Atch_1a_-_CCLD_Related_Wk_ _Ref_Docs.pdf

PDF 2 MB Posted

Attached to
Center for Character & Leadership Development Audio Visual Federal contract opportunity
Solicitation number
FA7000-15-T-0025
Issued by
Department of the Air Force Headquarters Air Force Academy

About this file

Attachment 1a CCLD Related Work Reference Documents For Informational Purposes Only

View the file

Other files for this federal contract opportunity

Other files attached to Center for Character & Leadership Development Audio Visual, newest first.
File Type Posted
Pre-award_notice_SB.pdf PDF
USAFA_CCLD_AV_Site_Visit_Q As_(4).docx DOCX document
CCLD-Room_Numbers_-_Room_Availability.pdf PDF
USAFA_CCLD_AV_Site_Visit_Q As_(3).docx DOCX document
USAFA_CCLD_AV_Site_Visit_Q As_(2).docx DOCX document
CCLD_SAG_Meeting_Apr_2015_Full_SAG__20150403.pptx PPTX presentation
FA7000-15-T-0025_CCLD_AV_Amendment_2.pdf PDF
USAFA_CCLD_AV_Site_Visit_Q As.docx DOCX document
Atch_1_-_CCLD_AV_Systems_General_Requirments__Specifications.pdf PDF
Exibit_B_-_CCLD_AV_Equipment_List.xlsx XLSX spreadsheet
FA7000-15-T-0025_CCLD_AV_RFQ.pdf PDF
Index_of_Attachments.docx DOCX document
Exhibit_A_CDRLs.pdf PDF
Exibit_C-_CCLD_Gifts.xlsx XLSX spreadsheet
Atch_2a_-_CCLD_Drw_Set_08_4017_2300.pdf PDF
Atch_2_-_CCLD_AV_Systems_and_Equipment.pdf PDF
Show all 16

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

For Inf orm ati on al

Purp os es O nly

USAFA-CCLD\div26\26 04 00 Attachment 1a – CCLD Related Wk & Ref Docs

SECTION 26 04 00

MATERIALS AND METHODS COMMON TO ELECTRICAL

PART 1 - GENERAL

1.1 SUMMARY

A. General: Provide Materials and Methods Common to Electrical in accordance with requirements of the Contract Documents.

1.2 SYSTEM DESCRIPTION

A. Drawings: The layouts of the various items of equipment, accessories, specialties, and wiring on the Drawings are diagrammatic, unless specifically dimensioned, and do not necessarily indicate every box, conduit, switch, wiring device or similar items required for a complete installation.

B. Electrical Service Characteristics:

1. Distribution for Power and Fluorescent Lighting: 480Y/277 volts, 3 phase, 4 wire via conduit and cable risers.

2. Distribution for Incandescent Lighting and Convenience Outlets: 208Y/120 volts, 3 phase, 4 wire via dry type transformers and distribution panels.

3. Distribution for Emergency Power and Lighting: 480Y/277 volts, 3 phase, 4 wire via conduit and cable risers and distribution panels.

4. Motors 1/2 HP and Greater: Furnish to operate on 480 volts, 3 phase, 60 hertz service.

5. Motors Less Than 1/2 HP: Furnish to operate on 120 volts, single phase, 60 hertz service.

C. Computer Equipment Areas: 480Y/277 volt, and/or 208Y/120 volt, 3 phase, 4 wire, 60 hertz.

Provide non-linear, dry type transformers and non-linear receptacle panels with 200% neutral bus and isolated ground bus.

D. Green Building Performance Criteria: Provide the Work and submit documentation demonstrating compliance with the credit requirements of LEED NC, Version 2.2, as specified in Section 01 81 13, SUSTAINABLE DESIGN REQUIREMENTS.

1.3 SUBMITTALS

A. Product Data: Submit for Contracting Officer's action. Furnish manufacturer's literature, specifications and installation instructions describing the general properties of each material and accessory to be used in the Work. Furnish data for the following.

United States Air Force Academy Materials and Methods Common to Electrical Center for Character & Leadership Development 26 04 00-1 100% CD Redesign I April 13, 2012

Copyright © Skidmore, Owings & Merrill LLP

For information purposes only.

orm ati on al

Purp os es O

1. Identification materials.

2. Sleeve seals.

B. Shop Drawings: Submit for Contracting Officer's action. Furnish shop drawings for the fabrication and installation of the Work. Include floor layouts at not less than 1/8" = 1'-0" minimum scale showing equipment, wireways and conduit. Provide sections at not less than 1/4" = 1'-0" minimum scale. Show typical details of the conditions for every member, joint, anchorage and support in the system, including locations of seismic restraining devices.

C. Green Building Submittal Requirements: Submit the necessary documentation to verify compliance with LEED NC requirements as specified in Section 01 81 13, SUSTAINABLE

DESIGN REQUIREMENTS.

D. Closeout Submittals: Submit for Government's documentation.

1. Record Drawings: Furnish record drawings annotated with the changes made during installation of the Work so as to be a complete set of "as installed" plans and wiring diagrams.

1.4 QUALITY ASSURANCE

A. Contractor's Quality Control Responsibilities: Contractor is solely responsible for quality control of the Work.

B. Regulatory Requirements: Comply with applicable requirements of the laws, codes, ordinances and regulations of Federal, State and Municipal authorities having jurisdiction.

Obtain necessary approvals from all such authorities.

1.5 DELIVERY, STORAGE, AND HANDLING

A. General: Deliver and store materials in manufacturer's original packaging labeled to show name, brand, type, and grade. Store materials in protected dry location off ground in accordance with manufacturer's instructions. Do not open packaging nor remove labels until time for installation.

1.6 PROJECT / SITE CONDITIONS

A. Weather Conditions: Do not proceed with the Work during inclement weather nor when weather forecasts are unfavorable, unless the Work will proceed in accordance with the manufacturer's requirements and instructions and any agreements or restrictions of the Pre-Construction Conference.

PART 2 - PRODUCTS

2.1 TEMPLATES

A. General: Provide templates or details for chases and openings to be left in the floors, walls and partitions to accommodate the Work.

2.2 SEALANT FOR CONDUIT AND CABLE PENETRATIONS

A. Firestop Systems: Refer to Section 07 84 00, FIRESTOPPING.

United States Air Force Academy Materials and Methods Common to Electrical Center for Character & Leadership Development 26 04 00-2 100% CD Redesign I April 13, 2012 orm ati on al

Purp os es O

B. Sleeve-Seal Systems: Modular sealing device, designed for field assembly, to fill annular space between sleeve and raceway or cable.

Advance Products & Systems, Inc.

CALPICO, Inc.

Metraflex Company (The) Pipeline Seal and Insulator, Inc.

Proco Products, Inc.

1. Sealing Elements: EPDM or Nitrile (Buna N) rubber interlocking links shaped to fit surface of pipe. Include type and number required for pipe material and size of pipe.

2. Pressure Plates: Carbon steel for interior applications and stainless steel for exterior applications.

3. Connecting Bolts and Nuts: Carbon steel with corrosion-resistant coating, or stainless steel, to match pressure plate construction, of length required to secure pressure plates to sealing elements.

C. Sleeve-Seal Fittings: Manufactured plastic, sleeve-type, waterstop assembly made for embedding in concrete slab or wall. Unit shall have plastic or rubber waterstop collar with center opening to match piping OD.

D. Multiple Conduit / Cable Waterproof Seals: Single or multiple core ethylene- propylene rubber (EPDM) multi-diameter sealing modules consisting of two halves with removable layers and a center core, sized as required for the conduit size being sealed. Stainless steel flanged frames for casting, welding or bolting into place as required for the application, with extension as required for thick walls or floors to seal the entire depth of the entry. Coordinate frame sizes with the concrete openings prior to fabrication. Install frames with a sealing strip to provide a positive seal to the concrete. Provide all necessary tools and accessories for both horizontal and vertical installations.

Roxtec International AB "Type RM Seal and Type G Frame" or acceptable equivalent

2.3 SLEEVES

A. Wall Sleeves:

1. Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, zinc coated, plain ends.

2. Cast-Iron Pipe Sleeves: Cast or fabricated "wall pipe," equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop unless otherwise indicated.

B. Sleeves for Conduits Penetrating Non-Fire-Rated Gypsum Board Assemblies:

Galvanized-steel sheet; 0.0239"; round tube closed with welded longitudinal joint, with tabs for screw-fastening the sleeve to the board.

C. Sleeves for Rectangular Openings:

United States Air Force Academy Materials and Methods Common to Electrical Center for Character & Leadership Development 26 04 00-3 100% CD Redesign I April 13, 2012 orm ati on al

Purp os es O

1. Material: Galvanized sheet steel, minimum gage as follows.

a. For sleeve cross-section rectangle perimeter less than 50" and with no side larger than 16", thickness 0.052".

b. For sleeve cross-section rectangle perimeter 50" or more and one or more sides larger than 16", thickness 0.138".

2.4 IDENTIFICATION MATERIALS

A. Power Raceway Identification Materials:

1. General: Comply with ANSI A13.1 for minimum size of letters for legend and for minimum length of color field for each raceway size.

2. Colors for Raceways Carrying Circuits at 600 V or Less:

a. Black letters on an orange field.

b. Legend: Indicate voltage and system or service type.

3. Self-Adhesive Vinyl Labels for Raceways Carrying Circuits at 600 V or Less:

Preprinted, flexible label laminated with a clear, weather- and chemical-resistant coating and matching wraparound adhesive tape for securing ends of legend label.

4. Snap-Around Labels for Raceways Carrying Circuits at 600 V or Less: Slit, pretensioned, flexible, preprinted, color-coded acrylic sleeve, with diameter sized to suit diameter of raceway or cable it identifies and to stay in place by gripping action.

5. Snap-Around, Color-Coding Bands for Raceways Carrying Circuits at 600 V or Less:

Slit, pretensioned, flexible, solid-colored acrylic sleeve, 2" long, with diameter sized to suit diameter of raceway or cable it identifies and to stay in place by gripping action.

6. Metal Tags: Brass or aluminum, 2" x 2" x 0.05", with stamped legend, punched for use with self-locking cable tie fastener.

B. Power and Control Cable Identification Materials:

1. General: Comply with ANSI A13.1 for minimum size of letters for legend and for minimum length of color field for each raceway and cable size.

2. Self-Adhesive Vinyl Labels: Preprinted, flexible label laminated with a clear, weather-and chemical-resistant coating and matching wraparound adhesive tape for securing ends of legend label.

3. Metal Tags: Brass or aluminum, 2" x 2" x 0.05" with stamped legend, punched for use with self-locking cable tie fastener.

4. Snap-Around Labels: Slit, pretensioned, flexible, preprinted, color-coded acrylic sleeve, with diameter sized to suit diameter of raceway or cable it identifies and to stay in place by gripping action.

United States Air Force Academy Materials and Methods Common to Electrical Center for Character & Leadership Development 26 04 00-4 100% CD Redesign I April 13, 2012 orm ati on al

Purp os es O

5. Snap-Around, Color-Coding Bands: Slit, pretensioned, flexible, solid-colored acrylic sleeve, 2" long, with diameter sized to suit diameter of raceway or cable it identifies and to stay in place by gripping action.

C. Conductor Identification Materials:

1. Color-Coding Conductor Tape: Colored, self-adhesive vinyl tape not less than 3 mils thick by 1 to 2" wide.

2. Self-Adhesive Vinyl Labels: Preprinted, flexible label laminated with a clear, weather-and chemical-resistant coating and matching wraparound adhesive tape for securing ends of legend label.

3. Snap-Around Labels: Slit, pretensioned, flexible, preprinted, color-coded acrylic sleeve, with diameter sized to suit diameter of raceway or cable it identifies and to stay in place by gripping action.

4. Snap-Around, Color-Coding Bands: Slit, pretensioned, flexible, solid-colored acrylic sleeve, 2" long, with diameter sized to suit diameter of raceway or cable it identifies and to stay in place by gripping action.

5. Marker Tapes: Vinyl or vinyl-cloth, self-adhesive wraparound type, with circuit identification legend machine printed by thermal transfer or equivalent process.

D. Floor Marking Tape:

1. General: 2" wide, 5-mil pressure-sensitive vinyl tape, with black and white stripes and clear vinyl overlay.

E. Warning Labels and Signs:

1. General: Comply with NFPA 70 and 29 CFR 1910.145.

2. Self-Adhesive Warning Labels: Factory-printed, multicolor, pressure-sensitive adhesive labels, configured for display on front cover, door, or other access to equipment unless otherwise indicated.

3. Baked-Enamel Warning Signs:

a. Preprinted aluminum signs, punched or drilled for fasteners, with colors, legend, and size required for application.

b. 1/4" grommets in corners for mounting.

c. Nominal size, 7" x 10".

4. Metal-Backed, Butyrate Warning Signs:

a. Weather-resistant, nonfading, preprinted, cellulose-acetate butyrate signs with 0.0396"galvanized-steel backing; and with colors, legend, and size required for application.

United States Air Force Academy Materials and Methods Common to Electrical Center for Character & Leadership Development 26 04 00-5 100% CD Redesign I April 13, 2012 orm ati on al

Purp os es O

b. 1/4" grommets in corners for mounting.

c. Nominal size, 10" x 14".

5. Warning Label and Sign: Shall include, but are not limited to, the following legends.

a. Multiple Power Source Warning: "DANGER - ELECTRICAL SHOCK

HAZARD - EQUIPMENT HAS MULTIPLE POWER SOURCES".

b. Workspace Clearance Warning: "WARNING - OSHA REGULATION - AREA

IN FRONT OF ELECTRICAL EQUIPMENT MUST BE KEPT CLEAR FOR

36 INCHES".

F. Instruction Signs:

1. General: Engraved, laminated acrylic or melamine plastic, minimum 1/16" thick for signs up to 20 in2 ,1/8" thick for larger sizes.

a. Engraved legend with black letters on white face.

b. Punched or drilled for mechanical fasteners.

c. Framed with mitered acrylic molding and arranged for attachment at applicable equipment.

2. Adhesive Film Label with Clear Protective Overlay: Machine printed, in black, by thermal transfer or equivalent process. Minimum letter height shall be 3/8". Overlay shall provide weatherproof and UV-resistant seal for label.

G. Equipment Identification Labels:

1. Adhesive Film Label: Machine printed, in black, by thermal transfer or equivalent process. Minimum letter height shall be 3/8".

2. Adhesive Film Label with Clear Protective Overlay: Machine printed, in black, by thermal transfer or equivalent process. Minimum letter height shall be 3/8". Overlay shall provide weatherproof and UV-resistant seal for label.

3. Self-Adhesive, Engraved, Laminated Acrylic or Melamine Label: Adhesive backed, with white letters on a dark-gray background. Minimum letter height shall be3/8".

4. Engraved, Laminated Acrylic or Melamine Label: Punched or drilled for screw mounting. White letters on a dark-gray background. Minimum letter height shall be 3/8".

5. Stenciled Legend: In nonfading, waterproof, black ink or paint. Minimum letter height shall be3/8".

H. Miscellaneous Identification Products:

1. Paint: Comply with requirements in Section 09 91 00 PAINTING for paint materials and application requirements. Select paint system applicable for surface material and location (exterior or interior).

United States Air Force Academy Materials and Methods Common to Electrical Center for Character & Leadership Development 26 04 00-6 100% CD Redesign I April 13, 2012 orm ati on al

Purp os es O

2. Fasteners for Labels and Signs: Self-tapping, stainless-steel screws or stainless-steel machine screws with nuts and flat and lock washers.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Verification of Conditions: Examine the areas to receive the Work and the conditions under which the Work would be performed. Remedy conditions detrimental to the proper and timely completion of the Work. Do not proceed until unsatisfactory conditions have been corrected.

3.2 PREPARATION

A. Painting:

1. Priming: Clean the surfaces and apply 1 shop coat of paint primer to shop-fabricated and factory-built equipment, devices and apparatus not galvanized, or protected by plating, or a baked enamel finish. Recoat portions of shop coat damaged in delivery, during construction, and prior to finish painting.

2. Finish Painting:

a. Coordinate the work with Section 09 91 00 "PAINTING", to ensure that equipment, devices, apparatus and exposed conduit are painted an ANSI Standard Color; unless otherwise directed by the Contracting Officer.

b. Equipment located in the same room or space shall be a matching color.

c. Do not allow painting of nameplates, labels, placards, tags, stainless steel and plated items as valve stems, motor shafts, levers, handles and trim strips.

3.3 INSTALLATION

A. General: Provide in accordance with the submittals and the manufacturer's written recommendations. Verify measurements and dimensions at the project site and coordinate with the Work of other trades. Install at locations shown, in correct alignment and elevation, plumb, level, straight and true. Use procedures that prevent damaging and soiling the Work during installation.

B. Firestopping: Refer to Section 07 84 00, FIRESTOPPING.

3.4 MOTOR AND DRIVE INSTALLATION AND WIRING

A. Installation and Connections: Install loose motors furnished under the Work of this trade.

Make electrical connections and check for correct rotation on building motors for fans, pumps and other equipment furnished with loose motors and controllers.

B. Motor Power Circuit Wiring: Provide complete power circuit wiring and connections for permanent mechanical equipment requiring electrical power supply, functional testing, special electrical equipment, and proper phasing out for the correct rotation of motors, and include Work up to and including connections at motor terminals, unless otherwise indicated..

United States Air Force Academy Materials and Methods Common to Electrical Center for Character & Leadership Development 26 04 00-7 100% CD Redesign I April 13, 2012 orm ati on al

Purp os es O

C. Control Circuit Wiring: Provide control circuit wiring, coordinated control wiring diagrams and sequence of operation for control wiring. Temperature control wiring and associated interlock wiring and equipment are provided as part of the Building Automation System.

D. Special Requirements: The Contract Documents are intended to fully delineate control circuit wiring required for motorized and other electrical equipment in the project. The possibility of variation from the Drawings due to differences between manufacturers of mechanical equipment and other conditions is anticipated. The Drawings and Specifications are not intended to limit the scope of the control wiring work. Provide complete electric control circuit wiring required for every item of permanent equipment in the project, without additional cost to the Government. Include the following.

1. Mount motor starter actuating devices which are furnished in Work included under other Sections of the Specifications.

2. Modify factory internal wiring of motor starters if and where required by the indicated control schemes.

3.5 APPLIANCES, HARDWARE, SPECIAL EQUIPMENT, SECURITY, ALARMS, COMMUNICATIONS

AND SIGNALLING SYSTEMS

A. General: Provide complete installation of wiring to interconnect all parts as required for proper operation of the electrical components and systems. Install and wire the systems, equipment and devices in strict accordance with the manufacturers' recommendations for power, wiring, interlocking, and grounding. Contractor shall consult with the manufacturers to obtain all information required to provide completely wired electrical components and systems.

B. Circuiting: Utilize the panels and circuits indicated, or as directed by the Contracting Officer.

Where power supply circuits are not shown, connect the circuits to the nearest panelboards intended to supply such systems with suitable voltages and spare circuit breakers or space for installation.

1. Where GFI breakers are used to protect circuits, provide a separate neutral conductor for each circuit.

C. Power: Provide separate power supply circuit for each system so that a malfunction in one system does not affect any other system.

1. System voltages shall not exceed 120 VAC. Provide step-down transformers for the power voltages required by the application or required by code.

2. Provide low-voltage transformers where not furnished with low-voltage signalling or controlling devices.

D. Disconnects: Provide disconnect switches and lock-out switches for systems and equipment as required.

1. Provide a warning indicator on the handle of the branch circuit breaker to prevent accidental de-energizing of the systems.

United States Air Force Academy Materials and Methods Common to Electrical Center for Character & Leadership Development 26 04 00-8 100% CD Redesign I April 13, 2012 orm ati on al

Purp os es O

E. Control Circuit Wiring: For wiring and equipment of special control systems, refer to Division 08 Section HARDWARE; Division 23 Section INSTRUMENTATION AND CONTROL FOR HVAC; Division 28, ELECTRIC SAFETY AND SECURITY.

3.6 GAS VALVE AND GAS LEAK ALARM SYSTEM

A. General: Provide conduit, wiring devices, junction boxes, wiring, etc., to each alarm device as required for complete gas valve alarm system where required.

B. Gas Alarm: Provide 120 volt, single phase, service to each gas emergency shut-off valve and gas leak monitoring alarm panel, and specified in Division 28 ELECTRIC SAFETY AND

SECURITY.

3.7 SLEEVE, SEALANT AND ACCESS PANEL INSTALLATION

A. Templates: Lay out the work in accordance with accepted shop drawings. Furnish and set in place in advance of pouring of slabs or construction of walls, inserts and sleeves necessary to complete the Work.

B. Fire Rated Penetrations: Firestopping sealants and safing are specified in Section 07 84 00, FIRESTOPPING.

C. Non-Fire-Rated Electrical Penetrations: Comply with NECA 1, comply with NEMA VE 2 for cable tray and cable penetrations.

1. Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.

2. Install sleeves for wall penetrations unless core-drilled holes or formed openings are used. Install sleeves during erection of walls. Cut sleeves to length for mounting flush with both surfaces of walls, unless otherwise indicated or required by Code. Deburr after cutting.

3. Install sleeves for floor and roof penetrations. Extend sleeves installed in floors 2" above finished floor level and roof sleeves 8" above roof. Install sleeves during erection of floors.

D. Sleeve-Seal-System:

1. Install sleeve-seal systems in sleeves in exterior concrete walls and slabs-on-grade at raceway entries into building to prevent the entrance of liquids (water), gases, vapors, and rodents into the building.

2. Install type and number of sealing elements recommended by manufacturer for raceway or cable material and size. Position raceway or cable in center of sleeve.

Assemble mechanical sleeve seals and install in annular space between raceway or cable and sleeve. Tighten stainless steel bolts and nuts bolts against pressure plates that cause sealing elements to expand and make watertight seal.

E. Sleeve-Seal-Fittings:

1. Install sleeve-seal fittings in new walls and slabs as they are constructed.

United States Air Force Academy Materials and Methods Common to Electrical Center for Character & Leadership Development 26 04 00-9 100% CD Redesign I April 13, 2012 orm ati on al

Purp os es O

2. Assemble fitting components of length to be flush with both surfaces of concrete slabs and walls. Position waterstop flange to be centered in concrete slab or wall.

F. Access Panels: Coordinate size and location of access panels required for access to pull boxes and electrical equipment. Where, in the opinion of the Contractor, access panels are required, but are not indicated on the Drawings, bring the omission to the attention of the Contracting Officer before installation of equipment. Note on shop drawings.

3.8 SUPPORTING DEVICE INSTALLATION

A. Equipment Foundations and Supports: Provide concrete supports, including concrete housekeeping pads, pedestals, bases, curbs and anchor blocks for all floor mounted equipment and apparatus. Provide anchor bolts, slab inserts, supports, hangers and sleeves required and necessary for proper support and attachment to the building structure for conduit, equipment and apparatus.

1. Concrete Supports:Coordinate installation to ensure that concrete supports are correctly located and sized, are a minimum of 6" high unless otherwise indicated, are adequately reinforced, and are complete with all required bolts, anchors and accessories. Extend concrete supports at least 6" beyond the equipment or apparatus base on all sides. Where concrete supports set directly on concrete floors, provide dowels or hair pins in the floors to tie the concrete supports to the floors.

Concrete work is specified in Section 03 30 00, CAST-IN-PLACE CONCRETE.

3.9 ELECTRICAL IDENTIFICATION

A. Installation:

1. Verify identity of each item before installing identification products.

2. Location: Install identification materials and devices at locations for most convenient viewing without interference with operation and maintenance of equipment.

3. Apply identification devices to surfaces that require finish after completing finish work.

4. Self-Adhesive Identification Products: Clean surfaces before application, using materials and methods recommended by manufacturer of identification device.

5. Attach signs and plastic labels that are not self-adhesive type with mechanical fasteners appropriate to the location and substrate.

6. System Identification Color-Coding Bands for Raceways and Cables: Each color-coding band shall completely encircle cable or conduit. Place adjacent bands of two-color markings in contact, side by side. Locate bands at changes in direction, at penetrations of walls and floors, at 30' maximum intervals in straight runs, and at 20' maximum intervals in congested areas.

7. Aluminum Wraparound Marker Labels and Metal Tags: Secure tight to surface of conductor or cable at a location with high visibility and accessibility.

United States Air Force Academy Materials and Methods Common to Electrical Center for Character & Leadership Development 26 04 00-10 100% CD Redesign I April 13, 2012 orm ati on al

Purp os es O

8. Cable Ties: For attaching tags. Use general-purpose type, except as listed below:

a. Outdoors: UV-stabilized nylon.

b. In Spaces Handling Environmental Air: Plenum rated.

9. Underground-Line Warning Tape: During backfilling of trenches install continuous underground-line warning tape directly above line at 6 to 8"below finished grade. Use multiple tapes where width of multiple lines installed in a common trench or concrete envelope exceeds 16" overall.

10. Painted Identification: Comply with requirements in Division 09 Section PAINTING for surface preparation and paint application.

B. Identification Schedule:

1. Accessible Raceways, 600 V or Less, for Service, Feeder, and Branch Circuits More Than 30A, and 120V to ground: Identify with self-adhesive vinyl tape applied in bands. Install labels at 10' maximum intervals.

2. Accessible Raceways and Cables within Buildings: Identify the covers of each junction and pull box of the following systems with self-adhesive vinyl labels with the wiring system legend and system voltage. System legends shall be as follows.

a. Emergency Power.

b. Normal Power.

3. Power-Circuit Conductor Identification, 600 V or Less: For conductors in vaults, pull and junction boxes, manholes, and handholes, use color-coding conductor tape to identify the phase.

a. Color-Coding for Phase and Voltage Level Identification, 600 V or Less: Use colors specified for ungrounded service, feeder and branch-circuit conductors.

4. Color shall be factory applied or field applied for sizes larger than No. 8 AWG, if authorities having jurisdiction permit.

a. Field-Applied, Color-Coding Conductor Tape: Apply in half-lapped turns for a minimum distance of 6"from terminal points and in boxes where splices or taps are made. Apply last two turns of tape with no tension to prevent possible unwinding. Locate bands to avoid obscuring factory cable markings.

5. Install instructional sign including the color code for grounded and ungrounded conductors using adhesive-film-type labels.

6. Conductors to Be Extended in the Future: Attach marker tape to conductors and list source.

7. Auxiliary Electrical Systems Conductor Identification: Identify field-installed alarm, control, and signal connections.

United States Air Force Academy Materials and Methods Common to Electrical Center for Character & Leadership Development 26 04 00-11 100% CD Redesign I April 13, 2012 orm ati on al

Purp os es O

a. Identify conductors, cables, and terminals in enclosures and at junctions, terminals, and pull points. Identify by system and circuit designation.

b. Use system of marker tape designations that is uniform and consistent with system used by manufacturer for factory-installed connections.

c. Coordinate identification with Project Drawings, manufacturer's wiring diagrams, and the Operation and Maintenance Manual.

8. Locations of Underground Lines: Identify with underground-line warning tape for power, lighting, communication, and control wiring and optical fiber cable.

a. Limit use of underground-line warning tape to direct-buried cables.

b. Install underground-line warning tape for both direct-buried cables and cables in raceway.

9. Workspace Indication: Install floor marking tape to show working clearances in the direction of access to live parts. Workspace shall be as required by NFPA 70 and 29 CFR 1926.403 unless otherwise indicated. Do not install at flush-mounted panelboards and similar equipment in finished spaces.

10. Warning Labels for Indoor Cabinets, Boxes, and Enclosures for Power and Lighting:

Baked-enamel warning signs.

a. Comply with 29 CFR 1910.145.

b. Identify system voltage with black letters on an orange background.

c. Apply to exterior of door, cover, or other access.

d. For equipment with multiple power or control sources, apply to door or cover of equipment including, but not limited to, the following:

1) Power transfer switches.

2) Controls with external control power connections.

11. Operating Instruction Signs: Install instruction signs to facilitate proper operation and maintenance of electrical systems and items to which they connect. Install instruction signs with approved legend where instructions are needed for system or equipment operation.

12. Emergency Operating Instruction Signs: Install instruction signs with white legend on a red background with minimum 3/8" high letters for emergency instructions at equipment used for power transfer or load shedding.

13. Equipment Identification Labels: On each unit of equipment, install unique designation label that is consistent with wiring diagrams, schedules, and the Operation and Maintenance Manual. Apply labels to disconnect switches and protection equipment, central or master units, control panels, control stations, United States Air Force Academy Materials and Methods Common to Electrical Center for Character & Leadership Development 26 04 00-12 100% CD Redesign I April 13, 2012 orm ati on al

Purp os es O terminal cabinets, and racks of each system. Systems include power, lighting, control, communication, signal, monitoring, and alarm systems unless equipment is provided with its own identification.

a. Labeling Instructions:

1) Indoor Equipment: Engraved, laminated acrylic or melamine label.

Unless otherwise indicated, provide a single line of text with 1/2" high letters on 1-1/2" high label; where two lines of text are required, use labels 2" high.

2) Elevated Components: Increase sizes of labels and letters to those appropriate for viewing from the floor.

3) Unless provided with self-adhesive means of attachment, fasten labels with appropriate mechanical fasteners that do not change the NEMA or NRTL rating of the enclosure.

b. Equipment to be Labeled:

1) Panelboards: Typewritten directory of circuits in the location provided by panelboard manufacturer. Panelboard identification shall be engraved, laminated acrylic or melamine label.

2) Enclosures and electrical cabinets.

3) Access doors and panels for concealed electrical items.

4) Switchboards.

5) Transformers: Label that includes tag designation shown on Drawings for the transformer, feeder, and panelboards or equipment supplied by the secondary.

6) Emergency system boxes and enclosures.

7) Enclosed switches.

8) Enclosed circuit breakers.

9) Enclosed controllers.

10) Variable-speed controllers.

11) Push-button stations.

12) Power transfer equipment.

13) Contactors.

14) Remote-controlled switches, dimmer modules, and control devices.

15) Power-generating units.

United States Air Force Academy Materials and Methods Common to Electrical Center for Character & Leadership Development 26 04 00-13 100% CD Redesign I April 13, 2012 orm ati on al

Purp os es O

16) Monitoring and control equipment.

3.10 ADJUSTING

A. Upon completion of the Work repair surfaces that have been permanently stained, marred, or otherwise damaged. Replace Work which is damaged or cannot be adequately cleaned as directed.

3.11 CLEANING

A. Upon completion of the Work, remove unused materials, debris, containers and equipment from the project site.

3.12 PROTECTION

A. Protect the Work during the construction period so that it will be without any indication of use or damage at the time of acceptance.

END OF SECTION

United States Air Force Academy Materials and Methods Common to Electrical Center for Character & Leadership Development 26 04 00-14 100% CD Redesign I April 13, 2012 orm ati on al

Purp os es O nly

USAFA-CCLD\div26\26 05 19 Attachment 1a – CCLD Related Wk & Ref Docs

SECTION 26 05 19

LOW-VOLTAGE POWER CONDUCTORS AND CABLES

PART 1 - GENERAL

1.1 SUMMARY

A. General: Provide Low-Voltage Power Conductors and Cables in accordance with requirements of the Contract Documents.

1.2 SYSTEM DESCRIPTION

A. Branch Circuit Wiring: Provide branch circuit wire required to serve circuit numbers adjacent to equipment as indicated on the Drawings. Branch circuit wire is not indicated on the Drawings, except for home runs and equipment connections.

1. Provide separate neutral conductors for emergency lighting circuits from exit and stair signs.

2. Provide separate neutral and ground conductors for the isolated type duplex receptacles from the other receptacle circuits.

3. Limit home run branch circuit conductors to not more than nine (9) conductors in the same conduit.

4. Provide separate neutral conductors for theatrical lighting circuits.

B. Green Building Performance Criteria: Provide the Work and submit documentation demonstrating compliance with the credit requirements of LEED NC, Version 2.2, as specified in Section 01 81 13, SUSTAINABLE DESIGN REQUIREMENTS.

1.3 SUBMITTALS

A. Product Data: Submit for Contracting Officer's action. Furnish manufacturer's literature, specifications and installation instructions describing the general properties of each material and accessory to be used in the Work.

B. Quality Control Submittals: Submit for Contracting Officer's information.

1. Qualification Data: For testing agency.

2. Field quality-control test reports.

C. Green Building Submittal Requirements: Submit the necessary documentation to verify compliance with LEED NC requirements as specified in Section 01 81 13, SUSTAINABLE

DESIGN REQUIREMENTS.

D. Closeout Submittals: Submit for Government's documentation.

United States Air Force Academy Low-Voltage Power Conductors and Cables Center for Character & Leadership Development 26 05 19-1 100% CD Redesign I April 13, 2012 orm ati on al

Purp os es O

USAFA-CCLD\div26\26 05 19 Attachment 1a – CCLD Related Wk & Ref Docs

1. Record Drawings: Furnish record drawings annotated with the changes made during installation of the Work so as to be a complete set of "as installed" wiring diagrams.

1.4 QUALITY ASSURANCE

A. Contractor's Quality Control Responsibilities: Contractor is solely responsible for quality control of the Work.

B. Testing Agency Qualifications: An independent agency, with the experience and capability to conduct the testing indicated, that is a member company of the InterNational Electrical Testing Association or is a nationally recognized testing laboratory (NRTL) as defined by OSHA in 29 CFR 1910.7, and that is acceptable to authorities having jurisdiction.

1. Testing Agency's Field Supervisor: Person currently certified by the InterNational Electrical Testing Association or the National Institute for Certification in Engineering Technologies to supervise on-site testing specified in Part 3.

C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

D. Regulatory Requirements: Comply with applicable requirements of the laws, codes, ordinances and regulations of Federal, State and Municipal authorities having jurisdiction.

Obtain necessary approvals from all such authorities.

1.5 DELIVERY, STORAGE, AND HANDLING

A. General: Deliver and store materials in manufacturer's original packaging labeled to show name, brand, type, and grade. Store materials in protected dry location off ground in accordance with manufacturer's instructions. Do not open packaging nor remove labels until time for installation.

1. Conductors and Cable: Deliver wire and cable to the job in complete coils or reels with the manufacturer's name and a tag attached indicating wire size, type of insulation and the NFPA approval.

PART 2 - PRODUCTS

2.1 CONDUCTORS AND CABLES, 600 VOLTS AND LESS

A. General: Provide complete system of copper wire and cable conductors.

B. Wire Lubricant: Provide wire lubricant for wire pulling, compatible with and causing no deterioration to conductor insulation and wireway.

Ideal Electric "No. 77" Klein Tools "Synthetic Wax Lubricant" Minnesota Mining & Mfg. Co. (3M) "WLX"

C. Color Coding, Wire and Cable:

1. Factory color code secondary distribution feeders and branch circuit wiring No. 8 AWG and smaller as follows.

United States Air Force Academy Low-Voltage Power Conductors and Cables Center for Character & Leadership Development 26 05 19-2 100% CD Redesign I April 13, 2012 orm ati on al

Purp os es O nly

USAFA-CCLD\div26\26 05 19 Attachment 1a – CCLD Related Wk & Ref Docs

Phase A

208YI120 Volts Black

480YI277 Volts Yellow

B Red Brown C Blue Orange Neutral Ground

White Green

White w/Tracer Green

2. Control Wiring: Use colors other than those specified for secondary distribution.

3. Colored pressure-sensitive plastic tapes may be used to color code wire in sizes No. 6 AWG and larger, 3/4" or 1" wide, and in specified colors.

D. Wire, Branch Lighting and Receptacle Circuits: Type "TW", "THHN" or "THWN" copper conductors of not less than 98% conductivity with 600 volt insulation, not smaller than 12 gage unless otherwise indicated, suitable for 75oC operating temperature, and of types appropriate for dry and wet locations. For 120 volt branch circuits extending more than 70 feet from the associated panel do not use less than No. 10 AWG to the first fixture or other current-consuming outlet.

E. Wire and Cable, Branch Power Circuits: Type "THW", "THHN" or "THWN" copper conductors of not less than 98% conductivity with 600 volt insulation, not smaller than 12 gage unless otherwise indicated, suitable for 75oC operating temperature, and of types appropriate for dry and wet locations. For 120 volt branch circuits extending more than 70 feet from the associated panel do not use less than No. 10 AWG to the first fixture or other current-consuming outlet. Use stranded copper wiring for sizes No. 8 and larger.

F. Wire and Cable, Feeders, Subfeeders and Motor Power Circuits: Type "THW", "XHHW" or "THHN" copper conductors of not less than 98% conductivity with 600 volt insulation, not smaller than 12 gage unless otherwise noted, suitable for 75oC operating temperature, and of types appropriate for dry and wet locations. Rate feeder, subfeeder and motor power wiring at 600 volts regardless of size. Use stranded copper wiring for sizes No. 8 and larger.

G. Wire, Motor Control: Type "TW", "THHN" or "THWN" copper conductors of not less than 98% conductivity with 600 volt insulation, not smaller than 14 gage unless otherwise noted, suitable for 75oC operating temperature, and of types appropriate for dry and wet locations.

Install in continuous runs between terminal points, without splices.

H. Fixture Wire: Stranded Type "SF-1" copper, 14 gage rated 600 volts, suitable for minimum 150oC operating temperature, and of types appropriate for dry and wet locations unless otherwise indicated.

2.2 WIRE CONNECTIONS AND CONNECTING DEVICES

A. General: Provide wire connections and connecting devices approved for plenum use as required by the Authority Having Jurisdiction.

B. Feeder Taps: Make feeder taps with cast copper connectors with bakelite or phenolic insulating covers. Make terminal connections with solderless, 2 bolt clamp lugs.

O-Z/Gedney Thomas and Betts or acceptable equivalent

United States Air Force Academy Low-Voltage Power Conductors and Cables Center for Character & Leadership Development 26 05 19-3 100% CD Redesign I April 13, 2012 orm ati on al

Purp os es O

C. Branch Circuit Taps: Make taps and splices for branch circuit wiring No. 14 to No. 6 with approved solderless pressure spring connectors with insulators.

Ideal Industries, Inc.

Minnesota Mining & Mfg. Co. (3M) or acceptable equivalent

2.3 SLEEVES AND SEALANT FOR CABLES

A. Sleeves and Sealant: Refer to Section 26 04 00, MATERIALS AND METHODS COMMON

TO ELECTRICAL.

2.4 CABLE TIES

A. General-Purpose Cable Ties: Fungus inert, self extinguishing, one piece, self locking, Type 6/6 nylon.

1. Minimum Width: 3/16"

2. Tensile Strength at 73oF, According to ASTM D638: 12,000 psi

3. Temperature Range: Minus 40 to plus 185oF.

4. Color: Black except where used for color-coding.

B. UV-Stabilized Cable Ties: Fungus inert, designed for continuous exposure to exterior sunlight, self extinguishing, one piece, self locking, Type 6/6 nylon.

1. Minimum Width: 3/16".

2. Tensile Strength at 73oF, According to ASTM D638: 12,000 psi.

3. Temperature Range: Minus 40 to plus 185oF

4. Color: Black.

C. Plenum-Rated Cable Ties: Self extinguishing, UV stabilized, one piece, self locking.

1. Minimum Width: 3/16

2. Tensile Strength at 73oF According to ASTM D638: 7000 psi.

3. UL 94 Flame Rating: 94V-0.

4. Temperature Range: Minus 50 to plus 284oF.

5. Color: Black.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Verification of Conditions: Examine the areas to receive the Work and the conditions under which the Work would be performed. Remedy conditions detrimental to the proper and timely completion of the Work. Do not proceed until unsatisfactory conditions have been corrected.

United States Air Force Academy Low-Voltage Power Conductors and Cables Center for Character & Leadership Development 26 05 19-4 100% CD Redesign I April 13, 2012 orm ati on al

Purp os es O nly

USAFA-CCLD\div26\26 05 19 Attachment 1a – CCLD Related Wk & Ref Docs

3.2 PREPARATION

A. General: Set sleeves in cast-in-place concrete, masonry walls, and other structural components as they are constructed.

3.3 CONDUCTOR MATERIAL APPLICATIONS

A. Feeders: Copper. Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger.

B. Branch Circuits: Copper. Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger.

3.4 INSTALLATION OF CONDUCTORS AND CABLES

A. General: Provide in accordance with the submittals and the manufacturer's written recommendations. Verify measurements and dimensions at the project site and coordinate with the Work of other trades. Install at locations shown, in correct alignment and elevation, plumb, level, straight and true. Use procedures that prevent damaging and soiling the Work during installation.

B. Color Coding: Where conductors carry unlike voltage characteristics other than those hereinbefore noted and are installed in or pass through a common enclosure, properly color code such conductors. Tag or label conductors installed in or which pass through a common enclosure with corresponding markings indicated on the Drawings or mark so that feeder or cable may be readily identified. Use nonferrous tags or pressure sensitive labels securely fastened to cables, feeders and power circuits.

C. Cables: Conceal cables in finished walls, ceilings, and floors, unless otherwise indicated.

Install exposed cables parallel and perpendicular to surfaces of exposed structural members, and follow surface contours where possible.

D. Pulling Methods: Use manufacturer-approved pulling compound or lubricant where necessary; compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will not damage cables or raceway.

E. Support: Refer to Section 26 05 29, HANGERS AND SUPPORTS FOR ELECTRICAL

SYSTEMS.

F. Identification: For identification and color-coding conductors and cables, refer to Section

26 04 00, MATERIALS AND METHODS COMMON TO ELECTRICAL.

1. Where conductors carry unlike voltage characteristics other than those hereinbefore noted and are installed in or pass through a common enclosure, properly color code such conductors. Tag or label conductors installed in or which pass through a common enclosure with corresponding markings indicated on the Drawings or mark so that feeder or cable may be readily identified. Use nonferrous tags or pressure sensitive labels securely fastened to cables, feeders and power circuits.

G. Firestopping: Refer to Section 07 84 00, FIRESTOPPING.

United States Air Force Academy Low-Voltage Power Conductors and Cables Center for Character & Leadership Development 26 05 19-5 100% CD Redesign I April 13, 2012 orm ati on al

Purp os es O

3.5 CONNECTIONS

A. Tightening: Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B.

B. Compatibility: Make splices and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conductors.

C. Wiring at Devices: Install conductor at each outlet, with at least 12" of slack.

3.6 FIELD QUALITY CONTROL

A. Testing Agency: Engage a qualified testing agency to perform tests and inspections and prepare test reports.

B. Tests and Inspections:

1. After installing conductors and cables and before electrical circuitry has been energized, test service entrance and feeder conductors, and conductors feeding the critical equipment and services for compliance with requirements.

2. Perform each visual and mechanical inspection and electrical test stated in NETA Acceptance Testing Specification. Certify compliance with test parameters.

a. Perform resistance measurements through bolted connections with low-resistance ohmmeter in accordance with NETA ATS-2009.

b. Perform insulation-resistance test on each conductor with respect to ground and adjacent conductors. Applied potential shall be 500 volts DC for 300 volt rated cable and 1000 volts DC for 600 volt rated cable. Test duration shall be

1.0 minute.

c. Perform continuity tests to insure correct cable connection.

d. Verify uniform resistance of parallel conductors.

e. Compare bolted connection resistances to values of similar connections.

f. Bolt-torque levels should be in accordance with NETA ATS-2009 unless otherwise specified by manufacturer.

g. Microhm or millivolt drop values shall not exceed the high levels of the normal range as indicated in the manufacturer's published data. If manufacturer's data is not available, investigate any values which deviate from similar connections by more than 50% of the lowest value.

h. Insulation-resistance values should be not less than 5.0 megohms.

i. Investigate deviations in resistance between parallel conductors.

United States Air Force Academy Low-Voltage Power Conductors and Cables Center for Character & Leadership Development 26 05 19-6 100% CD Redesign I April 13, 2012 orm ati on al

Purp os es O nly

USAFA-CCLD\div26\26 05 19 Attachment 1a – CCLD Related Wk & Ref Docs

3. Infrared Scanning: After Substantial Completion, but not more than 60 days after Final Acceptance, perform an infrared scan of each splice in cables and conductors No. 3 AWG and larger. Remove box and equipment covers so splices are accessible to portable scanner.

a. Follow-up Infrared Scanning: Perform an additional follow-up infrared scan of each splice 11 months after date of Substantial Completion.

b. Instrument: Use an infrared scanning device designed to measure temperature or to detect significant deviations from normal values. Provide calibration record for device.

c. Record of Infrared Scanning: Prepare a certified report that identifies splices checked and that describes scanning results. Include notation of deficiencies detected, remedial action taken, and observations after remedial action.

C. Test Reports: Prepare a written report to record the following:

1. Test procedures used.

2. Test results that comply with requirements.

3. Test results that do not comply with requirements and corrective action taken to achieve compliance with requirements.

3.7 ADJUSTING

A. Repair or replace components which do not operate as specified.

3.8 CLEANING

A. Upon completion of the Work, remove unused materials, debris, containers and equipment from the project site.

3.9 PROTECTION

A. Protect the Work during the construction period so that it will be without any indication of use or damage at the time of acceptance.

END OF SECTION

United States Air Force Academy Low-Voltage Power Conductors and Cables Center for Character & Leadership Development 26 05 19-7 100% CD Redesign I April 13, 2012 orm ati on al

Purp os es O

USAFA-CCLD\div26\26 05 26 Attachment 1a – CCLD Related Wk & Ref Docs

SECTION 26 05 26

GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1.1 SUMMARY

A. General: Provide Grounding and Bonding for Electrical Systems in accordance with requirements of the Contract Documents.

1.2 REFERENCES

A. Institute of Electrical & Electronics Engineers (IEEE): IEEE C2, "National Electrical Safety Code".

B. National Fire Protection Association (NFPA):

1. NFPA 70, "National Electrical Code".

2. NFPA 780, "Standard for the Installation of Lightning Protection Systems".

C. Underwriters Laboratories, Inc. (UL):

1. UL 96, "Lightning Protection Components".

2. UL 467, "Grounding and Bonding Equipment".

1.3 SYSTEM DESCRIPTION

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

1. Comply with UL 467.

B. Comply with NFPA 70. For overhead-line construction and medium-voltage underground construction comply with IEEE C2.

C. Comply with NFPA 780 and UL 96 when interconnecting with lightning protection system.

D. Comply with ANSI J-STD-607-A when grounding electrical/telecommunication systems.

E. Green Building Performance Criteria: Provide the Work and submit documentation demonstrating compliance with the credit requirements of LEED NC, Version 2.2, as specified in Section 01 81 13, SUSTAINABLE DESIGN REQUIREMENTS.

1.4 SUBMITTALS

A. Product Data: Submit for Contracting Officer's action. Furnish a material list with technical data documenting the primary function, quality, and performance of each system to be used in the…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .