AV__94_AW_Command_Questions.docx

DOCX document 14 KB Posted

Attached to
Audio Visual System Federal contract opportunity
Solicitation number
FA670317Q0022
Issued by
Department of the Air Force Reserve Command

About this file

ADDITIONAL QUESTIONS AND ANSWERS

View the file

Other files for this federal contract opportunity

Other files attached to Audio Visual System, newest first.
File Type Posted
Questions_and_Answers.pdf PDF
IMG_0586.jpg JPG image
IMG_0576.jpg JPG image
IMG_0572.jpg JPG image
IMG_0583.jpg JPG image
IMG_0581.JPG JPG image
IMG_0587.JPG JPG image
IMG_0575.jpg JPG image
IMG_0582.jpg JPG image
IMG_0577.jpg JPG image
IMG_0584.JPG JPG image
IMG_0578.jpg JPG image
IMG_0573.JPG JPG image
WD.pdf PDF
Combined_Solicitation_AV_Command_Post_1.pdf PDF
DARB4-Solicitation.pdf PDF
Bldg_838_PWS.DOCX DOCX document
Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AUDIO VISUAL 94 AW COMMAND POST

SOLICITATION FA670317Q022

DOBBINS ARB, GA

1. Is the ceiling air space in building 838, Dobbins ARB Plenum rated? If so plenum rated wiring will be required for all systems. I have contacted CE for an answer. I am awaiting a response.

1. Please confirm whether the control system interface for the podium is desired to be wired or wireless Wireless if possible.

1. Please confirm input requirements: Currently listed as 11 GOV laptops, 1 Podium CPU, 1 Classified GOV CPU, 1 Comcast HD box, 1 DVD/Bluray player and 1 base camera system feed. Those inputs are correct. However, we are currently working to have an additional camera feed for building 838. So, a total of 2 camera feeds will be required.

1. Please confirm type of video signal feed from the existing base cameras. Coaxial cable to BMC to RCA.

1. Please confirm that Microphone system and document scanner are being removed from the list of requirements for this room. They will NOT be a part of the new install and will be removed.

1. Is there a requirement for mandatory extra room % growth in rack and or HDMI Input matrix? Yes, at least 8-10% if possible.

1. Confirm it is OK for Control system to be connected to this rooms existing IP network. Contractor will have to consult with 94 Comm, per the SOW; however, the existing system is connected to the network.

1. During the walk through new requirement of 11 laptops was added in as input source? Yes

1. Should we redesign the system to accommodate these added source or would they not be needed or shared with the 4 displays and 2 projectors? Yes. They will need to be added.

1. Per Statement of Objective input sources are total of 6, does this mean we need to provide total of 17 inputs? Yes