Site Visit Q A.pdf
PDF 47 KB Posted
- Attached to
- Retrofit Hangar Doors Federal contract opportunity
- Solicitation number
- FA8571-12-T-0009
About this file
Q A from Site Visit
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| X201010403-CONTRACTOR.pdf | ||
| Site Visit Q A | — | |
| SOW Retrofit Hanger Doors.pdf | ||
| FA8571-12-T-0009.pdf | ||
| As-Builds.PDF | ||
| X201010403.pdf | ||
| SOW Retrofit Hanger Doors B59S | — | |
| Site Visit Pics 24 July 12.pdf | ||
| Revised Solicitation.pdf | ||
| SOW Retrofit Hanger Doors B59S | — | |
| X201010403.pdf | ||
| Solicitation | — | |
| SOW Retrofit Hanger Doors B59S | — |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
QUESTIONS/ANSWERS FROM SITE VIST, 7/24/12
Solicitation #: FA8571-12-T-0009
Q1. How will panel control doors, either seperately or simutaneaously?
A1. Button (control) will open both interior/exterior doors. (1.0 of revised SOW)
Q2. How many sets of control panels are required?
A2. One set for each door (2)
Q3. Should panel have capability to open/close doors from either side? Ex: If positioned on outside of hangar and exterior doors are closed, should have ability to close interior hangar doors also.
A3. YES…paragraph 3.2 & 3.3 of revised SOW
Q4. Do we have as-builts for building?
A4. Will determine and if possible release with ammended solicitation.
Q5. Is expectation for all doors/electrical controls to be explosion proof?
A5. Yes, clarified with 1.2 & 1.3 of revised SOW identifying UL rating and proper
Class I Div I groups.