40RUQ07---25 Split SystemHeat Pump Indoor Unit (Air---Handling Unit)
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Appendix_A_38AUQ-7-25-02PD_Product_Data_Exterior_Unit.pdf | ||
| ROT__Guarderia_HVAC.pdf | ||
| FA5575-18-Q-0001.pdf | ||
| Appendix_C_Drawings.pdf | ||
| Attachment_2_PWS__Youth_Center_HVAC_.pdf | ||
| Attachment_1_Pricing_Schedule.xls | XLS spreadsheet |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
40RUQ07---25
Split System Heat Pump Indoor Unit (Air---Handling Unit) With PuronR Refrigerant 60 Hz
Product Data
40RUQ 07 - 12
40RUQ 16 -25
C10887
Carrier’s versatile packaged heat pump air-handling units satisfy design requirements with:
S Multi--position design for horizontal or vertical installation without modification.
S Standard sloped drain pans and cleanable insulation treated with Environmental Protection Agency (EPA) registered antimicrobial agent improve indoor air quality.
S High-static design meets a wider range of applications than competitive packaged air handler lines.
S Economizer accessory provides ventilation air and “free” cooling.
S Cooling coils with mechanically bonded fins provide peak heat transfer.
S Hot water coil, steam coil, and electric heat accessories are available.
S Standard factory--installed thermo--static expansion valves (TXV) with removable power element on 40RUQ units.
S Die-formed galvanized steel casings provide durability and structural integrity. Optional paint is available.
FEATURES/BENEFITS
Easy-to-install and economical 40RU units provide reliable service.
The 40RUQ Series units with direct--expansion coils are the best choice for packaged heat pump air handlers. All models offer excellent fan performance, a unique combination of indoor air quality features, easy installation, and affordable prices. Their versatility and state--of--the--art features will provide economical performance now and in the future.
Indoor air quality features
The unique combination of features in the 40RUQ Series air handlers ensures that clean, fresh, conditioned air is delivered to the occupied space.
Cooling coils prevent the build--up of humidity in the room, even during part--load conditions.
FEATURES/BENEFITS (cont.)
Two--inch (51--mm) disposable filters remove dust and airborne particles from the occupied space.
Thermal insulation contains an immobilized anti--microbial agent to inhibit the growth of bacteria and fungi. The anti--microbial agent is registered with the U.S.
Environmental Protection Agency (EPA).
Pitched drain pan can be adjusted for a right--hand or left--hand connection to provide positive drainage and prevent standing condensate. Each unit contains two separate drain pans which are provided for either vertical or horizontal fan coil positions.
Accessory economizer can provide ventilation air to improve indoor air quality. When used with CO2 sensors, the economizer admits fresh outdoor air to replace stale, recirculated indoor air.
Economy
The 40RUQ Series packaged air handlers have low initial costs, and they continue to save money by providing reduced installation expense and energy--efficient performance.
Quick installation is ensured by the multi--position design.
Units can be installed in either the horizontal or vertical (upflow) configuration without modifications. All units have drain--pan connections on both sides, and pans can be pitched for right--hand or left hand operation with a simple adjustment.
Fan motors and contactors are pre--wired and TXVs are factory--installed on 40RUQ models.
High--efficiency, precision balanced fans minimize air turbulence, surging, and unbalanced operation, thereby cutting operating expenses.
Economizer accessory precisely controls the blend of outdoor air and room air to achieve comfort levels. When the outside air enthalpy is suitable, outside air dampers can fully open to provide “free” cooling.
Rugged dependability
Die--formed galvanized steel panels ensure structural integrity under all operating conditions. Mechanically bonded coil fins provide improved heat transfer.
Galvanized steel fan housings are securely mounted to a die--formed galvanized steel deck.
Coil flexibility
Model 40RUQ air handling units have galvanized steel casings; inlet and outlet connections are on the same end.
Direct expansion (DX) coils are designed for use with Puronr R--410A refrigerant and have copper tubes mechanically bonded to aluminum sine--wave fins.
Direct--expansion coils include matched, factory--installed thermostatic expansion valves (TXVs) with matching distributor nozzles.
Easier installation and service
The multi--position design and component layout allow for quick unit installation and operation. The DX coils have factory--installed TXVs with matching distributor nozzles. Units can be converted from horizontal to vertical operation by simply repositioning the unit.
Drain pan connections are duplicated on both sides of the unit. The filters, motor, drive, TXVs, and coil connections are easily accessed by removing a single side panel.
TABLE OF CONTENTS
PAGE
FEATURES AND BENEFITS 1
MODEL NUMBER NOMENCLATURE 3
PHYSICAL DATA 4
OPTIONS AND ACCESSORIES 5
DIMENSIONS 6
PERFORMANCE DATA 15
ELECTRICAL DATA 20
TYPICAL PIPING AND WIRING 30
TYPICAL CONTROL WIRING SCHEMATIC 32
APPLICATION DATA 33
GUIDE SPECIFICATIONS 36
R U Q
MODEL NUMBER NOMENCLATURE
Model Type 40RU = Packaged Air Handling Unit with Puron® R-410A Refrigerant
Type of Coil Q = DX Coil for Heat Pump Duty
Refrigerant Options A = None
Nominal Tonnage 07 = 6 Ton 16 = 15 Ton 08 = 7.5 Ton 25 = 20 Ton 12 = 10 Ton
Fan Motor Speed Controller A = None - Standard T = 2 Speed Fan Controller (VFD) - Staged Air Volume (SAVTM)
Indoor Fan Motor Options - Belt Drive NOTE: See the following two tables for Indoor Fan Motor Options for Single Speed and 2-Speed Motors. Available motors are indicated by a checkmark.
4Example 0 R U Q A 1 2 A 1 A 6 - 0 A 0 A 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Packaging 0 = Standard
Future Use A = Standard
Cabinet Paint 0 = None 1 = Painted
Future Use A = Standard
Revision Number
- = Standard
Voltage* 1 = 575/3/60 3 = 208/230-1-60 (07 and 08 sizes only) 5 = 208/230/3/60 6 = 460/3/60Coil Options
A = Standard Aluminum Fin / Copper Tube
Future Use 0 = Standard
Position
Notes:
* All 40RUQ07 through 16 units with a “6” voltage designation are triple voltage; ie., 208/230/460-3-60.
Size 40RUQ16 is also triple voltage in the “6” configuration unless the High Static (Alternate) motor option is used that is discrete 460-3-60.
Units that require 2-Speed indoor fan motor must use dedicated voltage models listed. The VFD used is not multi voltage.
C160009
Single Speed Motors Position 10 Motor Description Voltage
Unit Size 07 08 12 16 25
1 Std Static, Std Efficient Motor / Std Drive All n n n n – 4 Std Static, High Efficient Motor / Std Drive All – – – – n
2 Std Static, Std Efficient Motor / Med Drive All n n n n – 5 Std Static, High Efficient Motor / Med Drive All – – – – n
3 High (Alternate) Static, Std Efficient Motor / High Drive
575---3---60 n n n – – 208/230---1---60 n n – – – 208/230---3---60 460---3---60 n n n – –
6 High (Alternate) Static, High Efficient Motor / High Drive 575---3---60 – – – n n
208/230---3---60 460---3---60 – – – n n
2---Speed Motors Position 10 Motor Description Voltage
Unit Size 07 08 12 16 25
Std Static, Std Efficient Motor / Std Drive All n n n n – Std Static, High Efficient Motor / Std Drive All – – – – n
Std Static, Std Efficient Motor / Med Drive All n n – n – All – – – – n
High (Alternate) Static, Std Efficient Motor / Med Drive 575---3---60 – – n – – 208/230---3---60 460---3---60 – – – – –
High (Alternate) Static, High Efficient Motor / Med Drive 575---3---60 – – – – – 208/230---3---60 460---3---60 – – n – –
High (Alternate) Static, Std Efficient Motor / High Drive 575---3---60 n n n – – 208/230---3---60 460---3---60 n n – – –
High (Alternate) Static, High Efficient Motor / High Drive 575---3---60 – – – n n
208/230---3---60 460---3---60 – – n – –
R
PHYSICAL DATA
UNIT 40RUQ* 07 07T 08 12 16 25
NOMINAL CAPACITY (Tons) 6 6 71/2 10 15 20
OPERATING WEIGHT (lb) Base Unit with TXV 381 381 385 427 713 720 Plenum 175 175 175 175 225 225
FANS
Qty...Diam. (in.) 1...15 1...15 1...15 1...15 2...15 2...15 Nominal Airflow (cfm) 2400 2400 3000 4000 6000 8000 Airflow Range (cfm) 1800---3000 1800---3000 2250---3750 3000---5000 4500---7500 6000---10000 Nominal Motor Hp (Standard Motor)* 208/230---1---60 1.3 1.3 2.4 — — — 208/230---3---60 and 460---3---60 2.4 2.4 2.4 2.4 3.7 5.0 575---3---60 1.0 1.0 2.0 2.0 3.0 5.0 Motor Speed (rpm) 208/230---1---60 1725 1725 1725 — — — 208/230---3---60 and 460---3---60 1725 1725 1725 1725 1725 1760 575---3---60 1725 1725 1725 1725 1725 1745
REFRIGERANT R---410A R---410A R---410A R---410A R---410A R---410A
Operating charge (lb) (approx per circuit){ 3.0 3.0 3.0 2.0/2.0 3.0/3.0 3.5/3.5
DIRECT---EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine---Wave Fins Max Working Pressure (psig) 650 650 650 650 650 650 Face Area (sq ft) 8.33 8.33 8.33 10.0 16.56 19.9 No. of Splits 1 1 1 2 2 2 No. of Circuits per Split 15 12 12 9 10 10 Split Type...Percentage --- --- --- Face...50/50 Face...50/50 Face...50/50 Rows...Fins/in. 3...15 4...15 4...15 4...15 4...15 4...15
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 1...11/8 1...11/8 1...11/8 2...11/8 2...11/8 2...11/8 DX Coil — Liquid Refrigerant (ODF) 1...5/8 1...5/8 1...5/8 2...5/8 2...5/8 2...5/8 Steam Coil, In (MPT) 1...21/2 1...21/2 1...21/2 1...21/2 1...21/2 1...21/2 Steam Coil, Out (MPT) 1...11/2 1...11/2 1...11/2 1...11/2 1...11/2 1...11/2 Hot Water Coil, In (MPT) 1...11/2 1...11/2 1...11/2 1...11/2 1...2 1...2 Hot Water Coil, Out (MPT) 1...11/2 1...11/2 1...11/2 1...11/2 1...2 1...2 Condensate (PVC) 1...15/8 ODM / 11/4 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size (in.) 4...16 x 24 x 2 4...16 x 24 x 2 4...16 x 24 x 2 4...16 x 24 x 2 4...16 x 20 x 2 4...16 x 24 x 2
4...16 x 20 x 2 4...16 x 24 x 2
Access Location Either Side Either Side Either Side Either Side Either Side Either Side
STEAM COIL}
Max Working Pressure (psig at 260° F) 20 20 20 20 20 20 Total Face Area (sq ft) 6.67 6.67 6.67 6.67 13.33 13.33 Rows...Fins/in. 1...9 1...9 1...9 1...9 1...10 1...10
HOT WATER COIL}
Max Working Pressure (psig) 150 150 150 150 150 150 Total Face Area (sq ft) 6.67 6.67 6.67 6.67 13.33 13.33 Rows...Fins/in. 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 Water Volume (gal) 8.3 8.3 8.3 8.3 13.9 13.9 (ft3) 1.1 1.1 1.1 1.1 1.85 1.85
LEGEND
DX — Direct Expansion TXV— Thermostatic Expansion Valve { Units are shipped without refrigerant charge.
} Field installed accessory only.
* Refer to Alternate Fan Motor Data table for alternate motor data.
R U Q
1392442568E Highlight
OPTIONS AND ACCESSORIES
ITEM OPTION* ACCESSORY{
Alternate Fan Motors X Alternate Drives X Staged Air Volume System X CO2 Sensors X Condensate Drain Trap X Discharge Plenum X Economizer Ultra LOW LEAK---FDD X Economizer Standard Leak X Electric Heat X Hot Water Heating Coils X Overhead Suspension Package X Prepainted Units X Programmable Thermostats X Return Air Grille X Steam Heating Coil X Subbase X Display Kit for SAV system with VFD X
* Factory--- installed option.
{ Field--- installed accessory
Factory--installed options Alternate fan motors and drives are available to provide the widest possible range of performance.
Prepainted steel units are available from the factory for applications that require painted units. Units are painted with American Sterling Gray color.
Staged Air Volume (SAV) system saves energy and installation time by utilizing a Variable Frequency Drive (VFD) to automatically adjust the indoor fan motor speed in sequence with the units cooling operation. Per ASHRAE
90.1 2010 standard section 6.4.3.10.b, during the first stage of cooling operation the VFD will adjust the fan motor to provide 2/3rd of the total cfm established for the unit. When a call for the second stage of cooling is required, the VFD will allow the total cfm for the unit established (100%).
During the heating mode the VFD will allow total design cfm (100%) operation and during the ventilation mode the VFD will allow operation to 2/3rd of total cfm.
Compared to single speed indoor fan motor systems, Carrier’s SAV system can save substantial energy, 25%+*, versus single speed indoor fan motor systems.
*Data based on .10 ($/kWh) in an office application utilizing Carrier’s HAP 4.6 simulation software program.
The VFD used in Carrier’s SAV system has soft start capabilities to slowly ramp up the speeds, thus eliminating any high inrush air volume during initial start--up. It also has internal over current protection for the fan motor and a field installed display kit that allows adjustment and in depth diagnostics of the VFD.
This SAV system is available on models with 2--stage cooling operation with electrical mechanical controls.
The SAV system is very flexible for initial fan performance set up and adjustment. The standard factory shipped VFD is pre--programmed to automatically stage the fan speed between the first and second stage of cooling. The unit fan performance static pressure and cfm can be easily adjusted using the traditional means of pulley adjustments. The other means to adjust the unit static and cfm performance is to utilize the field installed
Display Kit and adjust the frequency and voltage in the VFD to required performance requirements. In either case, once set up, the VFD will automatically adjust the speed between the cooling stage operations.
Field--installed accessories CO2 sensors can be used in conjunction with the economizer accessory to help meet indoor air quality requirements. The sensor signals the economizer to open when the CO2 level in the space exceeds the set point. A Carrier Comfort System programmable thermostat can be used to override the sensor if the outside--air temperature is too high or too low.
Condensate drain trap includes an overflow shutoff switch that can be wired to turn off the unit if the trap becomes plugged. Kit also includes a wire harness that can be connected to an alarm if desired. The transparent trap is designed for easy service and maintenance.
Discharge plenum directs the air discharge directly into the occupied space; integral horizontal and vertical louvers enable redirection of airflow. Accessory is available unpainted or painted. Field assembly is required (only applicable for vertical application).
Economizers -- temperature dry bulb controlled --
Ultra LOW LEAK -- EconoMi$er X with solid--state W7220 controller, gear--driven, modulating damper, spring return actuator. Supply and outdoor air sensors, and CO2 sensor compatible, for use in electro mechanical controls only.
Also includes return and outside air damper leakage that meets California Title 24 section 140.4 requirements.
Controller meets California Title 24 Section 120.2 Fault Detection and Diagnostic (FDD) requirements.
STANDARD -- EconoMi$er IV -- with gear driven damper blades and W7212 controller (Use ----HH----57AC--078 for enthalpy control).
Electric resistance heat coils have an open--wire design and are mounted in a rigid frame. Safety cutouts for high temperature conditions are standard. Terminal block for single--point power connection is included.
Two--row hot water coils have copper tubes mechanically bonded to aluminum plate fins and non--ferrous headers.
Overhead suspension package includes necessary brackets to support units in horizontal ceiling installations.
Return--air grille provides a protective barrier over the return--air opening and gives a finished appearance to units installed in the occupied space. Accessory is available unpainted or painted.
One--row steam coil has copper tubes and aluminum fins.
The Inner Distributing Tube (IDT) design provides uniform temperatures across the coil face. The steam coil has a broad operating pressure range; up to 20 psi (138 kPag) at 260_F (126_C). The IDT steam coils are especially suited to applications where sub--freezing air enters the unit.
Subbase provides a stable, raised platform and room for condensate drain trap connection for vertical floor--mounted units. Accessory is available unpainted or painted.
R
DIMENSIONS
C14200
40RUQ*07, 08, 12
R
DIMENSIONS (cont.)
C14201
40RUQ*16 & 25
R
6 4
5 1
Fan
Fan
Coil
3 8
2 7
Steam Coil or Hot Water Coil
Base Unit Fan Coil Economizer
CORNER WEIGHTS
HORIZONTAL POSITION
C09039
40RUQ
UNIT SIZE
UNIT OR ACCESSORY
NAME
UNIT OR
ACCESSORY
WEIGHT
lb (kg)
CORNER NUMBER (WEIGHT IN LB)
1 2 3 4 5 6 7 8
07, 08, 12
FAN COIL BASE UNIT 394 (178.7) 108.0 104.7 89.4 92.2 — — — —
STEAM COIL ADD 137 (62.1) 25.6 0.0 0.0 25.9 42.4 43.0 0.0 0.0
HOT WATER COIL ADD 143 (64.9) 26.3 0.0 0.0 26.9 44.3 45.5 0.0 0.0
ECONOMIZER ADD 128 (58.5) 0.0 25.5 24.7 0.0 0.0 0.0 39.3 38.1
ECO + STEAM COIL ADD 264 (115.2) 25.6 25.5 24.7 25.9 42.4 43.0 39.3 38.1
ECO + HW COIL ADD 271 (122.9) 26.3 25.5 24.7 26.9 44.3 45.5 39.3 38.1
16, 25
FAN COIL BASE UNIT 684 (310.3) 220.5 174.9 127.8 161.1 — — — —
STEAM COIL ADD 239 (108.4) 43.2 0.0 0.0 43.6 75.8 76.5 0.0 0.0
HOT WATER COIL ADD 245 (111.1) 44.5 0.0 0.0 44.1 78.7 77.9 0.0 0.0
ECONOMIZER ADD 217 (98.4) 0.0 42.7 39.6 0.0 0.0 0.0 70.1 65.1
ECO + STEAM COIL ADD 456 (206.8) 43.2 42.7 39.6 43.6 75.8 76.5 70.1 65.1
ECO + HW COIL ADD 463 (210.0) 44.5 42.7 39.6 44.1 78.7 77.9 70.1 65.1
R
Motor
Economizer
Base Unit
NOTE: Steam, Hot Water & Plenum on top of positions 1,2,3,4
CORNER WEIGHTS
VERTICAL POSITION
C09040
40RUQ
UNIT SIZE
UNIT OR ACCESSORY
NAME
UNIT OR
ACCESSORY
WEIGHT
lb (kg)
CORNER NUMBER (WEIGHT IN LB)
1 2 3 4 5 6
07, 08, 12
FAN COIL BASE UNIT 394 (178.7) 99.3 113.5 96.8 84.7 — —
STEAM COIL ADD 137 (62.1) 34.5 34.5 34.0 34.0 0.0 0.0
HOT WATER COIL ADD 143 (64.9) 36.2 36.2 35.3 35.3 0.0 0.0
PLENUM ADD 175 (79.4) 50.8 36.7 36.7 50.8 0.0 0.0
ECONOMIZER ADD 128 (58.1) 25.5 0.0 0.0 24.7 39.3 38.1
ECO + STEAM COIL ADD 264 (119.7) 59.9 34.5 34.0 58.7 39.3 38.1
ECO + HW COIL ADD 271 (122.9) 61.7 36.2 35.3 60.0 39.3 38.1
16, 25
FAN COIL BASE UNIT 684 (310.3) 188.2 207.2 151.4 137.3 — —
STEAM COIL ADD 239 (108.4) 60.0 60.0 59.5 59.5 0.0 0.0
HOT WATER COIL ADD 245 (111.1) 61.0 61.0 61.6 61.6 0.0 0.0
PLENUM ADD 225 (102.1) 72.5 40.0 40.0 72.5 0.0 0.0
ECONOMIZER ADD 217 (98.4) 42.7 0.0 0.0 39.6 70.1 65.1
ECO + STEAM COIL ADD 456 (206.8) 102.7 60.0 59.5 99.1 70.1 65.1
ECO + HW COIL ADD 463 (210.0) 103.7 61.0 61.6 101.2 70.1 65.1
R
OVERHEAD SUSPENSION ACCESSORY
UNIT SIZES 07-12
(FRONT)
UNIT SIZES 16 & 25
(FRONT)
C10877
R
PLENUM, RETURN-AIR GRILLE, AND SUBBASE ACCESSORIES
UNIT SIZES 07-12
NOTE: Dimensions in [ ] are millimeters.
C10116
UNIT SIZES 16 & 25
(FRONT)
C10878
R
HOT WATER AND STEAM COIL ACCESSORIES
UNIT SIZES 07 - 12
NOTE: Dimensions in [ ] are millimeters.
DIMENSION HOT WATER COIL STEAM COIL
A 11/2″ MPT [38.1] 11/2″ MPT [38.1]
B 11/2″ MPT [38.1] 21/2″ MPT [63.5]
C 23/8″ [60.3] 31/8″ [79.4]
D 47/8″ [123.8] 31/8″ [79.4]
E 21/8″ [54.0] 49/16″ [115.8]
F 1′-111/4″ [590.6] 1′-9″ [584.2]
G 3′-4″ [1016.0] 3′-4″ [1016.0]
C10117
UNIT SIZES 16 & 25
DIMENSION HOT WATER COIL STEAM COIL
A 2″ MPT [50.8] 11/2″ MPT [38.1]
B 2″ MPT [50.8] 21/2″ MPT [63.5]
C 23/8″ [60.3] 31/8″ [79.4]
D 47/8″ [123.8] 31/8″ [79.4]
E 21/8″ [54.0] 49/16″ [115.8]
F 1′-111/4″ [590.6] 1′-9″ [584.2]
G 6′-8″ [2032.0] 6′-8″ [2032.0]
C10879
R U Q
UNIT SIZES 16 & 25
ECONOMIZER ACCESSORY
UNIT SIZES 07-12
NOTE:
1. For horizontal unit applications, economizer can be attached to end of unit opposite duct connections.
2. Dimensions in [ ] are millimeters.
C10889
R U Q
ELECTRIC HEAT ACCESSORY
UNIT SIZES 07 - 12
UNIT SIZE 16 - 25
C160008
UNIT SIZE A B C D E F G H J
16 --- 25 1’-31/4 [387.4]
4’-63/8 [1381.1]
25/16 [58.7]
2’-11/4 [641.4]
105/8 [269.9]
1’-4 [406.4]
1’-45/16 [414.3]
1’-63/4 [476.3]
1-7/8 [327.0]
NOTE: Dimensions in [ ] are millimeters.
R
PERFORMANCE DATA
COOLING ONLY PERFORMANCE
UNIT
40RUQ
EVAPORATOR AIR COIL REFRIGERANT TEMP _F (_C)
AIR
FLOW
(CFM)
EWB
_F (_C)
30 (---1.1) 35 (1.7) 40 (4.4) 45 (7.2) 50 (10)
TC SHC TC SHC TC SHC TC SHC TC SHC
72 (22.2) 146.4 71.0 132.1 64.3 116.7 57.3 100.0 49.7 81.8 42.0 67 (19.4) 121.8 74.0 107.6 66.4 92.4 58.9 76.0 51.2 58.3 43.6 62 (16.7) 99.3 75.5 85.3 67.9 70.2 60.2 54.9 52.4 44.2 44.2
72 (22.2) 179.3 87.1 161.7 79.1 142.6 70.4 122.0 61.2 99.5 51.8 67 (19.4) 149.5 91.5 132.2 82.4 113.3 73.2 93.0 63.8 71.0 54.4 62 (16.7) 122.3 94.2 105.0 84.9 86.2 75.5 67.6 65.7 55.2 55.2
72 (22.2) 207.4 101.3 186.8 92.0 164.6 81.7 140.6 71.2 114.6 60.4 67 (19.4) 173.3 106.7 153.1 96.4 131.2 85.8 107.5 75.1 81.9 64.3 62 (16.7) 142.1 110.8 122.0 100.2 100.0 89.3 78.2 78.2 65.2 65.2
72 (22.2) 182.6 88.6 165.5 132.0 146.7 95.2 126.3 64.2 104.0 104.0 67 (19.4) 152.4 92.7 135.4 83.7 116.9 74.6 96.6 65.2 74.6 55.7 62 (16.7) 124.9 95.2 107.8 86.0 89.3 76.6 70.2 67.0 56.7 56.7
72 (22.2) 221.4 107.7 200.6 98.2 177.7 87.8 152.8 76.8 125.7 65.6 67 (19.4) 185.4 113.8 164.7 103.1 142.1 92.1 117.4 80.9 90.5 69.5 62 (16.7) 152.4 118.1 131.6 107.2 109.0 95.8 86.2 83.9 70.9 70.9
72 (22.2) 253.9 124.2 229.9 113.3 203.8 101.4 175.1 89.0 143.9 76.3 67 (19.4) 213.4 132.1 189.5 120.1 163.4 107.7 135.0 95.0 104.0 82.0 62 (16.7) 175.8 138.6 151.9 126.1 125.8 113.1 99.4 99.4 83.3 83.3
72 (22.2) 221.4 107.7 200.6 163.3 177.7 117.8 152.8 79.1 125.7 125.7 67 (19.4) 185.4 113.8 164.7 103.1 142.1 92.1 117.4 80.9 90.5 69.5 62 (16.7) 152.4 118.1 131.6 107.2 109.0 95.8 86.2 83.9 70.9 70.9
72 (22.2) 263.7 129.4 238.7 117.9 211.6 105.6 181.9 92.8 149.4 79.6 67 (19.4) 221.7 137.8 197.0 125.4 169.9 112.6 140.3 99.4 108.1 85.9 62 (16.7) 182.9 144.9 158.0 132.1 130.8 118.5 104.0 104.0 87.2 87.2
72 (22.2) 298.3 147.4 270.2 134.4 239.6 120.8 205.9 106.6 169.0 91.9 67 (19.4) 251.7 158.5 223.7 144.8 193.0 130.6 159.4 115.9 122.9 100.7 62 (16.7) 208.3 168.6 180.1 154.3 149.1 138.5 120.4 120.4 101.5 101.5
72 (22.2) 360.1 174.8 326.2 260.8 289.1 187.9 248.7 126.7 204.7 204.7 67 (19.4) 300.7 183.1 267.0 165.3 230.4 147.2 190.2 128.6 146.8 109.9 62 (16.7) 246.5 188.2 212.7 170.0 176.0 151.4 138.3 132.3 111.9 111.9
72 (22.2) 435.7 212.1 394.7 193.6 349.4 172.9 300.3 151.3 246.8 129.2 67 (19.4) 365.2 224.3 324.1 203.3 279.5 181.6 230.8 159.5 177.6 136.9 62 (16.7) 300.2 233.1 259.1 211.5 214.3 189.0 169.6 165.5 139.7 139.7
72 (22.2) 499.1 244.5 451.7 222.9 400.1 199.4 343.7 175.1 282.2 150.0 67 (19.4) 419.5 260.2 372.5 236.6 321.1 212.2 265.0 187.0 203.9 161.3 62 (16.7) 345.9 273.1 298.6 248.6 247.0 222.8 195.7 195.7 164.0 164.0
72 (22.2) 443.7 215.8 406.1 329.5 363.8 240.8 317.1 164.0 265.2 265.2 67 (19.4) 374.1 229.7 335.9 210.2 293.5 189.7 246.5 168.3 194.4 146.0 62 (16.7) 309.8 240.3 271.0 219.9 227.9 198.4 182.4 175.5 149.2 149.2
72 (22.2) 523.5 257.1 479.7 236.8 430.7 214.8 375.8 191.3 314.5 166.4 67 (19.4) 443.7 276.5 399.2 254.6 349.3 231.1 293.7 206.4 232.0 180.5 62 (16.7) 369.1 293.6 323.5 270.3 272.6 245.2 220.6 217.2 184.8 184.8
10000 72 (22.2) 586.4 289.8 538.6 268.1 484.6 244.5 423.1 218.9 354.4 191.6 67 (19.4) 499.5 316.4 450.2 292.8 394.6 267.3 332.3 240.1 262.8 211.4 62 (16.7) 417.2 340.3 366.3 314.9 309.4 286.4 253.1 253.1 215.4 215.4
LEGEND
db — Dry---Bulb Temp (_F) Ewb — Entering Wet---Bulb Temp (_F) lwb — Leaving Wet---Bulb Temp (_F) SHC — Sensible Heat Capacity (1000 Btuh) TC — Total Capacity (1000 Btuh)
NOTES:
1. Ratings based on approximately 15_F superheat leaving coil.
2. Direct interpolation is permissible. Do not extrapolate.
3. Dashes indicate coil loading limits are exceeded.
4. Evaporator fan heat not deducted from ratings.
5. Formulas:
Leaving db = entering db ---sensible heat capacity (Btuh)
1.1 x cfm
Leaving wb = wet---bulb temperature corresponding to enthalpy of air leaving coil (hlwb) hlwb = hewb ---total capacity (Btuh)
4.5 x cfm where hlwb = enthalpy of air entering coil
6. SHC is based on 80_F db temperature of air entering evaporator coil.
R U Q
PERFORMANCE DATA (cont.)
HYDRONIC HEATING CAPACITIES
UNIT AIRFLOW
(Cfm)
1-ROW
STEAM*
2-ROW
HOT WATER COIL†
Cap. Ldb Cap. Ldb Water Flow (Gpm)
PD
40RUQ07
1,800 2,400 3,000
156.0 183.0 206.0
15.6 18.3 20.6
3.4 4.3 5.2
40RUQ08
2,250 3,000 3,750
174.0 206.0 238.0
17.4 20.6 23.8
4.0 5.2 6.5
40RUQ12
3,000 4,000 5,000
299.0 275.0 316.0
29.9 27.5 31.6
5.0 6.6 8.2
40RUQ16
4,500 6,000 7,500
412.0 471.0 529.0
41.2 47.1 52.9
4.5 5.5 6.6
40RUQ25
6,000 8,000 10,000
506.0 584.0 652.0
50.6 58.4 65.2
5.1 6.3 7.5
LEGEND:
Cap. --- Capacity (Btuh in thousands) Ldb --- Leaving Air Dry Bulb Temp (_F) PD --- Pressure Drop (ft water).
* Based on 5 psig steam, 60° F entering-air temperature. All steam coils are non-freeze type.
† Based on 200° F entering water, 20° F water temperature drop, 60° F entering-air temperature.
NOTES:
1. Maximum operating limits for heating coils: 20 psig at 260_F.
2. Leavingdb=ent db (_F) + Capacity (Btuh)
1.1 x cfm
3. See Heating Correction Factors table.
HEATING CORRECTION FACTORS
HOT WATER COIL
Water Temp Drop
_F (_C) Ent Water Temp
_F (_C) Entering-Air Temp_F (_C)
40 (4.4) 50 (10) 60 (15.6) 70 (21.1) 80 (26.7)
10 (---12.2)
140 (60) 0.72 0.64 0.57 0.49 0.41 160 (71) 0.89 0.81 0.74 0.66 0.58 180 (82) 1.06 0.98 0.90 0.83 0.75 200 (93) 1.22 1.15 1.07 1.00 0.92 220 (104) 1.39 1.32 1.24 1.17 1.09
20 (---6.7)
140 (60) 0.64 0.57 0.49 0.41 0.33 160 (71) 0.81 0.74 0.66 0.58 0.51 180 (82) 0.98 0.91 0.83 0.75 0.68 200 (93) 1.15 1.08 1.00 0.93 0.85 220 (104) 1.32 1.25 1.17 1.10 1.02
30 (---1.1)
140 (60) 0.56 0.49 0.41 0.33 0.24 160 (71) 0.74 0.66 0.58 0.51 0.43 180 (82) 0.91 0.83 0.76 0.68 0.60 200 (93) 1.08 1.00 0.93 0.85 0.78 220 (104) 1.25 1.18 1.10 1.03 0.95
STEAM COIL
Steam Pressure
(psig) Entering-Air Temp _F (_C)
40 (4.4) 50 (10) 60 (15.6) 70 (21.1) 80 (26.7) 0 1.06 0.98 0.91 0.85 0.78 2 1.09 1.02 0.95 0.89 0.82 5 1.13 1.06 1.00 0.93 0.87
NOTE: Multiply capacity given in the Hydronic Heating Capacities table by the correction factor for conditions at which unit is actually operating. Correct leaving-air temperature using formula in Note 2 of Hydronic Heating Capacities table.
R
FAN PERFORMANCE DATA — 40RUQ 0.0-1.2 in. wg ESP — 60 Hz
UNIT AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.0 0.2 0.4 0.6 0.8 1.0 1.2
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
40RUQ*07
1,800 419 0.21 471 0.26 564 0.37 649 0.49 727 0.63 797 0.77 862 0.92 2,100 471 0.31 519 0.37 602 0.49 679 0.62 751 0.77 819 0.92 882 1.09 2,400 524 0.44 568 0.51 645 0.64 715 0.79 781 0.94 844 1.11 905 1.28 2,700 578 0.61 619 0.69 690 0.84 755 0.99 816 1.15 875 1.33 932 1.51 3,000 633 0.81 671 0.90 738 1.07 799 1.24 856 1.41 910 1.60 963 1.79
40RUQ*08
2,250 290 0.10 510 0.39 594 0.51 669 0.65 739 0.79 806 0.95 870 1.12 2,600 349 0.19 561 0.55 640 0.70 709 0.84 773 1.00 834 1.16 893 1.34 3,000 579 0.70 621 0.79 695 0.96 759 1.12 818 1.30 874 1.47 928 1.66 3,400 646 0.99 683 1.09 752 1.29 813 1.48 869 1.67 920 1.86 970 2.06 3,750 705 1.31 739 1.42 804 1.63 862 1.85 915 2.05 964 2.26 1011 2.48
40RUQ*12
3,000 421 0.35 592 0.73 670 0.90 737 1.06 797 1.23 854 1.41 908 1.59 3,500 626 0.98 664 1.08 735 1.28 798 1.48 855 1.67 908 1.87 958 2.07 4,000 706 1.42 738 1.54 803 1.77{ 862 2.00{ 917 2.23 967 2.45 1014 2.67 4,500 786 1.99{ 815 2.12{ 873 2.39 929 2.65 980 2.90 1028 3.16 1073 3.41 5,000 867 2.70 893 2.84 946 3.14 997 3.43 1046 3.72 1092 4.00 1135 4.28
40RUQ*16
4,500 437 0.61 483 0.72 576 1.01 660 1.35 732 1.69 797 2.03 856 2.38 5,300 499 0.95 538 1.07 617 1.37 696 1.74 767 2.13 830 2.53 888 2.94 6,000 555 1.34 590 1.48 659 1.79 730 2.17 798 2.59 860 3.04 918 3.49 6,800 620 1.91 651 2.06 712 2.39 774 2.78 836 3.22 896 3.71 952 4.21 7,500 677 2.52 706 2.69 761 3.04 817 3.44 873 3.89 929 4.39 984 4.93
40RUQ*25
6,000 542 1.29 577 1.42 646 1.72 716 2.09 785 2.51 849 2.95 907 3.40 7,000 620 1.99 652 2.15 711 2.48 771 2.85 831 3.28 890 3.76 947 4.27 8,000 700 2.92 728 3.10 781 3.46 833 3.85 885 4.29 938 4.78 990 5.32 9,000 781 4.10 806 4.30 854 4.71 900 5.13 946 5.58 993 6.08 1039 6.62 10,000 862 5.56 885 5.79 929 6.24 971 6.70 1012 7.18 1054 7.69 1096 8.24
LEGEND
Bhp — Brake Horsepower Input to Fan ESP — External Static Pressure Bold indicates field---supplied drive is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than the standard motor and standard drive combination is required.
Refer to fan motor and drive tables to complete selection.
{ — With two speed fan, these operating points require different motor and drive combination.
R
FAN PERFORMANCE DATA — 40RUQ 1.4-2.4 in. wg ESP — 60 Hz
UNIT AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
1.4 1.6 1.8 2.0 2.2 2.4
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
40RUQ*07
1,800 921 1.07 975 1.23 1026 1.39 1074 1.55 1120 1.72 1164 1.90 2,100 942 1.26 997 1.43 1048 1.61 1097 1.79 1143 1.97 1186 2.16 2,400 963 1.47 1017 1.66 1069 1.85 1118 2.05 1164 2.25 — — 2,700 987 1.71 1039 1.91 1090 2.12 1138 2.33 1185 2.55 — — 3,000 1015 1.99 1065 2.20 1113 2.42 1161 2.65 — — — —
40RUQ*08
2,250 930 1.29 986 1.47 1039 1.65 1089 1.84 1136 2.03 1181 2.22 2,600 950 1.53 1005 1.72 1057 1.92 1107 2.13 1154 2.33 — — 3,000 980 1.86 1031 2.06 1081 2.27 1129 2.49 1175 2.72 — — 3,400 1018 2.26 1065 2.48 1111 2.70 1156 2.93 — — — — 3,750 1057 2.69 1101 2.92 1144 3.15 1186 3.39 — — — —
40RUQ*12
3,000 961 1.78 1012 1.98 1062 2.19 1111 2.41 1158 2.64 — — 3,500 1005 2.27 1052 2.49 1098 2.71 1142 2.94 1186 3.18 — — 4,000 1058 2.90 1101 3.13 1143 3.36 1184 3.60 — — — — 4,500 1116 3.66 1157 3.91 1196 4.16 — — — — — — 5,000 1176 4.56 — — — — — — — — — —
40RUQ*16
4,500 912 2.75 967 3.12 1019 3.52 1070 3.92 1120 4.35 1168 4.79 5,300 942 3.34 992 3.76 1041 4.18 1088 4.61 1134 5.06 1179 5.52 6,000 971 3.95 1020 4.40 1067 4.86 1112 5.33 1156 5.81 1198 6.29 6,800 1005 4.72 1054 5.23 1101 5.75 1145 6.27 1187 6.79 — — 7,500 1036 5.48 1084 6.04 1131 6.61 1174 7.17 — — — —
40RUQ*25
6,000 961 3.86 1011 4.31 1058 4.77 1104 5.24 1147 5.71 — — 7,000 1000 4.79 1050 5.32 1097 5.85 1142 6.38 1184 6.91 — — 8,000 1041 5.88 1090 6.47 1137 7.07 1181 7.67 — — — — 9,000 1086 7.21 1133 7.82 1178 8.47 — — — — — — 10,000 1138 8.83 1180 9.46 — — — — — — — —
LEGEND
Bhp — Brake Horsepower Input to Fan ESP — External Static Pressure Bold indicates field---supplied drive is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than the standard motor and standard drive combination is required. Refer to fan motor and drive tables to complete selection.
DUCT SOUND POWER LEVELS (Lw)
MODEL SIZE CFM dB(A) OCTAVE BAND CENTER FREQUENCY (Hz)
63 125 250 500 1000 2000 4000
40RUQ
07 2,400 86.3 93.2 89.2 85.2 84.2 80.2 78.2 74.2 08 3,000 88.3 95.3 91.3 87.3 86.3 82.3 80.3 76.3 12 4,000 92.0 99.0 95.0 91.0 90.0 86.0 84.0 80.0 16 6,000 92.9 99.2 95.2 91.2 92.2 86.2 84.2 80.2 25 8,000 96.4 102.6 98.6 94.6 95.6 89.2 87.6 839.6
LEGEND:
ASHRAE --- American Society of Heating, Refrigerating and Air Conditioning, Inc.
HVAC --- Heating, Ventilation and Air Conditioning
NOTES:
1. The above estimated sound power levels are based upon the ASHRAE calculation approach from the ASHRAE HVAC Systems and Applications handbook.
2. Since this data is calculated, these sound power levels may be different than the actual sound power levels.
3. The acoustic center of the unit is located at the geometric center of the unit.
R
FACTORY-SUPPLIED FILTER PRESSURE DROP
SIZE UNIT AIRFLOW
(Cfm)
PRESSURE DROP
(in. wg)
07 40RUQ
1,800 2,400 3,000
0.05 0.08 0.11
08 40RUQ
2,250 3,000 3,750
0.07 0.11 0.15
12 40RUQ
3,000 4,000 5,000
0.11 0.17 0.23
16 40RUQ
4,500 6,000 7,500
0.08 0.12 0.17
25 40RUQ
6,000 8,000 10,000
0.12 0.19 0.26
ACCESSORY PLENUM AIR THROW DATA (Ft)
UNIT AIRFLOW
(Cfm)
VANE DEFLECTION
Straight 211/2 45
40RUQ07 2,400 39 33 24
40RUQ08 3,000 45 38 28
40RUQ12 4,000 55 46 33
40RUQ16 6,000 50 43 31
40RUQ25 8,000 60 51 37
NOTE: Throw distances shown are for 75 fpm terminal velocity. Use the following multipliers to determine throw values for other terminal velocities.
TERMINAL VELOCITY
(Fpm) THROW FACTOR
50 X 1.50 100 X 0.75 150 X 0.50
ACCESSORY PRESSURE DROP (in. wg)
UNIT AIRFLOW
(Cfm)
DISCHARGE
PLENUM
RETURN AIR
GRILLE Hot Water Steam Electric ECONOMIZER
40RUQ07
1,800 2,400 3,000
0.06 0.10 0.14
0.01 0.01 0.02
0.10 0.16 0.23
0.10 0.16 0.23
0.04 0.06 0.10
0.05 0.07 0.09
40RUQ08
2,250 3,000 3,750
0.09 0.14 0.21
0.01 0.02 0.03
0.15 0.23 0.35
0.15 0.23 0.35
0.06 0.10 0.15
0.06 0.09 0.15
40RUQ12
3,000 4,000 5,000
0.14 0.22 0.32
0.02 0.04 0.06
0.23 0.37 0.53
0.23 0.37 0.53
0.10 0.17 0.26
0.09 0.17 0.28
40RUQ16
4,500 6,000 7,500
0.10 0.16 0.23
0.01 0.02 0.03
0.15 0.23 0.33
0.15 0.23 0.33
0.06 0.10 0.15
0.06 0.09 0.15
40RUQ25
6,000 8,000 10,000
0.16 0.26 0.37
0.02 0.04 0.06
0.23 0.37 0.53
0.23 0.37 0.53
0.10 0.17 0.26
0.09 0.17 0.28
R
ELECTRICAL DATA
Table 1 – Electrical Data, Standard Motors with Factory--Installed Single Speed Fan Option
UNIT V---PH---Hz{ VOLTAGE
LIMITS
FAN MOTOR POWER SUPPLY
Hp (kW) FLA Minimum Circuit Amps
MAX FUSE or
HACR BRKR
40RUQ*07
208/230---1---60 187---253 1.3 (0.97) 6.60 9.00 15 208/230---3---60 187---253 2.4 (1.79) 5.2 7.0 15 460---3---60 414---506 2.4 (1.79) 2.6 4.0 15 575---3---60 518---632 1.0 (0.75) 1.40 2.0 15
40RUQ*08
208/230---1---60 187---253 2.4 (1.79) 11.00 13.80 20 208/230---3---60 187---253 2.4 (1.79) 5.2 7.0 15 460---3---60 414---506 2.4 (1.79) 2.6 4.0 15 575---3---60 518---632 2.0 (1.49) 2.40 3.0 15
40RUQ*12
208/230---3---60 187---253 2.4 (1.79) 5.2 7.0 15 460---3---60 414---506 2.4 (1.79) 2.6 4.0 15 575---3---60 518---632 2.0 (1.49) 2.40 3.0 15
40RUQ*16
208/230---3---60 187---253 3.7 (2.76) 10.2 13.0 20 460---3---60 414---506 3.7 (2.76) 4.8 6.0 15 575---3---60 518---632 3.0 (2.24) 3.80 5.0 15
40RUQ*25
208/230---3---60 187---253 5.0 (3.73) 18.0 23.0 40 460---3---60 414---506 5.0 (3.73) 9.1 12.0 20
575---3---60 518---632 5.0 (3.73) 8.0 10.0 15
See: “Legend and Notes for Tables 1 --- 4” on page 22.
Table 2 – Electrical Data, Alternate Motors with Factory--Installed Single Speed Fan Option
UNIT V---PH---Hz{ VOLTAGE
LIMITS
FAN MOTOR POWER SUPPLY
Hp (kW) FLA Minimum Circuit Amps
MAX FUSE or
HACR BRKR
40RUQ*07
208/230---1---60 187---253 2.4 (1.79) 11.00 13.80 20 208/230---3---60 187---253 2.9 (2.16) 7.5 10.0 15 460---36---0 414---506 2.9 (2.16) 3.4 5.0 15 575---3---60 518---632 2.0 (1.49) 2.40 3.0 15
40RUQ*08
208/230---1---60 187---253 2.4 (1.79) 11.00 13.80 15 208/230---3---60 187---253 2.9 (2.16) 7.5 10.0 15 460---3---60 414---506 2.9 (2.16) 3.4 5.0 15 575---3---60 518---632 3.0 (2.24) 3.80 5.0 15
40RUQ*12
208/230---3---60 187---253 3.7 (2.76) 10.2 13.0 20 460---3---60 414---506 3.7 (2.76) 4.8 6.0 15 575---3---60 518---632 3.0 (2.24) 3.80 5.0 15
40RUQ*16
208/230---3---60 187---253 5.0 (3.73) 18.0 23.0 40 460---3---60 414---506 5.0 (3.73) 9.1 12.0 20 575---3---60 518---632 5.0 (3.73) 8.0 10.0 15
40RUQ*25
208/230---3---60 187---253 7.5 (5.59) 23.5 30.0 50 460---3---60 414---506 7.5 (5.59) 15.0 19.0 30
575---3---60 518---632 7.5 (5.59) 10.0 13.0 20
See: “Legend and Notes for Tables 1 --- 4” on page 22.
R
ELECTRICAL DATA (cont.)
Table 3 – Electrical Data, Standard Motors with Factory--Installed 2--Speed Fan Option
UNIT V---PH---Hz{ VOLTAGE
LIMITS
FAN MOTOR POWER SUPPLY
Hp (kW) FLA Minimum Circuit Amps
MAX FUSE or
HACR BRKR
40RUQ*07
208/230---3---60 187---253 2.4 (1.79) 7.1 9.0 15 460---3---60 414---506 2.4 (1.79) 3.8 5.0 15 575---3---60 518---632 2.4 (1.79) 3.5 5.0 15
40RUQ*08
208/230---3---60 187---253 2.4 (1.79) 7.1 9.0 15 460---3---60 414---506 2.4 (1.79) 3.8 5.0 15 575---3---60 518---632 2.4 (1.79) 3.5 5.0 15
40RUQ*12
Units Produced On or Prior to 02/28/2016
208/230---3---60 187---253 2.4 (1.79) 7.1 9.0 15
460---3---60 414---506 2.4 (1.79) 3.8 5.0 15
575---3---60 518---632 2.4 (1.79) 3.5 5.0 15
40RUQ*12
Units Produced On or After 02/29/2016
208/230---3---60 187---253 1.7 (1.27) 5.8 8.0 15
460---3---60 414---506 1.7 (1.27) 2.9 4.0 15
575---3---60 518---632 1.7 (1.27) 2.8 4.0 15
40RUQ*16
208/230---3---60 187---253 3.7 (2.76) 10.8 14.0 20 460---3---60 414---506 3.7 (2.76) 4.9 7.0 15 575---3---60 518---632 3.7 (2.76) 4.5 6.0 15
40RUQ*25
208/230---3---60 187---253 5.0 (3.73) 18.0 23.0 40 460---3---60 414---506 5.0 (3.73) 9.1 12.0 20
575---3---60 518---632 5.0 (3.73) 8.0 10.0 15
See: “Legend and Notes for Tables 1 --- 4” on page 22.
Table 4 – Electrical Data, Alternate Motors with Factory--Installed 2--Speed Fan Option
UNIT V---PH---Hz{ VOLTAGE
LIMITS
FAN MOTOR POWER SUPPLY
Hp (kW) FLA Minimum Circuit Amps
MAX FUSE or
HACR BRKR
40RUQ*07
208/230---3---60 187---253 3.7 (2.76) 10.8 14.0 20 460---36---0 414---506 3.7 (2.76) 4.9 7.0 15 575---3---60 518---632 3.7 (2.76) 4.5 6.0 15
40RUQ*08
208/230---3---60 187---253 3.7 (2.76) 10.8 14.0 20 460---3---60 414---506 3.7 (2.76) 4.9 7.0 15 575---3---60 518---632 3.7 (2.76) 4.5 6.0 15
40RUQ*12
Units Produced On or Prior to 02/28/2016
208/230---3---60 187---253 3.7 (2.76) 10.8 14.0 20
460---3---60 414---506 3.7 (2.76) 4.9 7.0 15
575---3---60 518---632 3.7 (2.76) 4.5 6.0 15
40RUQ*12
Units Produced On or After 02/29/2016
208/230---3---60 187---253 3.7 (2.76) 10.6 14.0 20
460---3---60 414---506 3.7 (2.76) 5.3 7.0 15
575---3---60 518---632 3.7 (2.76) 4.5 6.0 15
40RUQ*16
208/230---3---60 187---253 5.0 (3.73) 18.0 23.0 40 460---3---60 414---506 5.0 (3.73) 9.1 12.0 20 575---3---60 518---632 5.0 (3.73) 8.0 10.0 15
40RUQ*25
208/230---3---60 187---253 7.5 (5.59) 23.5 30.0 50 460---3---60 414---506 7.5 (5.59) 15.0 19.0 30
575---3---60 518---632 7.5 (5.59) 10.0 13.0 20
See: “Legend and Notes for Tables 1 --- 4” on page 22.
R
Legend and Notes for Tables 1 --- 41
LEGEND:
FLA --- Full Load Amps MOCP --- MAX FUSE or HACR BRKR { Motors are designed for satisfactory operation within 10% of normal voltage shown. Voltages should not exceed the limits shown in the Voltage Limits column.
NOTES:
4. Minimum circuit amps (MCA) and fuse or HACR breaker values are calculated in accordance with The NEC. Article 440.
5. Motor FLA values are established in accordance with Under-writers’ Laboratories (UL). Standard 1995.
6. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the formula in the example (see column to the right) to determine the percentage of volt-age imbalance.
7. Installation with Accessory Electric Heaters Size the Field Power Wiring between the heater TB1 and the 40RUQ indoor fan motor per NEC Article 430---28 (1) or (2) (depends on length of conduit between heater enclosure and 40RUQ power entry location). Install wires in field--- installed conduit.
Example: Supply voltage is 230-3-60
% Voltage Imbalance = 100 x max voltage deviation from average voltage average voltage
AB = 393 v BC = 403 v AC = 396 v
Average Voltage = (393 + 403 + 396)
3 3
= 397
Determine maximum deviation from average voltage.
(AB) 397 – 393 = 4 v (BC) 403 – 397 = 6 v (AC) 397 – 396 = 1 v Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.5%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
R
Table 5 – Electric Heater Data -- Single Speed Motor
HEATER
PART NO.
CAELHEAT
SIZE V-PH-Hz
FAN MOTOR
ELECTRIC HEATER(S)
MCA* MOCP*Nom.
Cap.
(kW)
Actual Capacity (kW)
FLA
Hp kW FLA Stage
Stage 2 Total
001A00
40RUQ
07---12
208---3---60
1.3† 0.97 6.6 5.0 3.8 --- 3.76 10.4 21.3 25 2.4† 1.79 11.0 5.0 3.8 --- 3.76 10.4 26.8 35
2.4 1.79 5.2 5.0 3.8 --- 3.76 10.4 19.5 20
2.9 2.16 7.5 5.0 3.8 --- 3.76 10.4 22.4 25
3.7 2.76 10.2 5.0 3.8 --- 3.76 10.4 25.8 30
240---3---60
1.3† 0.97 6.6 5.0 5.0 --- 5.0 12.0 23.3 25 2.4† 1.79 11.0 5.0 5.0 --- 5.0 12.0 28.8 35
2.4 1.79 5.2 5.0 5.0 --- 5.0 12.0 21.5 25
2.9 2.16 7.5 5.0 5.0 --- 5.0 12.0 24.4 25
3.7 2.76 10.2 5.0 5.0 --- 5.0 12.0 27.8 30
002A00 480---3---60
2.4 1.79 2.6 5.0 5.0 --- 5.0 6.0 10.8 15
2.9 2.16 3.4 5.0 5.0 --- 5.0 6.0 11.8 15
3.7 2.76 4.8 5.0 5.0 --- 5.0 6.0 13.5 15
003A00 575---3---60
1.0 0.75 1.4 5.0 5.0 --- 5.0 5.0 8.0 15
2.0 1.49 2.4 5.0 5.0 --- 5.0 5.0 9.3 15
3.0 2.24 3.8 5.0 5.0 --- 5.0 5.0 11.0 15
004A00
208---3---60
1.3† 0.97 6.6 10.0 7.5 --- 7.51 20.8 34.3 35 2.4† 1.79 11.0 10.0 7.5 --- 7.51 20.8 39.8 40
2.4 1.79 5.2 10.0 7.5 --- 7.51 20.8 32.6 35
2.9 2.16 7.5 10.0 7.5 --- 7.51 20.8 35.4 40
3.7 2.76 10.2 10.0 7.5 --- 7.51 20.8 38.8 40
240---3---60
1.3† 0.97 6.6 10.0 10.0 --- 10.0 24.1 38.3 40 2.4† 1.79 11.0 10.0 10.0 --- 10.0 24.1 43.8 50
2.4 1.79 5.2 10.0 10.0 --- 10.0 24.1 36.6 40
2.9 2.16 7.5 10.0 10.0 --- 10.0 24.1 39.4 40
3.7 2.76 10.2 10.0 10.0 --- 10.0 24.1 42.8 50
005A00 480---3---60
2.4 1.79 2.6 10.0 10.0 --- 10.0 12.0 18.3 20
2.9 2.16 3.4 10.0 10.0 --- 10.0 12.0 19.3 20
3.7 2.76 4.8 10.0 10.0 --- 10.0 12.0 21.0 25
006A00 575---3---60
1.0 0.75 1.4 10.0 10.0 --- 10.0 10.0 14.3 15
2.0 1.49 2.4 10.0 10.0 --- 10.0 10.0 15.6 20
3.0 2.24 3.8 10.0 10.0 --- 10.0 10.0 17.3 20
007A00
208---3---60
1.3† 0.97 6.6 15.0 11.3 --- 11.27 31.3 47.4 50 2.4† 1.79 11.0 15.0 11.3 --- 11.27 31.3 52.9 60
2.4 1.79 5.2 15.0 11.3 --- 11.27 31.3 45.6 50
2.9 2.16 7.5 15.0 11.3 --- 11.27 31.3 48.5 50
3.7 2.76 10.2 15.0 11.3 --- 11.27 31.3 51.9 60
240---3---60
1.3† 0.97 6.6 15.0 15.0 --- 15.0 36.1 53.4 60 2.4† 1.79 11.0 15.0 15.0 --- 15.0 36.1 58.9 60
2.4 1.79 5.2 15.0 15.0 --- 15.0 36.1 51.6 60
2.9 2.16 7.5 15.0 15.0 --- 15.0 36.1 54.5 60
3.7 2.76 10.2 15.0 15.0 --- 15.0 36.1 57.9 60
See: “Legend and Notes for Tables 5 and 6” on page 29.
R
Table 5 -- Electric Heater Data -- Single Speed Motor (cont)
HEATER
PART NO.
CAELHEAT
SIZE V-PH-Hz
FAN MOTOR
ELECTRIC HEATER(S)
MCA* MOCP*Nom.
Cap.
(kW)
Actual Capacity (kW)
FLA
Hp kW FLA Stage
Stage 2 Total
008A00
40RUQ
07---12
480---3---60
2.4 1.79 2.6 15.0 15.0 --- 15.0 18.0 25.8 30
2.9 2.16 3.4 15.0 15.0 --- 15.0 18.0 26.8 30
3.7 2.76 4.8 15.0 15.0 --- 15.0 18.0 28.6 30
009A00 575---3---60
1.0 0.75 1.4 15.0 15.0 --- 15.0 15.1 20.6 25
2.0 1.49 2.4 15.0 15.0 --- 15.0 15.1 21.8 25
3.0 2.24 3.8 15.0 15.0 --- 15.0 15.1 23.6 25
010A00
208---3---60
1.3† 0.97 6.6 25.0 11.3 7.5 18.8 52.1 73.4 80 2.4† 1.79 11.0 25.0 11.3 7.5 18.8 52.1 78.9 80
2.4 1.79 5.2 25.0 11.3 7.5 18.8 52.1 71.7 80
2.9 2.16 7.5 25.0 11.3 7.5 18.8 52.1 74.5 80
3.7 2.76 10.2 25.0 11.3 7.5 18.8 52.1 77.9 80
240---3---60
1.3† 0.97 6.6 25.0 15.0 10.0 25.0 60.1 83.4 90 2.4† 1.79 11.0 25.0 15.0 10.0 25.0 60.1 88.9 90
2.4 1.79 5.2 25.0 15.0 10.0 25.0 60.1 81.7 90
2.9 2.16 7.5 25.0 15.0 10.0 25.0 60.1 84.6 90
3.7 2.76 10.2 25.0 15.0 10.0 25.0 60.1 87.9 90
011A00 480---3---60
2.4 1.79 2.6 25.0 15.0 10.0 25.0 30.1 40.8 50
2.9 2.16 3.4 25.0 15.0 10.0 25.0 30.1 41.8 50
3.7 2.76 4.8 25.0 15.0 10.0 25.0 30.1 43.6 50
012A00 575---3---60
1.0 0.75 1.4 25.0 15.0 10.0 25.0 25.1 33.1 35
2.0 1.49 2.4 25.0 15.0 10.0 25.0 25.1 34.4 35
3.0 2.24 3.8 25.0 15.0 10.0 25.0 25.1 36.1 40
013A00
40RUQ
08, 12
208---3---60
2.4† 1.79 11.0 35.0 15.0 11.3 26.3 73.0 105.0 110
2.4 1.79 5.2 35.0 15.0 11.3 26.3 73.0 97.7 100
2.9 2.16 7.5 35.0 15.0 11.3 26.3 73.0 100.6 110
3.7 2.76 10.2 35.0 15.0 11.3 26.3 73.0 104.0 110
240---3---60
2.4† 1.79 11.0 35.0 20.0 15.0 35.0 84.2 119.0 125
2.4 1.79 5.2 35.0 20.0 15.0 35.0 84.2 111.7 125
2.9 2.16 7.5 35.0 20.0 15.0 35.0 84.2 114.6 125
3.7 2.76 10.2 35.0 20.0 15.0 35.0 84.2 118.0 125
014A00 480---3---60
2.4 1.79 2.6 35.0 20.0 15.0 35.0 42.1 55.9 60
2.9 2.16 3.4 35.0 20.0 15.0 35.0 42.1 56.9 60
3.7 2.76 4.8 35.0 20.0 15.0 35.0 42.1 58.6 60
015A00 575---3---60
2.0 1.49 2.4 35.0 20.0 15.0 35.0 35.1 46.9 50
3.0 2.24 3.8 35.0 20.0 15.0 35.0 35.1 48.7 50
See: “Legend and Notes for Tables 5 and 6” on page 29.
R
Table 5 -- Electric Heater Data -- Single Speed Motor (cont)
HEATER
PART NO.
CAELHEAT
SIZE V-PH-Hz
FAN MOTOR
ELECTRIC HEATER(S)
MCA* MOCP*Nom.
Cap.
(kW)
Actual Capacity (kW)
FLA
Hp kW FLA Stage
Stage 2 Total
016A00
40RUQ
16, 25
208---3---60
2.9 2.16 7.5 10.0 7.5 --- 7.5 20.8 35.4 40
3.7 2.76 10.2 10.0 7.5 --- 7.5 20.8 38.8 40
5.0 3.73 18.0 10.0 7.5 --- 7.5 20.8 48.6 60
7.5 5.59 23.5 10.0 7.5 --- 7.5 20.8 55.4 70
240---3---60
2.9 2.16 7.5 10.0 10.0 --- 10.0 24.1 39.4 40
3.7 2.76 10.2 10.0 10.0 --- 10.0 24.1 42.8 50
5.0 3.73 18.0 10.0 10.0 --- 10.0 24.1 52.6 60
7.5 5.59 23.5 10.0 10.0 --- 10.0 24.1 59.4 70
017A00 480---3---60
2.9 2.16 3.4 10.0 10.0 --- 10.0 12.0 19.3 20
3.7 2.76 4.8 10.0 10.0 --- 10.0 12.0 21.0 25
5.0 3.73 9.1 10.0 10.0 --- 10.0 12.0 26.4 30
7.5 5.59 15.0 10.0 10.0 --- 10.0 12.0 33.8 40
018A00 575---3---60
3.0 2.24 3.8 10.0 10.0 --- 10.0 10.0 17.3 20
5.0 3.73 8.0 10.0 10.0 --- 10.0 10.0 22.6 25
7.5 5.59 10.0 10.0 10.0 --- 10.0 10.0 25.1 30
019A00
208---3---60
2.9 2.16 7.5 20.0 14.9 --- 15.0 41.7 61.5 70
3.7 2.76 10.2 20.0 14.9 --- 15.0 41.7 64.9 70
5.0 3.73 18.0 20.0 14.9 --- 15.0 41.7 74.6 80
7.5 5.59 23.5 20.0 14.9 --- 15.0 41.7 81.5 90
240---3---60
2.9 2.16 7.5 20.0 19.9 --- 20.0 48.1 69.5 70
3.7 2.76 10.2 20.0 19.9 --- 20.0 48.1 72.9 80
5.0 3.73 18.0 20.0 19.9 --- 20.0 48.1 82.6 90
7.5 5.59 23.5 20.0 19.9 --- 20.0 48.1 89.5 100
020A00 480---3---60
2.9 2.16 3.4 20.0 20.0 --- 20.0 24.1 34.3 35
3.7 2.76 4.8 20.0 20.0 --- 20.0 24.1 36.1 40
5.0 3.73 9.1 20.0 20.0 --- 20.0 24.1 41.4 50
7.5 5.59 15.0 20.0 20.0 --- 20.0 24.1 48.8 50
021A00 575---3---60
3.0 2.24 3.8 20.0 20.0 --- 20.0 20.1 29.9 30
5.0 3.73 8.0 20.0 20.0 --- 20.0 20.1 35.1 40
7.5 5.59 10.0 20.0 20.0 --- 20.0 20.1 37.6 40
022A00
208---3---60
2.9 2.16 7.5 30.0 15.0 7.5 22.5 62.5 87.5 90
3.7 2.76 10.2 30.0 15.0 7.5 22.5 62.5 90.9 100
5.0 3.73 18.0 30.0 15.0 7.5 22.5 62.5 100.7 110
7.5 5.59 23.5 30.0 15.0 7.5 22.5 62.5 107.5 110
240---3---60
2.9 2.16 7.5 30.0 20.0 10.0 30.0 72.2 99.6 100
3.7 2.76 10.2 30.0 20.0 10.0 30.0 72.2 103.0 110
5.0 3.73 18.0 30.0 20.0 10.0 30.0 72.2 112.7 125
7.5 5.59 23.5 30.0 20.0 10.0 30.0 72.2 119.6 125
023A00 480---3---60
2.9 2.16 3.4 30.0 20.0 10.0 30.0 36.1 49.4 50
3.7 2.76 4.8 30.0 20.0 10.0 30.0 36.1 51.1 60
5.0 3.73 9.1 30.0 20.0 10.0 30.0 36.1 56.5 60
7.5 5.59 15.0 30.0 20.0 10.0 30.0 36.1 63.9 70
024A00 575---3---60
3.0 2.24 3.8 30.0 20.0 10.0 30.0 30.1 42.4 50
5.0 3.73 8.0 30.0 20.0 10.0 30.0 30.1 47.7 50
7.5 5.59 10.0 30.0 20.0 10.0 30.0 30.1 50.2 60
025A00
208---3---60
3.7 2.76 10.2 50.0 22.6 15.0 37.6 104.3 143.1 150
5.0 3.73 18.0 50.0 22.6 15.0 37.6 104.3 152.8 175
7.5 5.59 23.5 50.0 22.6 15.0 37.6 104.3 159.7 175
240---3---60
3.7 2.76 10.2 50.0 30.0 20.0 50.0 120.3 163.1 175
5.0 3.73 18.0 50.0 30.0 20.0 50.0 120.3 172.9 175
7.5 5.59 23.5 50.0 30.0 20.0 50.0 120.3 179.7 200
026A00 480---3---60
3.7 2.76 4.8 50.0 30.0 20.0 50.0 60.1 81.2 90
5.0 3.73 9.1 50.0 30.0 20.0 50.0 60.1 86.6 90
7.5 5.59 15.0 50.0 30.0 20.0 50.0 60.1 93.9 100
027A00 575---3---60
3.0 2.24 3.8 50.0 30.0 20.0 50.0 50.2 67.5 70
5.0 3.73 8.0 50.0 30.0 20.0 50.0 50.2 72.8 80
7.5 5.59 10.0 50.0 30.0 20.0 50.0 50.2 75.3 80
See: “Legend and Notes for Tables 5 and 6” on page 29.
R
Table 6 – Electric Heater Data -- 2--Speed Motor
HEATER-
PART NO.-
CAELHEAT
SIZE V---Ph---Hz
FAN MOTOR
ELECTRIC HEATER(S)
MCA* MOCP*Nom.
Cap.
(kW)
Actual Capacity
FLA
HP kW FLA Stage 1 Stage 2 Total
001A00
40RUQ
07---12
208---3---60
1.7 1.27 5.8 5.0 3.8 --- 3.8 10.4 20.3 25
2.4 1.79 7.1 5.0 3.8 --- 3.8 10.4 21.9 25
3.7 2.76 10.8 5.0 3.8 --- 3.8 10.4 26.5 30 3.7** 2.76 10.6 5.0 3.8 --- 3.8 10.4 26.3 30
240---3---60
1.7 1.27 5.6 5.0 5.0 --- 5.0 12.0 22.0 25
2.4 1.79 7.1 5.0 5.0 --- 5.0 12.0 23.9 25
3.7 2.76 10.8 5.0 5.0 --- 5.0 12.0 28.5 35 3.7** 2.76 10.6 5.0 5.0 --- 5.0 12.0 28.3 35
002A00 480---3---60
1.7 1.27 2.9 5.0 5.0 --- 5.0 6.0 11.1 15
2.4 1.79 3.8 5.0 5.0 --- 5.0 6.0 12.3 15
3.7 2.76 4.9 5.0 5.0 --- 5.0 6.0 13.6 15 3.7** 2.76 5.3 5.0 5.0 --- 5.0 6.0 14.1 15
003A00 575---3---60
1.7 1.27 2.8 5.0 5.0 --- 5.0 5.0 9.8 15
2.4 1.79 3.5 5.0 5.0 --- 5.0 5.0 10.7 15
3.7 2.76 4.5 5.0 5.0 --- 5.0 5.0 11.9 15
004A00
208---3---60
1.7 1.27 5.8 10.0 7.5 --- 7.5 20.8 33.3 35
2.4 1.79 7.1 10.0 7.5 --- 7.5 20.8 34.9 35
3.7 2.76 10.8 10.0 7.5 --- 7.5 20.8 39.6 40 3.7** 2.76 10.6 10.0 7.5 --- 7.5 20.8 39.3 40
240---3---60
1.7 1.27 5.6 10.0 10.0 --- 10.0 24.1 37.1 40
2.4 1.79 7.1 10.0 10.0 --- 10.0 24.1 38.9 40
3.7 2.76 10.8 10.0 10.0 --- 10.0 24.1 43.6 50 3.7** 2.76 10.6 10.0 10.0 --- 10.0 24.1 43.3 50
005A00 480---3---60
1.7 1.27 2.9 10.0 10.0 --- 10.0 12.0 18.7 20
2.4 1.79 3.8 10.0 10.0 --- 10.0 12.0 19.8 20
3.7 2.76 4.9 10.0 10.0 --- 10.0 12.0 21.2 25 3.7** 2.76 5.3 10.0 10.0 --- 10.0 12.0 21.7 25
006A00 575---3---60
1.7 1.27 2.8 10.0 10.0 --- 10.0 10.0 16.1 20
2.4 1.79 3.5 10.0 10.0 --- 10.0 10.0 16.9 20
3.7 2.76 4.5 10.0 10.0 --- 10.0 10.0 18.2 20
007A00
208---3---60
1.7 1.27 5.8 15.0 11.3 --- 11.3 31.3 46.4 50
2.4 1.79 7.1 15.0 11.3 --- 11.3 31.3 48.0 50
3.7 2.76 10.8 15.0 11.3 --- 11.3 31.3 52.6 60 3.7** 2.76 10.6 15.0 11.3 --- 11.3 31.3 52.4 60
240---3---60
1.7 1.27 5.6 15.0 15.0 --- 15.0 36.1 52.1 60
2.4 1.79 7.1 15.0 15.0 --- 15.0 36.1 54.0 60
3.7 2.76 10.8 15.0 15.0 --- 15.0 36.1 58.6 60 3.7** 2.76 10.6 15.0 15.0 --- 15.0 36.1 58.4 60
008A00 480---3---60
1.7 1.27 2.9 15.0 15.0 --- 15.0 18.0 26.2 30
2.4 1.79 3.8 15.0 15.0 --- 15.0 18.0 27.3 30
3.7 2.76 4.9 15.0 15.0 --- 15.0 18.0 28.7 30 3.7** 2.76 5.3 15.0 15.0 --- 15.0 18.0 29.2 30
009A00 575---3---60
1.7 1.27 2.8 15.0 15.0 --- 15.0 15.1 22.3 25
2.4 1.79 3.5 15.0 15.0 --- 15.0 15.1 23.2 25
3.7 2.76 4.5 15.0 15.0 --- 15.0 15.1 24.5 25
010A00
208---3---60
1.7 1.27 5.8 25.0 11.3 7.5 18.8 52.1 72.4 80
2.4 1.79 7.1 25.0 11.3 7.5 18.8 52.1 74.0 80
3.7 2.76 10.8 25.0 11.3 7.5 18.8 52.1 78.7 80 3.7** 2.76 10.6 25.0 11.3 7.5 18.8 52.1 78.4 80
240---3---60
1.7 1.27 5.6 25.0 15.0 10.0 25.0 60.1 82.2 90
2.4 1.79 7.1 25.0 15.0 10.0 25.0 60.1 84.1 90
3.7 2.76 10.8 25.0 15.0 10.0 25.0 60.1 88.7 90 3.7** 2.76 10.6 25.0 15.0 10.0 25.0 60.1 88.4 90
See: “Legend and Notes for Tables 5 and 6” on page 29.
R
Table 6 -- Electric Heater Data -- 2--Speed Motor (cont)
HEATER-
PART NO.-
CAELHEAT
SIZE V---Ph---Hz
FAN MOTOR
ELECTRIC HEATER(S)
MCA* MOCP*Nom.
Cap.
(kW)
Actual Capacity
FLA
HP kW FLA Stage 1 Stage 2 Total
011A00
40RUQ
07---12
480---3---60
1.7 1.27 2.9 25.0 15.0 10.0 25.0 30.1 41.2 50
2.4 1.79 3.8 25.0 15.0 10.0 25.0 30.1 42.3 50
3.7 2.76 4.9 25.0 15.0 10.0 25.0 30.1 43.7 50 3.7** 2.76 5.3 25.0 15.0 10.0 25.0 30.1 44.2 50
012A00 575---3---60
1.7 1.27 2.8 25.0 15.0 10.0 25.0 25.1 34.9 35
2.4 1.79 3.5 25.0 15.0 10.0 25.0 25.1 35.8 40
3.7 2.76 4.5 25.0 15.0 10.0 25.0 25.1 37.0 40
013A00
208---3---60
1.7 1.27 5.8 35.0 15.0 11.3 26.3 73.0 98.5 100
2.4 1.79 7.1 35.0 15.0 11.3 26.3 73.0 100.1 110
3.7 2.76 10.8 35.0 15.0 11.3 26.3 73.0 104.7 110 3.7** 2.76 10.6 35.0 15.0 11.3 26.3 73.0 104.5 110
240---3---60
1.7 1.27 5.6 35.0 20.0 15.0 35.0 84.2 112.2 125
2.4 1.79 7.1 35.0 20.0 15.0 35.0 84.2 114.1 125
3.7 2.76 10.8 35.0 20.0 15.0 35.0 84.2 118.7 125 3.7** 2.76 10.6 35.0 20.0 15.0 35.0 84.2 118.5 125
014A00 480---3---60
1.7 1.27 2.9 35.0 20.0 15.0 35.0 42.1 56.2 60
2.4 1.79 3.8 35.0 20.0 15.0 35.0 42.1 57.4 60
3.7 2.76 4.9 35.0 20.0 15.0 35.0 42.1 58.7 60 3.7** 2.76 5.3 35.0 20.0 15.0 35.0 42.1 59.2 60
015A00 575---3---60
1.7 1.27 2.8 35.0 20.0 15.0 35.0 35.1 47.4 50
2.4 1.79 3.5 35.0 20.0 15.0 35.0 35.1 48.3 50
3.7 2.76 4.5 35.0 20.0 15.0 35.0 35.1 49.6 50
016A00
40RUQ
16 208---3---60
3.7 2.76 10.8 10.0 7.5 --- 7.5 20.8 39.6 40
5.0 3.73 18.0 10.0 7.5 --- 7.5 20.8 48.6 60
40RUQ
25 208---3---60
5.0 3.73 18.0 10.0 7.5 --- 7.5 20.8 48.6 60
7.5 5.59 23.5 10.0 7.5 --- 7.5 20.8 55.4 70
40RUQ
16 240---3---60
3.7 2.76 10.8 10.0 10.0 --- 10.0 24.1 43.6 50
5.0 3.73 18.0 10.0 10.0 --- 10.0 24.1 52.6 60
40RUQ
25 240---3---60
5.0 3.73 18.0 10.0 10.0 --- 10.0 24.1 52.6 60
7.5 5.59 23.5 10.0 10.0 --- 10.0 24.1 59.4 70
017A00
40RUQ
16…