DANGER
F‐54
消 火 器
Fuel Truck Grounding
High‐High Level 95%: Return Pump On High Level 90%: Supply P Off, Return P Off
Low Level 75%: Supply Pump On Low‐Low Level 70% : Lamp / Alarm
NATO Sign and
Danger Sign
Gauging Port
POL Piping (Under
Ground/Above Ground)
Water Drainage with Wing /Hand pump
Gauge
Ladder
Overflow Shut Off Valve with High Level Alarm
Double Wall SUPPORT AST
Unti‐Syphone Valve
Grounding Wire LineFire
Extinguisher
Dike for>55Gal
Sump Sump
Fuel Level Control
Fuel Containment
* Number reflects tank requirement on the spread sheet
Leak Detector, high level alarm panel
Calibration Chart
1/16” Tank Calibration
Chart
Fuel Day Tank Containment (Separate type/Generator Unit Inside type)
Spill Containment
Water Drainage
Foot Valve
Fill Port
Day Tank
Fuel Fill Port 2”/Spill
Containment
Supply & Return Line (Mark up fuel flow direction)
Flexible joint
PP
Supply & Return Pumps
* Provide some maintenance valves at corners.
Typical Required Fuel Tank System ‐ Pump Type
(Can be combined with Return Line below)
Return Line
M‐2
* Contractor shall made this PDF data with CAD data. 9/9
| 1301-T1 |
| 1301-E1 |
| 1301-E2 |
| 1301-E3 |
| 1301-E4 |
| 1301-E5 |
| 1301-E6 |
| 1301-M1 |
| 1301-M2 |