Item_Description_Heat_Exchangers.pdf
PDF 75 KB Posted
- Attached to
- PROCESS WATER HEAT EXCHANGERS Federal contract opportunity
- Solicitation number
- FA8125-19-Q-0005
About this file
ITEM DESCRIPTION
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA812519Q0005_AMENDMENT.docx | DOCX document | |
| Attachment_4_Current_Heat_Exchanger_Diagram.pdf | ||
| Heat_Excahngers_SOW.docx | DOCX document | |
| FA812519Q0005_Solicitation.docx | DOCX document | |
| Attachment_3_Current_Heat_Exchangers_Pictures.pdf | ||
| Attachment_2_Current_Heat_Exchanger_Schedule.pdf | ||
| SOW_(1)_Heat_Exchangers.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Commodity Item Description for the C19-016 Bldg. 3902 Heat Exchangers Replacement
-Two (2) Brand Name or Equivalent WCR Plate Heat Exchanger Model: WCR-UFX60 (Custom Fit per Attachment 4, 12 to 14 week lead time)
• Frame Material: Carbon Steel
• Frame Height (H) (in): 62"
• Frame Length (L) (in): 102"
• Heat Transfer Area: 1,494.9 ft²
• 8" Studded 316 connections
• 279) 0.5 mm 316L Plates
• NBR Clip Flow gaskets
• Single-Pass Flow
• Max Number of Plates: 319
• ASME rated 150 PSI at 230°F
• Safety Shroud included
Any Model being submitted outside of the unit above must meet the following minimum requirements and fit on the provided concrete pads.
A. Two (2) each “Plate” style heat exchangers
• Hot fluid side flow rate of 2908 gpm minimum
• Hot fluid side minimum inlet temperature of 65 to 75 degrees
• Cold fluid side flow rate of 1700 to 2800 gpm minimum
• Cold fluid side maximum inlet temperature of 45 to 50 degrees
• 100psi design operating pressure
• 150psi peak pressure @ 230°F design pressure
• Dimension no larger than 102”L X 42”W X 62”H
-On-site installation in accordance with SOW