FA4659-15-R-0011_-_Drawings_-_308-M-616.pdf
PDF 710 KB Posted
- Attached to
- Repair HVAC Controls & Equipment Multi Facilities Federal contract opportunity
- Solicitation number
- FA4659-15-R-0011
About this file
FA4659-15-R-0011 - Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA4659-15-R-0011_-_Amendment_4.pdf | ||
| FA4659-15-R-0011_-_Amendment_3.pdf | ||
| FA4659-15-R-0011_Technical_Specifications.pdf | ||
| FA4659-15-R-0011_-_Amendment_2.pdf | ||
| FA4659-15-R-0011_-_Amendment.pdf | ||
| FA4659-15-R-0011_-_Technical_Specifications.pdf | ||
| FA4659-15-R-0011_-_Climatalogical_Summary.pdf | ||
| FA4659-15-R-0011_-_SF1442_-_Solicitation.pdf | ||
| FA4659-15-R-0011_-_Technical_Specifications.pdf | ||
| FA4659-15-R-0011_-_Solicitation_Cover_Letter.pdf | ||
| FA4659-15-R-0011_-_Material_Submittal_Schedule.pdf | ||
| FA4659-15-R-0011_-_Past_Performance_Questionnaire_with_Cover_Letter.pdf | ||
| FA4659-15-R-0011_-_Drawings.pdf | ||
| FA4659-15-R-0011_-_FINANCIAL_INSTITUTION_REFERENCE_SHEET.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TS
M
PRE-FILTER
PD
HW COIL CW COIL SUPPLY FAN
M
GD
SUPPLY AIR
3,250 CFM
OUTDOOR AIR
750 CFM
R E
T U
R N
A
I R
C
F M
EXHAUST AIR
3,250 CFM
MECHANICAL POINT LISTING - B308 AHU-7 & AHU-8
MARK DESCRIPTION UN
IT
S
TY
PE
TR
EN
D
SC
HE
DU
LE
D
AL
AR
M
NO
TE
S
CW-V 3-WAY VALVE % AO - - -
HW-V 3-WAY VALVE % AO - - -
FS FREEZE STAT DEG. F AI - - YES
TS-MAT MIXED AIR TEMP. DEG. F AI YES - -
TS-RAT RETURN AIR TEMP. DEG. F AI YES - -
TS-SAT SUPPLY AIR TEMP. DEG. F AI YES YES -
DP-F PRE-FILTER DIFF. PRESS. IN. WC AI - - YES
SA-FAN SUPPLY AIR FAN MOTOR (CURRENT SENSOR) ON/OFF BI - YES YES
LDPR-EA LINKED EXHAUST/RELIEF AIR DAMPER % AO - - -
SD-RA RETURN AIR SMOKE DETECTOR ALARM BI - - YES
SD-SA SUPPLY AIR SMOKE DETECTOR ALARM BI - - YES
TS-RM SPACE TEMP. DEG. F AI YES YES -
KEYNOTE LEGEND
C01 ACTUATOR AND DAMPER. PROVIDE NEW DDC ACTUATOR. DAMPER TO REMAIN.
C05 MOTORIZED 3-WAY VALVE. PROVIDE NEW VALVE BODY AND DDC ACTUATOR.
C08 PROVIDE NEW DUCT MOUNTED, PROBE TYPE TEMPERATURE SENSOR
C11 PROVIDE NEW UNIT MOUNTED, AVERAGING TYPE CAPILARY TUBE TEMPERATURE
SENSOR
C12 PROVIDE NEW UNIT MOUNTED FREEZE STAT
C13 NEW WALL MOUNTED ROOM TEMPERATURE SENSOR. INCLUDE LCD DISPLAY.
OCCUPANCY OVERRIDE AND SETPOINT ADJUSTMENT
C15 EXISTING DUCT MOUNTED SMOKE DETECTOR TO REMAIN
C18 EXISTING PREFILTERS