Questions and Answers

1. Can we come back this week to check on the Electrical switch gear (Power source for existing compressor)? We would like to check distance, wire size, and breaker size at the switch gear.

panel breaker = 600A x 250Kcmil; from the 200A fuse to compressor = 4/0

2. Can we pour a pad outside for dryer and dry tank. See attached layout drawings. CE is able to put a concrete pad next to the building, but it will not be at the same location drawn in the diagram.

3. Where will this be located? Can you provide us a diagram or a visual aid?

See attachment

CE will allow a concrete block To be placed here on the North East side of this roll up door.

Contractors suggested area for concrete pad is not authorized as the gas meter can not be blocked

CE also stated drilling a hole in the wall for air piping is fine as long as the gap between the holes and the pipes is sealed afterwards.