Question: In the Cover PD paragraph 3.1 Description it mentions a mini mezzanine being converted into a maxi mezzanine, however there is nothing in the Cover PD that goes into detail, or a drawing that depicts where the maxi-mezzanine is to be placed. Was this a typo or is there information missing?

Answer: The reference for a maxi-mezzanine was removed from the project. I will remove this reference. An amendment to the RFP will be posted with this updated information.

Question: Is there an existing electric panel for VLM or will it requiring wiring and conduit from an electric room? If so, how far away is the electric room from the location of the VLM? Also, what is the voltage required for the VLM (what does the building have)?

Answer: There is not an existing electric panel for the VLM. There is a minimum of 208/220 power available and it is located within 100 feet of the VLM installation site.