Attachment_5_Fans.pdf
PDF 18 KB Posted
- Attached to
- HEDS Dome Scaffolding Federal contract opportunity
- Solicitation number
- FA8224-16-R-0058
About this file
Attachment 5 - Fans
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA8224-16-R-0058-0002_2nd_PoP_Extension.pdf | ||
| FA8224-16-R-0058-0001_PoP_Extension.pdf | ||
| Attachment_7_HEDS_Dome_Scaffolding_Machine_Drawings.pdf | ||
| Attachment_6_Scaffold_Equipment_Delivery_List.xlsx | XLSX spreadsheet | |
| HEDS_Scaffolding_PWS_12_Apr_16.docx | DOCX document | |
| CDRLs.pdf | ||
| Attachment_8_-_GFP_Equipment.pdf | ||
| Attachment_4_HEDS_Dome_Scaffolding_Images.pdf | ||
| Attachment_3_HEDS_Dome_Scaffold_Model_File_Locations.pdf | ||
| FA8224-16-R-0058.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment 2 Fans- Qty Required 4
Description A centrifugal type exhaust/supply fan specifically designed for moderate size ventilation applications. The fan can be mounted in any angle at any point along the duct work and straight-through air flow design allows easy installation. By using FC type mounting clamps fan can easily be removed from duct work for service. Fans are constructed in accordance with standard dimensions for spiral duct eliminating the need for transition pieces. Fan motors are capable of operating in air stream temperatures up to 140 oF. Motor bearings are permanently sealed, self lubricating ball type. All fans are 100% speed controllable through a decrease in the voltage by using a solid state or transformer type control.
Guide Specifications for Inline Duct Fans Supply, exhaust or return air inline fans shall be of the centrifugal, direct driven type.
Housing
• Fan housing shall be constructed of UV resistant ABS-PC blend thermo plastic.
• Fan shall be supplied with an integral external electrical terminal box with pre-wired terminal strip connections.
• Capacitor shall be provided and shall be located within the fan electrical terminal box for easy access.
Motor
• Motorized impeller shall be an external rotor type, class B insulation, totally enclosed PSC Type for maximum efficiency.
• Motor shall be a permanently sealed self-lubricating ball bearing type.
• Motor shall be equipped with automatic reset thermal overload protection.
• Motor shall be acceptable for continuous duty.
• Sufficient service factor shall be provided to ensure long maintenance free operation over maximum load conditions.
Wheel
• Fan wheel shall be of the backward inclined centrifugal type with a well-designed inlet venturi for maximum performance.
• Motorized impeller shall be both statically and dynamically balanced as one integral unit to provide for vibration free performance.
Performance
• Fan air flow performance shall be certified by HVI and licensed to bear the HVI Tested/Certified Performance Logo.
Code Approval
• Fan shall be tested and approved by UL and CSA (or equal) for safety.
Contractor will also need mounting and venting materials.