Q1.) Is there a CAD/dwg file for the rooms involved? This would help in the overall design accuracy to protect you and us the bidder.
A1.) We do not have CAD/dwg files for this requirement. Furniture sizes given on drawings will ensure accuracy.
Q2.) If not, are there room dimensions that can be provided to include location of doors, columns and any other object along that would stick out from the walls?
A2.) There are no room dimensions available. Furniture sizes given on drawings will ensure accuracy. Time can be made available for final dimensions to be done in person, prior to furniture being ordered.
Q3.) For the upper shelves, what depth are you looking to be quoted? (i.e. 12”, 18”)
A3.) Shelves are to be 12”d
Q4.) Based upon the scope, the assumption is that there is power on the wall to allow for each workstation to plug into. Is that a correct assumption?
A4.) Power bars will be will be available in the busway above the furniture to plug into and can be brought down to bench level height we necessary. The 15’ power cord length requirement will be sufficient to get to the busway.
Q5.) SOW states one power bar at each corner but the drawing does not show this. Are they required, or not?
A5.) Power bars are only required at the locations shown in the plan. SOW has been updated.
Q6.) There is one power bar noted @ the 36” section of the power drawing but not one on the back side. Is this by design or do they in fact need a power bar at both 36” sections?
A6.) There should be an additional power bar on the back side, drawing has been updated.
Q7.) Non-union install, or prevailing wage/union install required?
A7.) Prevailing wage as required on government contracts. Please note any subsequent contract will contain FAR Clause 52.222-42, Statement of Equivalent Rates for Federal Hires, and incorporate the most current wage rate and fringe for Employee Class 09040 Furniture Handler