Atch_3_IGU_Spec_08_88_00.pdf

PDF 378 KB Posted

Attached to
Renovate Bld 450 - ASLAC Federal contract opportunity
Solicitation number
FA4418-16-R-0022
Issued by
Department of the Air Force Air Mobility Command

About this file

Atch 3 - IGU Spec 08 88 00

View the file

Other files for this federal contract opportunity

Other files attached to Renovate Bld 450 - ASLAC, newest first.
File Type Posted
358_Space_Utilization_01-2016_FLOORPLAN.pdf PDF
FA4418-16-R-0022-0001.pdf PDF
FA4418-16-R-0022_fbo_Amendment_4.docx DOCX document
FBO_Amendment_3_FA4418-16-R-0022.pdf PDF
FA4418-16-R-0022_fbo_Amendment_2.pdf PDF
Atch_1_SOW_B450.pdf PDF
Atch_10_SC29_WD_20160715.pdf PDF
Atch_2_B_450_Floorplan.pdf PDF
Atch_5_Spec_01_50_10.pdf PDF
Atch_9_Asbestos_Survey_2010.pdf PDF
Atch_6_Spec_01_54_00.pdf PDF
Atch_7_Green_Procurement_Form.pdf PDF
Atch_8_Asbestos_Survey_1996.pdf PDF
Atch_4_Cable_Mgt.pdf PDF
FA4418-16-R-0022.pdf PDF
Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION 08 88 00

SPECIAL FUNCTION GLAZING

PART 1 - GENERAL

1.1 SUMMARY

A. Section includes:

1. SageGlass or equivalent electronically tintable insulating glass units (IGU) for dynamic light and heat control.

DELETE SECTIONS NOT IN PROJECT. ADD SECTIONS AS NECESSARY.

B. Related Sections:

1. Division 8 – Openings.

2. Division 25 - Integrated Automation.

3. Section 26 09 00 – IGU Wired Control System-Instrumentation and Control for Electrical System.

4. Section 26 09 10 – IGU Unplugged Control System-Instrumentation and Control for Electrical System.

5. Division 26 - Electrical.

1.2 DEFINITIONS

A. Fenestration: Openings in building's envelope including windows, doors, and skylights.

B. Framing System: Basic rigid supporting structure of window.

C. Glazing System: Soft material used in framing system.

D. Bite: Dimension by which edge of glass product is engaged into glazing channel.

E. IGU: Insulating Glass Unit.

F. IGU Pigtail: Wire that extends from individual insulated glass units.

G. Frame Cable: Wire that runs through framing system and connects IGU pigtail to low-voltage wiring on interior of building.

H. 2-ply Laminated Glass: 2-sheets of monolithic glass bonded together with plastic interlayer by heat and pressure.

I. Inboard Lite: Pane of IGU that faces interior of building.

J. Outboard Lite: Pane of IGU that faces exterior of building.

K. Performance Characteristics:

1. Center-of-Glass Characteristics: Performance values that take only center portion of IGU into account and not framing members.

2. Fenestration Performance: Performance based on total fenestration (glass and framing members).

Values that can be validated and certified by National Fenestration Rating Council (NFRC).

L. Sealing Insulating Glass Unit Surfaces and Coating Orientation:

1. Surface 1: Exterior surface of outer laminated glass ply.

2. Surface 2: Interior surface of outer laminated glass ply (surface facing the laminating material).

3. Surface 3: Exterior surface of inner laminated glass ply (surface facing the laminating material).

4. Surface 4: Interior surface of inner laminated glass ply which is coated with the electrochromic layers.

5. Surface 5: Exterior surface of inner pane.

6. Surface 6: Room side surface of inner pane.

M. Tinted: On state, with lowest visible light transmission.

N. Clear: Off state, with highest visible light transmission.

O. Variable Tint: Intermediate tint levels between fully tinted and Clear.

1.3 SYSTEM DESCRIPTION

A. Design Requirements:

1. SageGlass electronically tintable insulated glass units or equivalent shall be operated by an IGU control system as specified in Section 26 09 00.

System must be capable of providing up to 3 independently tintable zones in each pane to provide adequate light quality in the space. Refer to project drawings for zoning specifics.

FRAMING AND GLAZING NOT PROVIDED BY SAGE ELECTROCHROMICS.

2. Framing and Glazing Systems:

a. Designed to accommodate IGU components below:

b. Edge clearance: 1/4 inch (6 mm).

c. Bite clearance: 5/8 inch (16 mm).

d. Face clearance: 3/16 inch (5 mm).

e. Accommodate controls wiring.

f. Has glazing materials that are compatible with materials of SageGlass® IGU.

g. Provide glazing and framing systems capable of withstanding normal thermal movements, wind loads, and impact loads, without failure, including loss due to defective manufacture, fabrication, and installation, deterioration of glazing materials, and other defects in construction.

1) Normal Thermal Movement: Resulting from ambient temperature range of 120 degrees F

(67 degrees C) and from consequent temperature range within glass and glass framing members of 180 degrees F (100 degrees C).

3. Provide glass products in thicknesses and strengths (annealed or heat-treated) required to meet or exceed the following criteria based on Project loads and in-service conditions per the methodology described in ASTM E1300.

a. Select minimum thickness of annealed or heat-treated glass products to ensure probability of failure does not exceed the following:

1) 8 breaks per 1000 for glass installed vertically or not over 15 degrees or more from vertical plan and under wind action.

2) 1 break per 1000 for glass installed 15 degrees or more from vertical plane and under action of wind, snow, or both.

1.4 SUBMITTALS

A. Product Data: Manufacturer's Product Data sheets including installation instructions.

B. Documentation indicating compliance with ASTM E2953-14, Standard Specification for Evaluating

Accelerated Aging Performance of Electrochromic Devices in Sealed Insulating Glass Units as verified by third party test laboratory such as National Renewable Energy Laboratory (NREL).

C. Test Report: ASTM E2190 Specification for IGU Seal Durability. Provide certificate or test report stating that

IGUs that passed the testing requirement contained the electrochromic system (EC coatings, bus bars, wires etc.) as in the product specified herein. If triple glazing is specified herein, a test report for triple glazing is required.

D. IG Certification: IGCC/IGMA certification for insulating glass units containing electrochromic system. Provide certificate stating that IGUs that passed the testing requirement contained the electrochromic system (EC coatings, bus bars, wires etc.) as in the product specified herein. If triple glazing is specified, certification covering triple glazing is required. If capillary tubes are required for altitude applications, certification covering units with capillary tubes is also required.

E. Shop Drawings: Indicate framing system and accommodations for wiring paths, connectors, routing, and exit from framing system.

F. Manufacturer to submit a list containing a minimum of five completed commercial projects completed a minimum of five years ago which successfully utilized their electrochromic glazing product on the project. The list is to include: the project name, address, scope of work, type of application, and contact information for the architect and / or owner.

G. Structural Calculations: Provide structural calculations for framing system certified by structural engineer.

1.5 QUALITY ASSURANCE

A. Comply with published recommendations of glass product manufacturers and organizations below, except where more stringent requirements are indicated. Refer to these publications for glazing terms not otherwise defined in this section or referenced standards.

1. GANA Publications.

2. AAMA Publications.

3. IGMA Publications.

B. Safety glass products in the US are to comply with CPSC 16 CFR Part 1201 for Category II materials and

ANSI Z97.1 2009.

C. Glass thermal and optical performance properties shall be based on calculations from the current LBNL

WINDOW 6.3 computer program.

D. Provide glass that is heat-treated by horizontal (roller hearth) process with inherent roller wave distortion parallel to the base dimension, unless otherwise specified.

E. Manufacturer Qualifications: Manufacturer must have a minimum of five years’ experience manufacturing electrochromic glazing and have EC products successfully installed and operating in at least 5 different commercial architectural project installations for at least 5 years.

F. Installer Qualifications: Acceptable to IGU Electrochromics and capable of preparing data for glazed framing systems, based on testing and engineering analysis equivalent to or exceeding that of SAGE Electrochromics’ standard units.

G. Pre-Installation Meetings: Conduct pre-installation meeting/teleconference with the following parties in attendance:

1. Government, Architect, contractor, glazing contractor, framing manufacturer, IGU and controls manufacturer, electrical contractor, and other parties related to work of this section, to review procedures, schedules, safety, and coordination with other elements of Project.

1.6 DELIVERY, STORAGE, AND HANDLING

A. Comply with manufacturer's instruction for receiving, handling, storing, and protecting materials.

B. Deliver materials in manufacturer's original, unopened, undamaged containers with identification labels intact.

C. Store materials in original packaging, protected from exposure to harmful environmental conditions, including static electricity, and at temperature and humidity conditions recommended by manufacturer.

D. Exercise care to prevent edge damage to glass, wire, and coatings on glass.

E. Where insulating glass units will be exposed to substantial altitude changes, avoid seal ruptures by complying with manufacturer’s recommendations for venting and sealing.

1.7 PROJECT / SITE CONDITIONS

A. Verify frame channel dimensions are adequate for wire runs as designed.

B. Environmental Requirements:

1. Ensure that substrate surface and ambient air temperature are minimum of 40 degrees F (5 degrees C) and rising at application time and remain above 40 degrees F (5 degrees C) for at least 24 hours after application of sealants.

1.8 WARRANTY

A. Warrant IGUs against defects in material or workmanship causing material obstruction of vision as a result of fogging or film formation of the internal glass as a result of failure of the seal for a period of ten (10) years from the date of manufacture of the SageGlass or equivalent IGUs from the Manufacturer.

B. Warrant electrochromic glass against defects in material or workmanship, resulting in failure to tint, for a period of five (5) years from the date of manufacture of the SageGlass or equivalent electrochromic glass from the Manufacturer.

C. Warrant laminated products against lamination defects, such as edge separation or delamination that materially obstruct vision through the glass for a period of five (5) years from the date of manufacture of the SageGlass or equivalent electrochromic glass from the Manufacturer.

D. Warrant IGU controls against defects in material or workmanship for a period of five (5) years from the date of manufacture of the SageGlass or equivalent controls from the manufacturer.

1.9 MAINTENANCE

A. Extra Materials:

1. Furnish 1 percent (minimum of 1 IGU) of each size and type of IGU.

PART 2 - PRODUCTS

2.1 MANUFACTURER

A. The basis for design is SageGlass due to proven success within other Government facility renovations. IGUs selected and used were manufactured by:

SAGE Electrochromics, Inc.

2 Sage Way

Faribault, MN 55021

Local Contact: Jeremy Mack, Atlanta, GA

Telephone: 1-706-501-8205

Fax: 1-507-333-0145

E-mail: jeremy.mack@sageglass.com or bill.myers@sageglass.com

Internet: http://www.sageglass.com.

Alternate products and Substitutions: Alternate IGU products may be considered if they comply with all of the performance requirements of this specification and evidence is submitted of successful applications within similar facilities thereof. Products chosen must be equivalent to or exceed that of SageGlass IGUs.

2.2 MATERIALS – NOTE: IF SELECTED, SAGEGLASS OFFERS ADDITIONAL MAKEUPS TO MEET

DESIGN REQUIREMENTS. PLEASE CONTACT SAGE TO LEARN WHAT INNER PLY THICKNESS,

SPACER THICKNESS, GAS FILL AND INNER LITE THICKNESS OPTIONS ARE AVAILABLE.

Electrochromic Laminated Sealed Insulating Glass Units (IGUs), Air Filled:

1. Laminated Outboard Lite:

a. Outer Ply (Surface 1 & 2):

1) Glass Type: Float glass.

2) Glass Tint: Clear.

3) Nominal Thickness: 0.16 inch (3.9 mm).

4) Heat Treatment: Heat Strengthened

5) Obscuration: <23.5mm from IGU edge black ink obscuration band on surface # 2 around the perimeter.

b. Interlayer (between surface 2 & 3):

1) Interlayer Type: SentryGlas Ionoplast interlayer.

2) Interlayer Tint: Clear.

3) Nominal Thickness: 0.038 inch (0.90mm).

c. Inner Ply (Surface 3 & 4):

mailto:jeremy.mack@sageglass.com?subject=Request%20for%20SageGlass%20Quotation mailto:bill.myers@sageglass.com?subject=Request%20for%20SageGlass%20Quote http://www.sageglass.com/

1) Glass Type: EC 2.0 coated clear float glass.

2) Glass Tint: Electronically variable tintable.

3) Nominal Thickness: 0.087 inch (2.2 mm).

4) Heat treatment: Annealed.

5) Coating Orientation: Surface No. 4.

2. Cavity:

a. Spacer Material: Black finish.

b. Nominal Thickness: 0.45” +/- 0.02 in (11.5 mm +/- 0.5mm).

c. Cavity: 0.5” (12.2mm).

d. Wall Thickness: >/= 0.007 inch (.178 mm).

e. Gas Fill: Air.

f. Desiccant: Four legs filled with blend of 3A molecular sieve and silica gel desiccant.

3. Laminated inboard Lite:

d. Inner Ply (Surface 5 & 6):

1) Glass Type: Float glass.

2) Glass Tint: Clear.

3) Nominal Thickness: 0.16 inch (3.9 mm).

4) Heat Treatment: Heat Strengthened.

e. Interlayer (between surface 6 & 7):

1) Interlayer Type: SentryGlas Ionoplast interlayer.

2) Interlayer Tint: Clear.

3) Nominal Thickness: 0.090 inch (2.28 mm).

f. Outer Ply (Surface 7 & 8):

1) Glass Type: Float glass.

2) Glass Tint: Clear.

3) Nominal Thickness: 0.16 inch (3.9 mm).

4) Heat Treatment: Heat Strengthened.

4. Pigtail:

a. Multi-conductor sheathed cable.

b. 2, 3 or 4 pin weather tight connector.

5. Clear Performance Characteristics (Center of Glass):

a. Visible Transmittance: 63 percent.

b. Exterior Reflectance: No greater than 12 percent.

c. Interior Reflectance: No greater than 13 percent.

d. Summer U-factor (U-value): 0.32.

e. Winter U-factor (U-value): 0.32.

f. Solar Heat Gain Coefficient (SHGC): 0.44.

g. Shading Coefficient: 0.50.

6. Tinted Performance Characteristics (Center of Glass):

a. Visible Transmittance: 1 percent.

b. Exterior Reflectance: 6 percent.

c. Interior Reflectance: No greater than 10.5 percent.

d. Summer U-factor (U-value): 0.32.

e. Winter U-factor (U-value): 0.32.

f. Solar Heat Gain Coefficient (SHGC): 0.10.

g. Shading Coefficient: 0.12.

7. In-Pane Zoning

a. Provide up to 3 separate, independently tintable, sections (zones) within each electrochromic insulating glass unit to provide optimum daylight control, glare control and indoor light color quality (see architectural drawings for specific location and number of in-pane zones).

b. Each zone within the pane shall be individually controllable in accordance with standard, published capabilities of single zone panes with regard to level of tint and integration with system controllers and accessories.

c. For a three zone EC insulating glass unit, the individual pane is segmented so that zones/sections are vertically above the other to create a bottom, middle and top zone in the unit.

d. For a two zone EC insulating glass unit, the individual pane is segmented so that zones/sections are vertically above the other to create a bottom and top zone in the unit.

e. For a one zone electrochromic insulating glass unit, the entire area of the pane is controlled as one segment.

B. Frame Cable (one per IGU):

1. Multi-conductor plenum rated sheathed cable type CMP/CL2P.

2. 2, 3 or 4 pin weather tight connector.

3. Connector shall be thin at <0.2” in height and installed in the glazing pocket or other easy to access space in the framing system for ease of maintenance.

C. Off state: Clear.

D. Operating Voltage: 5 volts DC or less applied to the EC insulating glass. Class 2 (low voltage, low current) electrical system.

E. Requirements:

1. Control functionality: Automated control for daylight and glare shall be provided (reference Division

26 section 09 00). Manual over-ride must be provided in designated locations via wall mounted switch(es) or a software application. When a manual command is given via the wall switch or software application, it must over-ride the automated system immediately and initiate the requested change in state of the glass. Subsequent manual commands via the manual over-ride system must over-ride the previous command and be acted on by the control system immediately to initiate the requested change in state. This must occur no matter how soon the subsequent manual command(s) follow the previous manual command.

2. Heat-Strengthened Float Glass: Comply with ASTM C1048, Type I, Class 1 (clear), Quality Q3, Kind

HS.

3. Tempered Float Glass: Comply with ASTM C1048, Type I, Class 1 (clear), Quality Q3, Kind FT.

4. Safety Tempered Float Glass: Comply with ANSI Z97.1 and CPSC 16 CFR 1201.

5. Laminated Glass: Comply with ASTM C1172 and other requirements as specified.

6. Fabricate laminated glass products in autoclave with heat, plus pressure, free of foreign substances and air pockets.

7. Coated glass: For point defects, comply with ASTM C1376-10 section 6.1 (vision glass) or 6.2

(overhead glass) as appropriate for the glazing application. For vision glass the ASTM C1376-10 standard requires that the glass be inspected at a distance of 10 ft (3m) at a 90 o viewing angle against a bright uniform background. It allows for no more than 2 readily apparent blemishes in a 3” (75mm) diameter circle and no more than 5 readily apparent blemishes in a 12” (300mm) diameter circle. In addition, the maximum allowable pinhole and spot size is 1.6mm or 2.4mm in the central area and outer area respectively. The maximum length of a coating scratch or mark is 2” (50mm) and 3” (75mm) in the central and outer areas respectively. For more detail and definitions of central and outer area see

ASTM C1376-10.

8. Provide sealed IGU with dehydrated airspace, primary seal of polyisobutylene (PIB); color black and secondary seal of two part silicone; color- black, and >0.007 inch (.15mm) wall thickness stainless steel spacer as specified.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Site Verification and Conditions

1. Verify that site conditions are acceptable for glass installation.

2. Verify openings for glazing are correctly sized and within tolerance.

3. Verify that functioning weep system is present.

4. Verify that minimum required face and edge clearances are being met.

5. Verify that glazing channels and recesses are clear and free of obstructions, weeps are clear, and channels and recesses are ready for glazing.

6. Verify that framing system is appropriately sized for IGU thickness and that precautions are taken to not over compress the edge seals of the IGU when the glass is installed.

B. Do not proceed with glazing until unsatisfactory conditions have been corrected.

3.2 PREPARATION

A. Surface Preparation:

1. Clean and prepare glazing channels and other framing members to receive glass and wire.

2. Remove coatings and other harmful materials that will prevent glass and glazing installation required to comply with performance criteria specified.

3. Install grommets at all locations where Frame Cable will penetrate metal framing or structure.

3.3 INSTALLATION

A. Install products using recommendations of manufacturers of glass, sealants, gaskets, and other glazing materials, except where more stringent requirements are indicated, including those in the "GANA Glazing

Manual".

B. Verify that IGU secondary seal is compatible with glazing sealants.

C. Install glass in prepared glazing channels and other framing members.

D. Install glass per framing manufacturer’s wiring diagram showing IGU orientation and wire exit point into building. Comply with glass manufacturer’s labels and instructions for glass orientation.

E. Protect IGU pigtail and Frame Cable from any damage during installation. Use grommets during installation to protect wire when routing through frame. If Frame Cable or the connector is damaged during installation the Frame Cable must be replaced. If the IGU pigtail connector is damaged during installation manufacturer must be notified and the connector must be repaired with a manufacturer approved method.

F. PVC jacketed plenum cables (Bus, IGU Pigtails, 12 Conductor Cable, Frame Cables, Sensor Cables) should be conditioned for 24 hours at room temperature prior to installation and never installed below 0°C (32° F) ambient temperature. Once installed these wires must not be exposed to sunlight even through glass. If they are installed in an exposed location they must be covered or painted (latex / water based paint only).

G. Verify glazing pocket where IGU Pigtail and Frame Cable connection is made is a dry location.

H. Install silicone setting blocks in rabbets as recommended by referenced glazing standards in GANA Glazing

Manual and IGMA Glazing Guidelines and manufacturer’s Glazing Guidelines.

I. Use silicone edge blocks for all installed panes to prevent glass from walking post installation.

J. Provide bite on glass, minimum edge and face clearances, and glazing material tolerances recommended by

GANA Glazing Manual and as approved by glass manufacturer.

K. Provide weep system as recommended by GANA Glazing Manual.

L. Distribute weight of glass unit along edge rather than at corners.

M. Comply with framing manufacturer's and referenced industry recommendations on expansion joints and anchors, accommodating thermal movement, glass openings, use of setting and edge blocks, use of glass spacers, edge blocks, and installation of weep systems. Setting and edge blocks must be made from silicone.

The use of setting blocks made from other materials than as approved by manufacture is not permitted, as material has been known to alter the chemical makeup of plastics and rubbers they come in contact with, resulting in seal failure.

N. Protect glass from edge damage during handling and installation.

O. Install per IGMA North American Glazing Guidelines for Sealed Insulated Glass Units, for Commercial and

Residential Use TM-3000-90(04) states “For dry glazed systems, an adequate seal should consist of a minimum of 0.70 N/mm (4 lb/in) and not exceeding 1.75 N/mm (10 lb/in) applied to the edges of the insulated glass unit by gaskets or other fastening systems.”

P. Prevent glass from contact with contaminating substances that result from construction operations, such as weld spatter, fireproofing, or plaster.

Q. Once electronically tintable IGUs have been removed from manufacturer Electrochromics’ packaging, remove labels within 30 days of exposure to sunlight or other UV light sources.

3.4 ADJUSTING

A. Remove glass that is broken, chipped, cracked, or damaged in any way, and replace with new materials.

Damaged glass is glass with edge damage or other imperfections that, when installed, could weaken glass and impair performance and appearance.

3.5 CLEANING

A. Clean glass inside and outside, immediately after installation and sealants have cured, per manufacturer

Electrochromics’ written recommendations.

B. Remove labels and markings from glass.

C. Clean glass per:

1. GANA Glass Informational Bulletin GANA 01-0300 - Proper Procedures for Cleaning Architectural

Glass Products.

2. GANA Glass Information Bulletin GANA TD-02-0402 – Heat-Treated Glass Surfaces Are Different.

D. Do not use scrapers or other metal tools to clean glass.

3.6 TESTING

A. Do not use ‘high voltage spark’ gas analyzers such as Sparklike’s Gasglass on this product. Film and controls damage may occur and potentially void the warranty.

END OF SECTION

SECTION 26 09 00

IGU WIRED CONTROL SYSTEM - INSTRUMENTATION AND CONTROL FOR ELECTRICAL SYSTEM

PART 4 - GENERAL

4.1 SUMMARY

A. Section includes:

1. Control system for use with SageGlass or equivalent insulating glass units.

B. Related Sections:

1. Section 08 88 00 - Special Function Glazing.

2. Division 25 - Integrated Automation.

3. Division 26 - Electrical.

4.2 DEFINITIONS

A. IGU: Insulating Glass Unit.

B. IGU Pigtail: Cable that extends from individual insulating glass units.

C. Frame Cable: Cable that runs through framing system and connects IGU Pigtail to low voltage wiring on interior of building.

D. Interior Daylight Sensor: A Photosensor mounted on or near the interior of the framing system to measure the amount of light coming through SageGlass® glazing; used for automatic control of tint level to achieve consistent daylighting.

E. Exterior Daylight Sensor: A Photosensor mounted on or near the exterior of the framing system to measure available daylight; used for automatic control of tint level to achieve consistent daylighting.

F. Sensor Cable: Cable that runs through framing system and connects Daylight Sensor to low voltage wiring on interior of building.

G. IGU Switch: Wall-mounted two-button control interface of insulated glass units.

H. IGU Controller: Control module for up to 6 SageGlass or equivalent IGU’s or Daylight Sensors.

I. I/O Controller: Control module for analog/digital inputs and outputs.

J. System Integration Module: Programmable control module with a variety of automation interfaces, including optional BACnet and LonWorks modules which allow access to the SageGlass or equivalent control system.

K. Control Panel: Enclosure for SageGlass or equivalent IGU controls which mounts to an indoor surface or may be recessed in a wall for flush mounting; includes flush mount cover.

L. 12-conductor Cable: Cable which runs from the SageGlass or equivalent Controller to the Terminal Box

(maximum length of 300ft) in installations where more than 125 feet of wiring is required between Control

Panels and IGUs.

M. Terminal Box: Junction Box where 12-conductor Cables are connected to Frame Cables; mounts to an indoor surface or may be recessed in a wall for flush mounting; includes flush-mount cover.

N. IGU Bus™: Communications bus between IGU control products.

O. IGU Bus™ Cable: Cable which runs between IGU control products allowing communications (maximum length in daisy-chain configuration is 1500ft).

P. Backplane: An assembly, mounted inside a SageGlass or equivalent Control panel, with sockets for up to four

SageGlass or equivalent controllers and wiring connections for IGUs, power supplies, and sensors.

Q. 24V Power Supply: A UL listed, NEC Class 2 power supply which provides safe, low-voltage power from the

AC mains for use with IGU Controllers.

R. 12V Power Supply: A UL listed, NEC Class 2 power supply which provides safe, low-voltage power from the

AC mains for use with IGU System Integration Modules and Switches.

4.3 SYSTEM DESCRIPTION

A. Basic Controls

1. Each IGU Controller controls and monitors up to six IGUs or Daylight Sensors.

2. IGU Controller channels will be configured into multiple zones for independent operation of specific areas of the glazing.

3. System is configured for four tint levels (fully tinted, fully clear, and two intermediate).

B. Automation

1. SageGlass or equivalent controllers will be configured to automatically maintain daylight at a target brightness range by monitoring a Daylight Sensor.

2. A System Integration Module will automatically control one or more zones based on some combination of time, solar time (referenced to sunrise, sunset or solar noon) and sensor levels (e.g., light, occupancy, or temperature).

C. User Interface

1. SageGlass or equivalent Switches provide local control of one or more control zones to specific tint levels.

2. SageGlass or equivalent Switches permit specific control zones to be locally switched between automatic and manual over-ride modes.

D. System Integration

1. A System Integration Module enables integration with other automation systems using BACnet, LonWorks, and serial interfaces.

4.4 SUBMITTALS

A. Product Data: IGU Electrochromics’ Product Data sheets including installation instructions.

B. Shop Drawings: Indicate wiring diagram, connections to Frame Cables, and other related connections.

Indicate locations of materials and routing of wiring.

4.5 QUALITY ASSURANCE

A. Installer Qualifications: Acceptable to IGU Electrochromics and capable of preparing data for control systems, based on testing and engineering analysis of SAGE or equivalent Electrochromics’ standard units in assemblies similar to those indicated for this Project.

B. Pre-Installation Meetings: Conduct pre-installation meeting or teleconference with the following parties in attendance:

1. Government, Architect, Contractor, glazing contractor, framing manufacturer, IGU Electrochromics manufacturer, electrical contractor, automation engineer, and other parties related to Work of this

Section, to review procedures, schedules, safety, and coordination with other elements of Project.

4.6 DELIVERY, STORAGE, AND HANDLING

A. Comply with IGU manufacturer instruction for receiving, handling, storing, and protecting materials.

B. Deliver materials in IGU manufacturer original, unopened, undamaged containers with identification labels intact.

C. Store materials in original packaging, protected from exposure to harmful environmental conditions, including static electricity.

D. All cables supplied by manufacturer should be conditioned for 24 hours at room temperature prior to installation and never installed below 32 degrees F (0 degrees C) ambient temperature.

4.7 PROJECT / SITE CONDITIONS

A. Verify location of Control Panels and IGU Switches within building.

B. Verify locations of Terminal Boxes (if used) near IGUs.

C. Verify penetration locations of Frame/Sensor Cables into building.

D. The IGU control system must be installed in an indoor, climate-controlled environment.

E. Once installed, cables supplied by IGU manufacturer must not be routinely exposed to sunlight, even through glass.

4.8 WARRANTY

A. Warrant IGU controls against defects in material or workmanship for a period of five years from the date of shipping of the Controls from manufacturer per the manufacturer’s warranty.

PART 5 - PRODUCTS

2.1 MATERIALS

A. SageGlass or equivalent Panel Mounted Control System:

1. IGU Switch:

a. Power specifications

a. Peak Power: 1 watt.

b. Max input voltage: 12 volts DC.

c. Max input current: 0.1 amp.

b. Dimensions

a. Height: 4.1 inch (10.4 cm).

b. Width: 1.75 inch (4.45 cm).

c. Depth: 1.0 inch (2.54 cm).

c. Optional accessories

a. Bright white designer-style faceplate to fit installed single gang boxes. Supplied by manufacturer.

b. Single gang boxes to house IGU Switches. Supplied by Electrical

Contractor.

2. SageGlass or equivalent Controller (One Controller required for every 3-6 IGUs, depending on the number of sub-panes per IGU):

a. Power specifications

a. Electrical Peak Power: 80 watts.

b. Maximum Input Voltage: 24 volts DC.

c. Maximum Input Current: 3.3 amps.

d. Maximum Output Voltage: 16 volts DC.

e. Maximum Output Current (per channel): 2.5 amps.

b. Dimensions

a. Height: 2.75 inch (7.0 cm).

b. Width: 4.25 inch (10.8 cm).

c. Depth: 0.38 inch (1.0 cm).

3. I/O controller (requires one backplane slot; provides analog/digital inputs and outputs):

a. Power specifications

a. Electrical Peak Power: 80 watts.

b. Maximum Input Voltage: 24 volts DC.

c. Maximum Input Current: 3.3 amps.

d. Maximum Output Voltage: 22 volts DC.

e. Maximum Output Current (per channel): 90 mA.

EDIT NOTE: USE THE FOLLOWING IF INTEGRATION INTO BUILDING AUTOMATION SYSTEMS SUCH AS

LIGHTING CONTROLS THROUGH DRY CONTACT INPUT IS REQUIRED

f. Dry Contact Input. One channel of the I/O Controller Card provides

5VDC to one terminal of up to 11 independent contact closure inputs.

b. Dimensions

a. Height: 2.75 inch (7.0 cm).

b. Width: 4.25 inch (10.8 cm).

c. Depth: 0.38 inch (1.0 cm).

4. Backplane (attaches into Control Panel; one required for each one to four SageGlass® Controllers in a

Control Panel, depending on IGU size and configuration).

a. Length: 3.75 in (9.5 cm).

b. Width: 7.5 inch (19 cm).

c. Depth: 1.0 in (2.5 cm).

5. 24V Power Supply (one required for each Backplane in a panel):

a. Power Specifications

a. UL Listed, Class 2.

b. Max input Power: 110 watts.

c. Input voltage: 99 - 253 volts AC, 50/60 Hz.

d. Max output power: 91.2 watts.

e. Output voltage: 24 volts DC.

f. Max output current: 3.8. amps.

b. Dimensions

a. Length: 3.6” (9.1 cm).

b. Width: 3.5” (9.0 cm).

c. Depth: 2.2” (5.6 cm).

6. 12V Power Supply (one required for each System Integration Module and/or network of IGU

Switches):

a. Power Specifications

a. UL Listed, Class 2.

b. Max input Power: 65 watts.

c. Input voltage: 99 – 253 volts AC, 50/60 Hz.

d. Max output power: 54 watts.

e. Output voltage: 12 volts DC.

f. Max output current: 4.5 amps.

b. Dimensions

a. Length: 3.6” (9.1 cm).

b. Width: 2.8” (7.1 cm).

c. Depth: 2.2” (5.6 cm).

7. System Integration Module:

a. Power Specifications:

a. Peak Power: 60 watts.

b. Maximum Input Voltage: 12 volts DC.

c. Maximum Input Current: 1 amp.

b. Dimensions:

a. Height: 6 inch (15 cm).

b. Width: 7.5 inch (19 cm).

c. Depth: 1.5 inch (3.8 cm).

c. Interfaces:

a. RS-232.

b. Ethernet.

Optional interface capabilities:

c. BACnet MS/TP or IP.

d. LonWorks.

8. Exterior Daylight Sensor

a. Photosensor.

b. Illuminance ranges: 0-1000 fc.

c. Power specifications

a. Max input voltage: 24V DC.

b. Output voltage: 0-10V DC.

d. Dimensions

a. Diameter: 1.5 inches (5.1 cm).

b. Depth: 2.7 inches (3.0 cm).

e. Color: White .

9. Interior Daylight Sensor

a. Photosensor.

b. Illuminance ranges: 0-3.2 klux, 0-32 klux, 0-65 klux.

c. Power specifications

a. Max input voltage: 24V DC.

b. Output voltage: 0-10V DC.

d. Dimensions

a. Diameter: 2.0 inches (5.1 cm).

b. Depth: 1.2 inches (3.0 cm).

e. Color: White.

EDIT NOTE: DELETE PANEL SIZES NOT REQUIRED ON PROJECT.

10. Small Panel:

a. Dimensions (without cover)

a. Height: 23.3 inch (59.1 cm).

b. Width: 14.3 inch (36.2 cm).

c. Depth: 3.8 inch (9.5 cm).

b. Dimensions (including cover)

a. Height: 26.2 inch (66.4 cm).

b. Width: 17.2 inch (43.6 cm).

c. Depth: 4.9 inch (12.5 cm).

c. Capacity:

a. Three Backplanes or two Backplanes and one System Integration

Module.

b. Three 24V or 12V power supplies.

d. Color: White.

e. Includes flush-mount cover.

11. Medium Panel:

a. Dimensions (without cover)

a. Height: 35.3 inch (89.5 cm).

b. Width: 17.5 inch (44.4 cm).

c. Depth: 3.8 inch (9.5 cm).

b. Dimensions (including cover)

a. Height: 38.2 inch (96.9 cm).

b. Width: 20.4 inch (51.8 cm).

c. Depth: 4.9 inch (12.5 cm).

c. Capacity:

a. Six Backplanes or five Backplanes and one System Integration

Module.

b. Six 24V or 12V power supplies.

d. Color: White.

e. Includes flush-mount cover.

12. Large Panel:

a. Dimensions (without cover)

a. Height: 51.3 inch (130.2 cm).

b. Width: 17.5 inch (44.4 cm).

c. Depth: 3.8 inch (9.5 cm).

b. Dimensions (including cover)

a. Height: 54.2 inch (137.5 cm).

b. Width: 20.4 inch (51.8 cm).

c. Depth: 4.9 inch (12.5 cm).

c. Capacity:

a. Nine Backplanes and one System Integration Module.

b. Ten 24V or 12V power supplies.

d. Color: White.

e. Includes flush-mount cover.

13. Terminal Box:

a. Terminal Box Enclosure:

a. Height: 10 inch (25.4 cm).

b. Width: 14.4 inch (36.58 cm).

c. Depth: 2.5 (6.35 cm).

d. Capacity: 4 12-conductor Cables.

e. Color: White.

f. Terminal block type: Screw terminals.

b. Terminal Box Cover:

a. Height: 11.25 inch (28.58 cm).

b. Width: 15.63 inch (39.7 cm).

c. Color: White.

d. Includes flush-mount cover.

EDIT NOTE: DELETE THE FOLLOWING CONTROL SYSTEM IF NOT REQUIRED ON PROJECT.

14. IGU AT-410S Solo Output Module Control System (integrated two button switch with a four output controller):

a. Power specifications

a. Peak Power: 40 watts.

b. Maximum Input Voltage: 12 volts DC.

c. Maximum Input Current: 3.4 amps.

d. Fuse Rating: 4 amps.

e. Maximum Output Voltage: 12 volts DC.

f. Maximum Output Current (per channel): 1 amp.

b. Dimensions

a. Height: 4.1 inches (10.4 cm).

b. Width: 1.75 inches (4.45 cm).

c. Depth: 1 inch (2.54 cm).

c. Power Supply:

a. UL Listed, Class 2.

b. Max input power: 70 watts.

c. Input voltage: 90-305 volts AC, 50/60 Hz.

d. Max output power: 60 watts.

e. Max output voltage: 12 volts DC.

f. Max output current: 5 amps.

d. Optional accessories

a. Bright white designer-style faceplate to fit installed single gang boxes. Supplied by IGU manufacturer.

b. Single gang boxes to house IGU Switches. Supplied by Electrical

Contractor.

B. Class 2 Wiring:

1. 12-conductor Cable: Twelve conductor 16 or 18 AWG cable. Cable is of type Plenum PVC, CMP/CL2P insulation which complies with the typical requirements of the NEC and applicable building codes for Class 2 low voltage DC circuits.

2. IGU Bus™ Cable: Four-conductor cable containing an 18 AWG power pair and a 22 AWG twisted/shielded data pair. Cable is of type Plenum PVC, CMP/CL2P insulation and complies with the typical requirements of the NEC and applicable building codes for Class 2 low voltage DC circuits.

THE FOLLOWING MATERIAL IS NOT FURNISHED BY IGU MANUFACTURER. THESE NEED TO BE

PROVIDED BY CONTRACTOR.

C. 120V AC Wiring: 120V AC,15A or 20A service to each control enclosure.

PART 6 - EXECUTION

3.1 INSTALLATION

A. Cross functional team required.

B. Ensure that equipment, conduit, gang boxes, and other related materials are installed and ready to receive Work of this Section.

C. Install products per SAGE’s instructions.

D. Install SageGlass or equivalent Switches, Interior Daylight Sensors, Terminal Boxes and Panels in an indoor, climate-controlled environment.

E. Ensure Control Panels and Terminal Boxes are installed so as to be accessible.

F. Ensure 12-Conductor Cable runs between Control Panels and Terminal Boxes do not exceed the lengths shown in the following table, based on the length of Frame Cables used (top row):

Cable lengths in feet

Standard Frame Cables 50 75 125

12-Conductor Cable Maximum (AWG18) 200 125 0

12-Conductor Cable Maximum (AWG16) 300 200 0

G. Ensure total IGU Bus™ Cable run between Control Panels and IGU Switches is no longer than 1500 feet.

H. Ensure IGU Bus™ Cable connects all IGU Switches and Control Panels in a daisy-chain configuration.

I. Ensure IGU Bus™ Cable has been properly terminated at each end of line, using the jumpers on the IGU controller, IGU Switch and System Integration Module.

J. Install IGU Switches in standard single or multi- gang wall mounted junction box.

3.2 COMMISSIONING

A. Before start-up of SageGlass or equivalent system, conduct visual inspection to verify system is installed per code and in working order. Verify proper wire connections to and from equipment and insulating glass units.

B. When system is in start-up, conduct an overall system test and verify system is operating per system

SAGE’s operating instructions.

EDIT NOTE: USE THE FOLLOWING IF INTEGRATION WITH LIGHTING CONTROL SYSTEM

C. The electrochromic and lighting control systems shall be commissioned together to verify the Sequence of Operations by the lighting control system and the electrochromic glass manufacturers.

END OF SECTION

SECTION 08 6 25

METAL-FRAMED SKYLIGHTS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following:

1. Aluminum-framed double pitched skylights.

B. Related Sections may include, but are not limited to the following:

1. Division 5 Section "Structural Steel" for steel framing.

2. Division 7 Section "Joint Sealants" for sealants installed at metal-framed skylight perimeters.

3. Division 8 Section 08 88 00 Glass & Glazing

4. Division 26 09 00 Electrical

1.3 PERFORMANCE REQUIREMENTS

A. General: Provide metal-framed skylights capable of withstanding loads and thermal and structural movements indicated without failure. Failure includes the following:

1. Deflection exceeding specified limits.

2. Weakening of fasteners, attachments, and other components.

B. Deflection Limits: As follows:

1. Deflection of the entire length of framing members in direction normal to glazing plane is limited to

1/175 of clear span.

C. Lateral Support: Compression flanges 75% of flexural members requiring lateral be laterally braced by cross members with minimum depths equal to flexural member depth and by anchors to the building structure.

Glazing material does not provide lateral support.

D. Structural Loads: Provide metal-framed skylights, including anchorage, capable of withstanding the effects of the following design loads when supporting full dead loads:

1. Roof Loads

a. Concentrated Load: 250 lb applied to framing members at location that produces the most severe stress or deflection.

b. Snow Loads: As indicated.

c. Roof Loads: As indicated.

2. Seismic Loads: As indicated.

E. Structural Performance: Provide metal-framed skylights, including anchorage, capable of withstanding test pressure indicated without material and deflection failures and permanent deformation of structural members exceeding 0.2 percent of span when tested according to ASTM E 330.

1. Test Pressure: 160 PSF of positive and 160 PSF of negative wind-load design pressures.

2. Impact Resistance: Insulated glass glazed skylight system must meet the requirements per ASTM E

1996-02.

3. Static Air Pressure: Insulated glass glazed skylight system must meet the requirements per ASTM E

330.

4. Structural Loads: Insulated glass glazed skylight system must meet the requirements per ASTM E 330;

Design Pressure = 80 PSF.

5. Cyclic Wind Pressure Loading: Insulated glass glazed skylight system must meet the requirements per

ASTM E 1886; Design Pressure = 80 PSF.

F. Thermal Movement: Provide metal-framed skylights that allow for thermal movements resulting from the following maximum change (range) in ambient temperatures by preventing buckling, sealant failure, and other detrimental effects.

1. Temperature Change (Range): 100 deg F.

G. Air Infiltration: Provide metal-framed skylights with maximum air leakage of 0.06 cfm/sq. ft. (0.03 L/s per sq.

m) of surface when tested according to ASTM E 283 at a minimum static-air-pressure differential of 6.24lb/sq.

ft. (300 Pa).

H. Water Penetration: Provide metal-framed skylights that do not evidence water penetration when tested according to ASTM E 331 at a minimum differential static pressure of 20 percent of positive design wind pressure, but not less than 12 lb/sq. ft. (584 Pa).

1.4 SYSTEM DESCRIPTION

A. Aluminum-framed double pitch skylights: Provide units meeting the following requirements:

1. Span: 15’-0” O.D. Curb (horizontal)

2. Length: 42’- 0” O.D. of curb along length

3. Pitch: 4:12

4. Vertical glazed Ends

1.5 SUBMITTALS

A. Product Data: Include construction details, material descriptions, dimensions and profiles of components, and finishes for metal-framed SageGlass IGU skylights or equivalent.

B. Shop Drawings: For metal-framed I SageGlass IGU or equivalent skylights. Include plans, elevations, sections, details, and attachments to other work as required.

1. Include structural analysis data signed and sealed by the qualified professional engineer responsible for their preparation. Structural calculations shall be based on dimensions released for fabrication.

2. Include Electrochromic Glass layout, sensor locations, details for terminal boxes, control panels and low voltage wiring layout within the skylight system.

C. Samples for Initial Selection: Manufacturer's color charts consisting of sections of units showing the full range of colors available for factory-finished aluminum.

D. Samples for Verification: Provide 12-inch long sections of extrusions or formed shapes in same thickness and material indicated for the Work. Mill finished sampler to be provided on piece of 2”x3” aluminum sheet.

E. Installer Certificates: If required, signed by manufacturer certifying that installers comply with requirements.

F. Product Test Reports: From a qualified testing agency indicating skylights comply with requirements, based on comprehensive testing of current products.

G. Field Test Reports: Not required.

1.6 QUALITY ASSURANCE

A. Installer Qualifications: An experienced installer who has specialized in installing metal-framed skylights similar to those indicated for this Project and who is acceptable to manufacturer.

B. Professional Engineer Qualifications: A professional engineer who is experienced in providing engineering services of the kind indicated. Engineering services are defined as those performed for installations of skylights that are similar to those indicated for this Project in material, design, and extent.

C. Testing Agency Qualifications: An independent approved testing agency with the experience and capability to conduct the testing indicated, as documented according to ASTM E 548.

D. Pre-construction Testing: Not required.

E. Pre-construction Sealant Compatibility and Adhesion Testing: Not required.

F. Pre-installation Conference: When required, conduct conference at Project site to comply with requirements in

Division 1 Section "Project Meetings." Review methods and procedures related to metal-framed skylights including, but not limited to, the following:

1. Inspect and discuss condition of substrate and other preparatory work performed by other trades.

2. Review structural load limitations.

3. Review skylight curb structural requirements.

4. Review and coordinate Electrochromic Glass materials list/components with contractor and electrical contractor.

5. Review and finalize construction schedule and verify availability of materials, Installer's personnel, equipment, and facilities needed to make progress and avoid delays.

6. Review required testing procedures.

7. Review weather and forecasted weather conditions and procedures for unfavorable conditions.

8. Review protection of adjacent roof areas.

9. Review preparation and other requirements for installing structural silicone sealant.

1.7 PROJECT CONDITIONS

A. Field Measurements: Where metal-framed skylights are indicated to fit to other construction, verify dimensions of other construction by field measurements before fabrication and indicate measurements on Shop

Drawings. Coordinate fabrication schedule with construction progress to avoid delaying the Work.

1. Established Dimensions: Where field measurements cannot be made without delaying the Work, establish dimensions and proceed with fabricating skylights without field measurements. Coordinate construction to ensure that actual dimensions correspond to established dimensions.

1.8 WARRANTY

A. Warranty: Written warranty, executed by manufacturer agreeing to repair or replace components of metal-framed skylights that fail in materials or workmanship within specified warranty period. Failures include, but are not limited to, the following:

1. Structural failures.

2. Failure of systems to meet performance requirements.

3. Deterioration of metals, metal finishes, and other materials beyond normal weathering.

4. Water leakage; defined as uncontrolled water appearing on normally exposed interior surfaces of skylights from sources other than condensation, resulting from defects in skylight materials or workmanship. (Water controlled by flashing and gutters and drained back to the exterior and that cannot damage adjacent materials or finishes is not water leakage). Water leakage resulting from improper installations is not part of this warranty.

5. Warranty Period: Ten (10) years from date of final completion.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Manufacturers: Pinnacle HU system by Wasco Products, Inc. or equivalent. Contact:

John Douglass, Wasco Products: 207-216-4509, jdouglass@wascoproducts.com

B. Substitutions: Substitute manufacturers must have been in the custom skylight business for not less than a period of 15 years and must submit to the Architect the following:

1. List of similar IGU projects successfully completed within the last five years.

2. Complete details of proposed IGU skylight.

3. Complete specifications for Architect’s review.

2.2 FRAMING MATERIALS

A. Framing Members: Extruded aluminum alloy 6063-T6, ASTM B 221 with minimum effective thickness of

0.109 inches.

B. Exterior Pressure Caps: Extruded aluminum alloy 6063-T6, ASTM B 221 with minimum effective thickness of

0.090 inches.

C. Concealed Flashing: Manufacturer's standard corrosion-resistant, non-staining, non-bleeding flashing;

compatible with adjacent materials.

D. Exposed Flashing and Closures: Aluminum sheet alloy and temper of 1100-H14, thickness as require for proper performance.

1. Minimum Thickness: 0.032 inch Apron Flashing.

2. Minimum Thickness: 0.090 inch Closures.

E. Fasteners and Accessories: Manufacturer's standard corrosion-resistant, non-staining, non-bleeding fasteners and accessories; compatible with adjacent materials.

1. Aluminum-Retaining-Cap Fasteners and Framing Members Fasteners: ASTM A 193/A 193M, Series

300 stainless-steel screws; type as recommended by manufacturer.

2. Connections to Supporting Structure: Series 300 Stainless Steel or ASTM A 307, hot dipped galvanized steel fasteners.

F. Framing-System Sealants: Single-component, non-sag, high performance, non-priming, gun-grade elastomeric polyurethane sealant furnished by skylight manufacturer.

1. Sealant complies with ASTM C920, Type S, Grade NS, Class 25, Use T, NT, M, A, G, and O.

Canadian Specification CAN/CGSB-19.13-M87, ClassificationMCG-2-25-A-N.

2. Sealant conforms to USDA approval standards.

3. Color: Gray or Dark Bronze.

G. Bituminous Paint: Cold-applied asphalt mastic paint complying with SSPC-Paint 12, except containing no asbestos, and formulated for 30-mil thickness per coat.

2.3 ELECTROCHROMIC GLAZING MATERIALS/COMPONENTS

Insulating Electrochromic Glass: 1-5/16 inch consisting of ¼” Clear H.S. Laminated with .090 Sentry Glass

Plus Ionoplast inter layer exterior lite, 1/2 inch sealed air space with black stainless steel spacer, 9/16 inch clear heat strengthened laminated safety glass interior lite with .090 Sentry Glass Plus interlayer. Black Silicone

Seal.

Frame, sensor and Conductor cables, Power Supplies, Controller/backplane, Controller Panels/backplanes, Terminal Boxes, Daylight Sensors, Bus Cable, System Integration Module, and switch. These components will be furnished for installation by the electrical contractor.

* For additional information on glass, refer to Section 08 88 00.

A. Glazing Gaskets: 1/4” x 5/8” medium density structural glazing tape that meets AAMA 800-88. Structural glazing tape to be compatible with structural silicone adhesive sealant.

B. Spacers, Edge Blocks, and Setting Blocks: Manufacturer's standard permanent non-migrating type of elastomer type and hardness selected to comply with requirements. Spacers, Edge Blocks, and Setting Blocks to be extruded thermoplastic elastomer by the skylight manufacturer.

C. Structural Glazing Weatherseal Sealant: Single component neutral-curing silicone sealant recommended by skylight and sealant manufacturers for this use and furnished by skylight manufacturer.

1. Sealant is capable of withstanding 50 percent movement in both extension and compression (total of

100 percent movement) when tested for adhesion and cohesion under maximum cyclic movement according to ASTM C 719.

2. Sealant complies with ASTM C 920 for Type S, Grade NS, Class 50, Uses NT, G, A, and o, as applicable to substrates including other sealants with which it comes in contact.

3. Color: Black.

D. Flashing and Closure Sealant: Single-component, non-sag, high performance, non-priming, gun-grade elastomeric polyurethane sealant furnished by skylight manufacturer.

1. Sealant complies with ASTM C920, Type S, Grade NS, Class 25, Use T, NT, M, A, G, and O.

Canadian Specification CAN/CGSB-19.13-M87, Classification MCG-2-25-A-N.

2.…