Attachment_A_Item_Description.pdf

PDF 54 KB Posted

Attached to
Hazardous Materials Storage Buildings Federal contract opportunity
Solicitation number
FA8125-18-Q-0054
Issued by
Department of the Air Force Materiel Command Lifecycle Management Center Tinker Air Force Base

About this file

Attachment A Item Description

View the file

Other files for this federal contract opportunity

Other files attached to Hazardous Materials Storage Buildings, newest first.
File Type Posted
FA8125-18-Q-0054_Hazardous_Material_Storage_Buildings_QA.pdf PDF
FA8125-18-Q-0054_-_CSS_-Hazardous_Material_Storage_Buildings.doc_R1.pdf PDF
Attachment_B_Drawing.pdf PDF
FA8125-18-Q-0054_-_CSS_-Hazardous_Material_Storage_Buildings.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DEPARTMENT OF THE AIR FORCE

OKLAHOMA CITY AIR LOGISTICS COMPLEX (OC-ALC)

TINKER AIR FORCE BASE OKLAHOMA

Statement of Requirement / Item Description

A18-012 Hazardous Material Storage Buildings

Two (2) Hazardous Material Storage Buildings:

• Shall be 46’L x 14’W x 9’H

• Shall be climate controlled equipped with HVAC System

• Shall be equipped with dry chemical fire suppression System (Rated for Class A, B, C Fires)

• Shall be equipped with interior and exterior lighting

• Shall be equipped with two (2) sets of double doors (Both located on the long side of the storage building) 60” W x 80” H

• Shall have access ramps for each double door. Minimum ramp dimensions:

48’W x 88’L

• Shall be equipped with a dual thermostat (Explosion Proof ) (Class I, Division 1

Groups B-D)

• Shall be equipped with premanufactured fire Sprinkler System with separate control valves Per UFC3-600-01,4-16.7

• Prefabricated structures MUST meet requirements of NFPA400

• Shall have emergency eye wash station that complies with AFI 32-1066 Backflow

Prevention Program

• All Piping used for plumbing shall be hard drawn copper. External plumbing shall extends to the short side of the building, with each having opposing connections similar to the HVAC arrangement.

• Please see Attachment A( Drawing)