JPRA-West 600 Amp Automatic Transfer Switch
Required Characteristics:
General Requirements.
Transfer Switch-Electronic Control: 600A (Service Rated)
The transfer switch incorporates electrical and mechanical interlocks to prevent inadvertent interconnection of the source
Listing UL 1008/CSA Certification Application-Commercial power to Genset
Minimum Warranty-2 Year Comprehensive
Poles-4 (Switched Neutral) (VERY IMPORTANT AF REQUIREMENT)
Cabinet-Type Nema1 (inside enclosure) Frequency-60 Hz
System-3 Phase, 3 hots and neutral 4 Wire Voltage-480 Volts AC (Service Rated)
Genset Starting Battery-24V DC PC Control
Transfer switch mechanisms must be equipped with means to manually transfer.
All sources must be de-energized before manual operation is attempted.
Service Tech for startup. (Not installation)