Please see the below correction to question 8 of the original questions and answers document.
Question 8: Do the Comm closets have user provided racks?
Answer 8: Installation of video security equipment and camera infrastructure was considered during the early design stage of this construction project but was deleted during review. Therefore the Comm closets were not allocated any floor space for any additional video equipment. The racks currently in the design are allocated for communication fiber and copper equipment and did not design for spare rack space. The walls of the com closets were designed to accommodate com equipment and cable TV equipment. No space was allocated for other systems.