IB

300 KB Posted

Attached to
Fort Worth Lanham Chiller Replacement Federal contract opportunity
Solicitation number
GS-07P-15-JU-C-0022
Issued by
General Services Administration Public Buildings Service Region 7

About this file

IB (5)(I)(H)(2) 475T Chiller Exhibit 2

Text of this file

October 06, 2014

Smardt Inc · 1840 Trans Canada Hwy · Dorval Qc H9P 1H7 · (514) 426-8989 · Fax (514) 426-5757 ·

Customer: Customer Ref:

Quoted for: Prepared By:

Date: October 06, 2014

PART NUMBER DESCRIPTION

WA140.3HG08.F2HLMA.F2BBMA.TN0 Water Cooled Chiller

INCLUDED BY SMARDT:

Chiller(s) to be shipped Standard - Unit shipped fully assembled Chillers are ETL listed and certified to CSA C22.2 No.236 Conforming to ANSI/UL 1995 Power connection style: Single Point Power Connection Nema 1 Control enclosures - indoor use only Mechanical HP/LP switch.

ASME certified horizontal shell-and-tube heat exchangers.

Supporting baffles inside Standard EVAP and COND tubesheets High efficiency enhanced tubes Evaporator Insulation: Standard Thermal Insulation 3/4" (19mm) Evaporator water boxes rated to 145psig fitted with Grooved Pipe Connection Condenser water boxes rated to 145psig fitted with Grooved Pipe Connection Chilled water : IFM – Thermal Dispersion Switch Condenser water : IFM – Thermal Dispersion Switch Dual pressure relief valves on evaporator and condenser mounted on changeover valve.

Factory Startup: Certified Startup Agent Connectivity: Modbus RTU (RS485)

NOT INCLUDED BY SMARDT:

Vibration isolation pad (not required by manufacturer) Rigging and providing access for equipment.

Piping from refrigerant pressure relief valves to outside.

Grooved flange couplings.

Refrigerant monitor.

Seismic certification.

Performance test.

Sound test.

Harmonic or EMI Filters Extended warranties.

Any other item not mentioned above.

PERFORMANCE INFORMATION

Description Capacity Model Centrifugal liquid chiller 475.0 tonsR WA140.3HG08.F2HLMA.F2BBMA.TN0

Options W489 | E999 | C16 |

XXXXXXXXXXXXX.XXXX.XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX.XXXXXXXXXXX.XXXXXXXXXXXXXXX

Evaporator Data Fluid Type Water Fluid Concentration (%) 0% Flow Rate 1133.2 US gpm Tube Material Cu 0.025” Enhanced Surface Entering Fluid Temp 55.0°F Tube Wall Thickness 0.025Inch

Leaving Fluid Temp 45.0°F Circuit number of passes Two(2)

Fouling Factor 0.00010 h•ft²•ºF/Btu Constant speed flow min (pressure drop at flow) 511.7 USGPM (2.07 PSI)

Pressure Drop 10.16 psi (23.43 ft H2O) Variable speed flow min (pressure drop at flow) 341.1 USGPM (0.92 PSI)

Condenser Data Fluid Type Water Fluid Concentration (%) 0% Flow Rate 1333.6 US gpm Tube Material Cu 0.025” Enhanced Surface Entering Fluid Temp 85.0°F Tube Wall Thickness 0.025Inch Leaving Fluid Temp 95.0°F Circuit number of passes Two(2)

Fouling Factor 0.00025 h•ft²•ºF/Btu Constant speed flow min (pressure drop at flow) 489.4 USGPM (0.89 PSI)

Pressure Drop 14.07 psi (32.46 ft H2O) Variable speed flow min (pressure drop at flow) 326.3 USGPM (0.40 PSI)

Physical Data Length(ft) See product drawing Weight (Empty) 13442 lbs Width(ft) See product drawing Weight (Operating) 16248 lbs Height(ft) See product drawing Refrigerant Charge 1012 lbs

Equipment Details

Capacity(TR) 475.0 tonsR Type of compressor TT400-G8-1-ST-E-O-NC

Unit Power(kW) 280.5 kW Full load Efficiency 0.591 kW/tonsR

Number of compressors 3 Compressor Efficiency 0.590 kW/tonsR Compressor Power (kW) each 93.5 kW Environmentally friendly HFC-134a refrigerant.

Unit power characteristics

Supply Power 460 V MCA 417 A

Amps 385 A MOCP 546 A

14.1.0.0 October 06, 2014

AHRI CERTFIED PER 550/590

Program Scope

1.3.1 Program Scope Inclusions.

1.3.1.1 60 Hz WCCL Product Inclusions.

All compressor types;

Chillers rated with capacities >0 and ≤3000 tonsa [10,551 kW]b;

Hermetic & open type, electric motor driven;

Units selected for use within the range of Application Rating Conditions as per the Standard (part-load performance no less than 25% of the rated full load capacity);

Chillers with voltages ≤15,000 volts; and Positive Displacement Units intended for use with glycol or other secondary coolant for freeze protection with a leaving chilled fluid temperature above 32°F [0°C] are certified when tested with water at Standard Rating Conditions.

Notes:

a. Capacity refers to the capacity of Packaged Units rated at full load AHRI Standard 550/590 (I-P) Rating

Conditions and the capacity of Configurable Units rated at application full load operating conditions provided these conditions are within the scope of AHRI Standard 550/590 (I-P).

b. kW conversions provided for reference only.

1.3.1.2 50 Hz WCCL Product Inclusions All compressor types;

Chillers rated with capacities ≥200 and ≤3000 tonsa [703 and 10,551 kW]b;

Optional certification for chillers rated with capacities >0 and <200 tonsa [703kW]b (The Certify-All Policy does not apply to these units.);

Hermetic & open type, electric motor driven;

Units selected for use within the range of application rating conditions as per the Standard (part-load performance no less than 25% of the rated full load capacity);

Chillers with voltages ≤15,000 volts; and Positive Displacement Units intended for use with glycol or other secondary coolant for freeze protection with a leaving chilled fluid temperature above 32°F [0°C] are certified when tested with water at Standard Rating Conditions.

Notes:

a. Capacity refers to the capacity of Packaged Units rated at full load AHRI Standard 550/590 (I-P) Rating

Conditions and the capacity of Configurable Units rated at application full load operating conditions provided these conditions are within the scope of AHRI Standard 550/590 (I-P).

b. kW conversions provided for reference only.

1.3.2 Program Scope Exclusions. The following are exclusions for 50 Hz and 60 Hz WCCL products:

Condenserless chillers;

Evaporatively-cooled chillers;

Chillers that are not electrically driven Chillers with motors not supplied with the unit by the Participant; and Heat recovery & heat pump ratings are not certified; however, Participants may elect to certify these chillers in the cooling mode with this option turned off.

Units with condensers intended for use with glycol or other secondary coolants.

Units with evaporators intended for use with glycol or other secondary coolants not included in Sections

1.3.1.1 and 1.3.1.2.

Certified in accordance with the AHRI Water-Cooled Water Chilling Packages Using Vapor Compression Cycle Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org

WA140.3HG08.F2HLMA.F2BBMA.TN0

14.1.0.0

IPLV : 0.328 kW/tonsR (36.6 EER) % Load Capacity Perf kW Chw Flow Chw In Chw Out Cw Flow Cw In Cw Out 100 475.0 0.601 285.60 1140.00 53.95 44.01 1425.00 84.99 94.32 75 356.3 0.407 145.13 1140.00 51.46 44.01 1425.00 75.02 81.69 50 237.5 0.279 66.25 1140.00 48.98 44.01 1425.00 64.94 69.24 25 118.8 0.308 36.60 1140.00 46.49 44.01 1425.00 64.94 67.11

NPLV : 0.320 kW/tonsR (37.5 EER) % Load Capacity Perf kW Chw Flow Chw In Chw Out Cw Flow Cw In Cw Out 100 475.0 0.590 280.45 1133.17 55.01 45.00 1333.57 85.00 95.00 75 356.3 0.400 142.57 1133.17 52.50 45.00 1333.57 75.00 82.11 50 237.5 0.272 64.54 1133.17 50.00 45.00 1333.57 64.99 69.58 25 118.8 0.298 35.43 1133.17 47.50 45.00 1333.57 64.99 67.30

PPLV : 0.320 kW/tonsR (37.5 EER) % Load Capacity Perf kW Chw Flow Chw In Chw Out Cw Flow Cw In Cw Out 100 475.0 0.590 280.45 1133.17 55.00 45.00 1333.57 85.00 95.00 75 356.3 0.400 142.57 1133.17 52.50 45.00 1333.57 75.00 82.11 50 237.5 0.272 64.54 1133.17 50.00 45.00 1333.57 64.99 69.58 25 118.8 0.298 35.43 1133.17 47.50 45.00 1333.57 64.99 67.30

Sound Data Description Global 60 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz Lw dB 92.1 80.6 80.2 82.7 83.4 87.6 83.9 77 80.8 Lw dB(A) 90.8 54.4 64.1 74.1 80.2 87.6 85.1 78 79.7 Lp dB(A) at

3.3 ft 82.9 46.5 56.2 66.2 72.3 79.7 77.2 70.1 71.8

10 Point Part Load Value : 0.320 kW/tonsR (37.5 EER) Loa d

Capacity , tonsR kW/ton R kW

Evaporato r Flow, US gpm

Evaporato r In Temp, °F

Evaporato r Out Temp, °F

Condense r Flow, US gpm

Condense r In Temp, °F

Condense r Out Temp, °F

100 475.0 0.590 280.4 5 1133.17 55.00 45.00 1333.57 85.00 95.00

90 427.5 0.500 213.8 1 1133.17 54.00 45.00 1333.57 80.99 89.74

80 380.0 0.431 163.7 1 1133.17 53.00 45.00 1333.57 76.98 84.62

70 332.5 0.371 123.5 1 1133.17 52.00 45.00 1333.57 72.96 79.55

60 285.0 0.327 93.12 1133.17 51.00 45.00 1333.57 68.95 74.53 50 237.5 0.272 64.53 1133.17 50.00 45.00 1333.57 64.94 69.52 40 190.0 0.263 49.89 1133.17 49.00 45.00 1333.57 64.94 68.60 30 142.5 0.250 35.62 1133.17 48.00 45.00 1333.57 64.94 67.67 20 95.0 0.251 23.86 1133.17 47.00 45.00 1333.57 64.94 66.76 10 47.5 0.240 11.38 1133.17 46.00 45.00 1333.57 64.94 65.85 Note: Part load entering condenser water temperatures vary linearly from design at 100% load to 64.95 °F at 50% load, and fixed at 64.95 °F for 50% to 0% loads.

DIMENSIONS

L W W/Flash Econ H

177.2 in 51.4 in 67.4 in 94.8 in A B C D

33.1 in 9.6 in 14.6 in

EVAPORATOR CONDENSER

IN OUT IN OUT

8.0 in 8.0 in 6.0 in 6.0 in

W/Flash Econ

Other files for this federal contract opportunity

Other files attached to Fort Worth Lanham Chiller Replacement, newest first.
File Type Posted
Amendment_2.pdf PDF
Amendment_1.pdf PDF
IB —
IB —
IB —
IB —
IB —
IB —
IB —
IB —
IB —
IB —
IB —
IB —
IB —
IB —
IB —
IB —
IB —
IB —
IB —
IB —
IB —
Show all 23

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

File details come from the government source that posted it. Updated .