DEPARTMENT OF THE AIR FORCE
OKLAHOMA CITY AIR LOGISTICS COMPLEX
TINKER AIR FORCE BASE OKLAHOMA
MEMORANDUM FOR RECORD
SUBJECT: Item Description, Booster Pumps
Reference:
1. The is requesting utilization of funds to procure adequate booster pumps in order to fulfill requiremen The booster pumps will replace existing pumps within
2. The requested equipment item descriptions/specifications are outlined below.
a. Xylem Goulds Pump Aquaforce e-HV Series Booster Pump or equivalent
(1) Model Number: HVL4D3-10SV11GJ4F60-6GD with RS485 BMS or equivalent
(2) Quantity: Two (2)
(3) The booster pump must meet the following requirements
(a) Four vertically assembled multistage centrifugal pumps in parallel with pump split
25/25/25/25, (Lead + Lag 1 + Lag 2 + Lag 3)
(b) Stainless steel: pump body, impeller, diffuser, casing, and shaft; Stainless steel pedestal and base mounted
(c) Voltage 460/3/60, 3500rpm,
(d) Working liquid temperature 32F-180F
(e) Each single pump with Hydrovar VFD
(f) Electric disconnect panel with pump circuit breakers
(g) Discharge transducers (1ea/VFD)
(h) Low Water Pressure Switch, Isolation Butterfly Valves, Wafer Check Valve
(i) Pressure gauge for suction and discharge manifolds
(j) Duty Point Flow rate 220 GPM @ 465 ft Head
OC-ALC OBCA 2
SUBJECT: Item Description, M19-072 Booster Pumps
(k) Max. Operating Pressure 270 psi
(l) Single Pump 10HP
(m) Single Pump Total Impeller Stages =11, 2 Pole
(n) Prem-TEFC Pump Motor Enclosure
(o) Built-in protection for motor and inverter over temperature
(p) Overall Assembly Dimension 60”L x 40”D x 60”H
(q) RS-485 Communication, Bacnet, RTU, ASCII for Full Integration Into Building
Management System (Communication Protocol)
(r) VFD Schematic Diagram and Installation & Operation Manual
b. Xylem Goulds Pump Aquaforce e-HV Series Booster Pump or equivalent
(1) Model Number: HVL3D2-5SV18GH4F60-4GD with RS485 BMS or equivalent
(2) Quantity: One (1)
(3) The booster pump must meet the following requirements:
(a) Three vertically assembled multistage centrifugal pumps in parallel with pump split 33/33/33, (Lead + Lag 1 + Lag 2)
(b) Stainless steel: pump body, impeller, diffuser, casing, and shaft; Stainless steel pedestal and base mounted
(c) Dia. 2” Header Stainless Steel Suction and Discharge Manifolds w/ Victaulic end
(d) Voltage 460/3/60, 3500rpm
(e) Working Liquid Temperature 32F-180F
(f) Each Single Pump with Hydrovar VFD
(g) Electric Disconnect Panel with Pump Circuit Breakers
(h) Discharge Transducers (1ea/VFD)
(i) Low Water Pressure Switch
OC-ALC OBCA 3
SUBJECT: Item Description, M19-072 Booster Pumps
(j) Isolation Ball Valves
(k) Silent Check Valve
(l) Pressure gauge for suction and discharge manifolds
(m) Duty Point Flow rate 95 GPM @ 460 ft Head
(n) Max. Operating Pressure 270 psi
(o) Single Pump 7.5HP
(p) Single Pump Total Impeller Stages =18, 2 Pole
(q) Prem-TEFC Pump Motor Enclosure
(r) Built-in protection for motor and inverter over temperature
(s) Overall Assembly Dimension 44”L x 40”D x 60”H
(t) RS-485 Communication, Bacnet, RTU, ASCII for Full Integration Into Building
Management System (Communication Protocol)
(u) VFD Schematic Diagram and Installation & Operation Manual
c. Xylem Bell & Gossett ASME Bladder Expansion Tank or equivalent
(1) Quantity: One (1)
(2) The expansion tank must meet the following requirements:
(a) ASME Code Vertical Bladder Expansion Tank with ASME data plate
(b) Factory Pre-Charged
(c) Operating temperature up to 300F
(d) Heavy duty diaphragm
(e) Tank Material of construction - Carbon Steel
(f) Charging Valve
(g) Working Pressure 300 psi rating
(h) Tank volume 132 gallon
OC-ALC OBCA 4
SUBJECT: Item Description, Booster Pumps
(i) Tank Acceptance factor 0.65
(j) Tank Size: Max. 85” Height, Max. 24" Diameter
(k) Dia. 2" System Connection
(l) Exterior Finish Gray Powder Paint