD) S/N: 21181375 Calibration Date: 02/08/2023
Propagation Delay (ns) 802 Length ft 537 PASS Limit 131234
1310 nm 1550 nm Result PASS PASS Loss (dB) 0.81 0.75 Limit (dB) 1.57 1.57 Margin (dB) 0.76 0.82
Reference (dBm) -2.87 -2.83
Number of Adapters: 2 Number of Splices: 0 Connector Type: LC Patch Length1 (ft): 7 Reference Date: 05/01/2023 03:35:48 PM 1 Jumper
Loss (M->R)
PASS
Test Limit:
Limits Version:
Date / Time:
1310 nm 1550 nm Result PASS PASS Loss (dB) 0.75 0.68 Limit (dB) 1.57 1.57 Margin (dB) 0.82 0.89
Reference (dBm) -2.68 -2.79
Compliant Network Standards:
1000BASE-LX 100GBASE-ER4 100GBASE-LR4
10GBASE-E 10GBASE-L 10GBASE-LRM
10GBASE-LX4 40GBASE-ER4 40GBASE-FR
40GBASE-LR4 Fibre Channel 100-SM-LC-L Fibre Channel 1200-SM-LC-L Fibre Channel 1600-SM-LC-L Fibre Channel 200-SM-LC-L Fibre Channel 400-SM-LC-L Fibre Channel 400-SM-LC-M Fibre Channel 800-SM-LC-I Fibre Channel 800-SM-LC-L
N1585
Cable ID: B682 SM06 02 Test Summary: PASS Date / Time: 05/01/2023 03:50:14 PM n = 1.467000 (1310 nm) Backscatter Coefficient: -79.5dB (1310 nm) Cable Type: OS2 Singlemode n = 1.468000 (1550 nm) Backscatter Coefficient: -82.0dB (1550 nm)
Project: FUTENMA B682 Site: Not Set Building: Not Set Floor: Not Set Room: Not Set Rack: Not Set Patch: Not Set 6SM FOC TEST REPORT.flw Page 4
LinkWare™ PC Version 11.1
Loss (R->M)
PASS
Test Limit: TIA-568.3-D-1 Singlemode OSP
(STD)
Limits Version: 7.7 Date / Time: 05/01/2023 03:50:14 PM Operator: MASASHI FUKUCHI Main: Versiv
S/N: 21023215 Software Version: V6.8 Build 6
Module: CertiFiber Pro (CFP-QUAD) S/N: 21181384 Calibration Date: 02/08/2023
Remote: Versiv S/N: 21110369 Software Version: V6.8 Build 6
Module: CertiFiber Pro Remote (CFP-QUAD) S/N: 21181375 Calibration Date: 02/08/2023
Propagation Delay (ns) 802 Length ft 537 PASS Limit 131234
1310 nm 1550 nm Result PASS PASS Loss (dB) 0.54 0.50 Limit (dB) 1.57 1.57 Margin (dB) 1.03 1.07
Reference (dBm) -2.87 -2.83
Number of Adapters: 2 Number of Splices: 0 Connector Type: LC Patch Length1 (ft): 7 Reference Date: 05/01/2023 03:35:48 PM 1 Jumper
Loss (M->R)
PASS
Test Limit:
Limits Version:
Date / Time:
1310 nm 1550 nm Result PASS PASS Loss (dB) 0.61 0.60 Limit (dB) 1.57 1.57 Margin (dB) 0.96 0.97
Reference (dBm) -2.68 -2.79
Compliant Network Standards:
1000BASE-LX 100GBASE-ER4 100GBASE-LR4
10GBASE-E 10GBASE-L 10GBASE-LRM
10GBASE-LX4 40GBASE-ER4 40GBASE-FR
40GBASE-LR4 Fibre Channel 100-SM-LC-L Fibre Channel 1200-SM-LC-L Fibre Channel 1600-SM-LC-L Fibre Channel 200-SM-LC-L Fibre Channel 400-SM-LC-L Fibre Channel 400-SM-LC-M Fibre Channel 800-SM-LC-I Fibre Channel 800-SM-LC-L
N1585
Cable ID: B682 SM06 03 Test Summary: PASS Date / Time: 05/01/2023 03:51:05 PM n = 1.467000 (1310 nm) Backscatter Coefficient: -79.5dB (1310 nm) Cable Type: OS2 Singlemode n = 1.468000 (1550 nm) Backscatter Coefficient: -82.0dB (1550 nm)
Project: FUTENMA B682 Site: Not Set Building: Not Set Floor: Not Set Room: Not Set Rack: Not Set Patch: Not Set 6SM FOC TEST REPORT.flw Page 5
LinkWare™ PC Version 11.1
Loss (R->M)
PASS
Test Limit: TIA-568.3-D-1 Singlemode OSP
(STD)
Limits Version: 7.7 Date / Time: 05/01/2023 03:51:05 PM Operator: MASASHI FUKUCHI Main: Versiv
S/N: 21023215 Software Version: V6.8 Build 6
Module: CertiFiber Pro (CFP-QUAD) S/N: 21181384 Calibration Date: 02/08/2023
Remote: Versiv S/N: 21110369 Software Version: V6.8 Build 6
Module: CertiFiber Pro Remote (CFP-QUAD) S/N: 21181375 Calibration Date: 02/08/2023
Propagation Delay (ns) 802 Length ft 537 PASS Limit 131234
1310 nm 1550 nm Result PASS PASS Loss (dB) 0.41 0.44 Limit (dB) 1.57 1.57 Margin (dB) 1.16 1.13
Reference (dBm) -2.87 -2.83
Number of Adapters: 2 Number of Splices: 0 Connector Type: LC Patch Length1 (ft): 7 Reference Date: 05/01/2023 03:35:48 PM 1 Jumper
Loss (M->R)
PASS
Test Limit:
Limits Version:
Date / Time:
1310 nm 1550 nm Result PASS PASS Loss (dB) 0.40 0.42 Limit (dB) 1.57 1.57 Margin (dB) 1.17 1.15
Reference (dBm) -2.68 -2.79
Compliant Network Standards:
1000BASE-LX 100GBASE-ER4 100GBASE-LR4
10GBASE-E 10GBASE-L 10GBASE-LRM
10GBASE-LX4 40GBASE-ER4 40GBASE-FR
40GBASE-LR4 Fibre Channel 100-SM-LC-L Fibre Channel 1200-SM-LC-L Fibre Channel 1600-SM-LC-L Fibre Channel 200-SM-LC-L Fibre Channel 400-SM-LC-L Fibre Channel 400-SM-LC-M Fibre Channel 800-SM-LC-I Fibre Channel 800-SM-LC-L
N1585
Cable ID: B682 SM06 04 Test Summary: PASS Date / Time: 05/01/2023 03:50:48 PM n = 1.467000 (1310 nm) Backscatter Coefficient: -79.5dB (1310 nm) Cable Type: OS2 Singlemode n = 1.468000 (1550 nm) Backscatter Coefficient: -82.0dB (1550 nm)
Project: FUTENMA B682 Site: Not Set Building: Not Set Floor: Not Set Room: Not Set Rack: Not Set Patch: Not Set 6SM FOC TEST REPORT.flw Page 6
LinkWare™ PC Version 11.1
Loss (R->M)
PASS
Test Limit: TIA-568.3-D-1 Singlemode OSP
(STD)
Limits Version: 7.7 Date / Time: 05/01/2023 03:50:48 PM Operator: MASASHI FUKUCHI Main: Versiv
S/N: 21023215 Software Version: V6.8 Build 6
Module: CertiFiber Pro (CFP-QUAD) S/N: 21181384 Calibration Date: 02/08/2023
Remote: Versiv S/N: 21110369 Software Version: V6.8 Build 6
Module: CertiFiber Pro Remote (CFP-QUAD) S/N: 21181375 Calibration Date: 02/08/2023
Propagation Delay (ns) 802 Length ft 537 PASS Limit 131234
1310 nm 1550 nm Result PASS PASS Loss (dB) 0.57 0.48 Limit (dB) 1.57 1.57 Margin (dB) 1.00 1.09
Reference (dBm) -2.87 -2.83
Number of Adapters: 2 Number of Splices: 0 Connector Type: LC Patch Length1 (ft): 7 Reference Date: 05/01/2023 03:35:48 PM 1 Jumper
Loss (M->R)
PASS
Test Limit:
Limits Version:
Date / Time:
1310 nm 1550 nm Result PASS PASS Loss (dB) 0.48 0.48 Limit (dB) 1.57 1.57 Margin (dB) 1.09 1.09
Reference (dBm) -2.68 -2.79
Compliant Network Standards:
1000BASE-LX 100GBASE-ER4 100GBASE-LR4
10GBASE-E 10GBASE-L 10GBASE-LRM
10GBASE-LX4 40GBASE-ER4 40GBASE-FR
40GBASE-LR4 Fibre Channel 100-SM-LC-L Fibre Channel 1200-SM-LC-L Fibre Channel 1600-SM-LC-L Fibre Channel 200-SM-LC-L Fibre Channel 400-SM-LC-L Fibre Channel 400-SM-LC-M Fibre Channel 800-SM-LC-I Fibre Channel 800-SM-LC-L
N1585
Cable ID: B682 SM06 05 Test Summary: PASS Date / Time: 05/01/2023 03:51:51 PM n = 1.467000 (1310 nm) Backscatter Coefficient: -79.5dB (1310 nm) Cable Type: OS2 Singlemode n = 1.468000 (1550 nm) Backscatter Coefficient: -82.0dB (1550 nm)
Project: FUTENMA B682 Site: Not Set Building: Not Set Floor: Not Set Room: Not Set Rack: Not Set Patch: Not Set 6SM FOC TEST REPORT.flw Page 7
LinkWare™ PC Version 11.1
Loss (R->M)
PASS
Test Limit: TIA-568.3-D-1 Singlemode OSP
(STD)
Limits Version: 7.7 Date / Time: 05/01/2023 03:51:51 PM Operator: MASASHI FUKUCHI Main: Versiv
S/N: 21023215 Software Version: V6.8 Build 6
Module: CertiFiber Pro (CFP-QUAD) S/N: 21181384 Calibration Date: 02/08/2023
Remote: Versiv S/N: 21110369 Software Version: V6.8 Build 6
Module: CertiFiber Pro Remote (CFP-QUAD) S/N: 21181375 Calibration Date: 02/08/2023
Propagation Delay (ns) 803 Length ft 538 PASS Limit 131234
1310 nm 1550 nm Result PASS PASS Loss (dB) 0.53 0.49 Limit (dB) 1.57 1.57 Margin (dB) 1.04 1.08
Reference (dBm) -2.87 -2.83
Number of Adapters: 2 Number of Splices: 0 Connector Type: LC Patch Length1 (ft): 7 Reference Date: 05/01/2023 03:35:48 PM 1 Jumper
Loss (M->R)
PASS
Test Limit:
Limits Version:
Date / Time:
1310 nm 1550 nm Result PASS PASS Loss (dB) 0.43 0.41 Limit (dB) 1.57 1.57 Margin (dB) 1.14 1.16
Reference (dBm) -2.68 -2.79
Compliant Network Standards:
1000BASE-LX 100GBASE-ER4 100GBASE-LR4
10GBASE-E 10GBASE-L 10GBASE-LRM
10GBASE-LX4 40GBASE-ER4 40GBASE-FR
40GBASE-LR4 Fibre Channel 100-SM-LC-L Fibre Channel 1200-SM-LC-L Fibre Channel 1600-SM-LC-L Fibre Channel 200-SM-LC-L Fibre Channel 400-SM-LC-L Fibre Channel 400-SM-LC-M Fibre Channel 800-SM-LC-I Fibre Channel 800-SM-LC-L
N1585
Cable ID: B682 SM06 06 Test Summary: PASS Date / Time: 05/01/2023 03:51:34 PM n = 1.467000 (1310 nm) Backscatter Coefficient: -79.5dB (1310 nm) Cable Type: OS2 Singlemode n = 1.468000 (1550 nm) Backscatter Coefficient: -82.0dB (1550 nm)
Project: FUTENMA B682 Site: Not Set Building: Not Set Floor: Not Set Room: Not Set Rack: Not Set Patch: Not Set 6SM FOC TEST REPORT.flw Page 8
LinkWare™ PC Version 11.1
Loss (R->M)
PASS
Test Limit: TIA-568.3-D-1 Singlemode OSP
(STD)
Limits Version: 7.7 Date / Time: 05/01/2023 03:51:34 PM Operator: MASASHI FUKUCHI Main: Versiv
S/N: 21023215 Software Version: V6.8 Build 6
Module: CertiFiber Pro (CFP-QUAD) S/N: 21181384 Calibration Date: 02/08/2023
Remote: Versiv S/N: 21110369 Software Version: V6.8 Build 6
Module: CertiFiber Pro Remote (CFP-QUAD) S/N: 21181375 Calibration Date: 02/08/2023
Propagation Delay (ns) 803 Length ft 538 PASS Limit 131234
1310 nm 1550 nm Result PASS PASS Loss (dB) 0.51 0.53 Limit (dB) 1.57 1.57 Margin (dB) 1.06 1.04
Reference (dBm) -2.87 -2.83
Number of Adapters: 2 Number of Splices: 0 Connector Type: LC Patch Length1 (ft): 7 Reference Date: 05/01/2023 03:35:48 PM 1 Jumper
Loss (M->R)
PASS
Test Limit:
Limits Version:
Date / Time:
1310 nm 1550 nm Result PASS PASS Loss (dB) 0.60 0.63 Limit (dB) 1.57 1.57 Margin (dB) 0.97 0.94
Reference (dBm) -2.68 -2.79
Compliant Network Standards:
1000BASE-LX 100GBASE-ER4 100GBASE-LR4
10GBASE-E 10GBASE-L 10GBASE-LRM
10GBASE-LX4 40GBASE-ER4 40GBASE-FR
40GBASE-LR4 Fibre Channel 100-SM-LC-L Fibre Channel 1200-SM-LC-L Fibre Channel 1600-SM-LC-L Fibre Channel 200-SM-LC-L Fibre Channel 400-SM-LC-L Fibre Channel 400-SM-LC-M Fibre Channel 800-SM-LC-I Fibre Channel 800-SM-LC-L
N1585
| TR#58.a_Transmittal Cover |
| Hipot Test Result |
| doc06711420230522093809 |
| doc06711320230522093720 |
| Megger Test |
| L1 |
| l2 |
| L3 |
| N |
| MCB to MDB |
6SM FOC TEST REPORT
| Text1: 58.a |
| Text2: 69 |
| Text3: |
| Text4: |
| Text5: |
| Text6: |
| Text7: |
| Text8: |
| Text9: Field Acceptance Checks and Tests |
| Text11: (Hipot,Megger and FOC Test) |
| Text12: |
| Text13: |
| Text14: |
| Text15: |
| Text16: |
| Text17: 1 |
| Text18: |
| Text19: |
| Text20: |
| Text21: |
| Text22: |
| Text23: |
| Text24: 3.18.1 |
| Text25: |
| Text26: |
| Text27: |
| Text28: |
| Text29: |
| Text30: |
| Text31: |
| Text32: |
| Text33: |
| Text34: |
| Text35: |
| Text36: |
| Text37: |
| Text38: F |
| Text39: |
| Text40: |
| Text41: |
| Text42: |
| Text43: |
| Text44: |
| Text45: |
| Text48: |
| Text49: |
| Check Box50: Off |
| Check Box51: Off |
| Check Box52: Off |
| Check Box53: Off |
| Check Box54: Yes |
| Check Box55: Off |
| Check Box56: Off |
| Check Box57: Off |
| Check Box58: Yes |
| Text59: 33 71 02 |
| Check Box60: Yes |
| Check Box61: Off |
| Check Box62: Off |
| Text63: |
| Text64: |
| Date65_af_date: 5/24/23 |
| Date66_af_date: 5/24/23 |
| Date67_af_date: |
| Date68_af_date: |
| Date69_af_date: |
| Date70_af_date: |
| Date71_af_date: |
| Text72: 1 |
| Text73: 1 |
| Dropdown74: [SD-06 Test Report] |
| Dropdown75: [ ] |
| Dropdown76: [ ] |
| Dropdown77: [ ] |
| Dropdown78: [ ] |
| Dropdown79: [ ] |
| Dropdown 80: [ ] |
| Text75: Modification P0002 (Transformer Installation) Submittal. |
- Hipot Test
- 600 Volt Wiring Test / Megger Test
- 6SM FOC Test Report for Fiber Optic Cable.
| 2023-05-25T08:43:55+0900 | |
| AMARAL.GREGORY.GIL.1558647295 |
Date79_af_date: