JPRA-West 600 Amp Automatic Transfer Switch
Required Characteristics:
General Requirements.
Transfer Switch-Electronic Control: 600A (Service Rated) The transfer switch incorporates electrical and mechanical interlocks to prevent inadvertent interconnection of the source Listing UL 1008/CSA Certification Application-Commercial power to Genset Minimum Warranty-2 Year Comprehensive Poles-4 (Switched Neutral) (VERY IMPORTANT AF REQUIREMENT) Cabinet-Type Nema1 (inside enclosure) Frequency-60 Hz System-3 Phase, 3 hots and neutral 4 Wire Voltage-480 Volts AC (Service Rated) Genset Starting Battery-24V DC PC Control Transfer switch mechanisms must be equipped with means to manually transfer. All sources must be de-energized before manual operation is attempted.
Service Tech for startup. (Not installation)