Questions
Would be able to adjust the specifications on the Office Building - from 20' x 30' x 9'h to 20' x 32' x 9'6h? No, need to stay with 20’ x 30’ x 9’ or 9’6h
What the electrical requirements (A/C, outlets…) are for the units as well as the tonnage of the HVAC required? 5 Outlets are for 4 workstations and for one printer; A/C would have separate outlet for power.
Junction box inside each module to provide capacity for up to 10 - 20A circuits (2#12, 1#14 ground) to be installed in each module.
We are an enclosure manufacturer and the material we use is EXOACM which is an extruded aluminum exoskeleton composite that consists of 20 thousand aluminum on each side with a heat resistant core.
Will this be an acceptable material? Yes.