Details for Electrical Service Panel Skids (Item#:510107) ore equal:

FA441818R0009

400A, 480VAC and 200A, 208Y/120VAC receptacle outlet panel.

Enclosure is type 4X approximately 52”H x 58”W x 34”D, fabricated from 12GA 304SS natural finish, with fork pockets and lifting eyes.

Unit has a center divider to separate the 480VAC service from the 280Y/120VAC service with side access covers.

Input to both services are via Duraline DE1022 and EZ1016 single pole cam-style connectors.

The 480V service contains (2) sets of input cams (located on the left side), one for 400A, one for 200A, each set factory wired to a main circuit breaker (35KAIC @ 480VAC, 65KAIC @ 240VAC). The load of the main circuit breaker is factory wired to the outlet receptacles (3) L16-30, (1) MIL-R-2726/16, (1) 50A pin & sleeve, (1) 60A pin & sleeve, (3) sets of 200A Duraline EZ1016 single pole cam-style receptacles.

Each receptacle has a NEMA 3R weatherproof cover and is individually protected by a circuit breaker (200A cam-style receptacles are protected by adjustable trip 250A circuit breakers) behind a deadfront and hinged cover.

The 208Y/120V service contains (1) set of Duraline input 200A cams (located on the right side), factory wired to a main circuit breaker. The load of the main circuit breaker is factory wired to outlet receptacles (1) PS460R12- W, (5) L6-20, (1) HBL560R9W, (6) 5-20 GFCI, (1) L6-30, (1) L6-50, (1) L15-20, (1) L15-30, (1) CS8369 with a NEMA 3R weatherproof cover, (3) sets of Duraline EZ1016 150A, single pole female cam-style receptacles.

Each receptacle has a NEMA 3R weatherproof cover and is individually protected by a circuit breaker (200A cam-style receptacles are protected by adjustable trip 150A circuit breakers) behind a deadfront and hinged cover.