Questions and Answers for FA3030-11-T-0049 Q1- What is the gross area of building (sq. ft.)?
A1- 519= 108,379sq ft & 523= 75,882sq ft Q2- Is the building multi-function, or critical space/data center operation only?
A2-Both 519 & 523 buildings are multi-functional, however, the electrical audit is only required for the critical area and the equipment only services the critical area.
Q3-Number and size(s) of UPS(s) serving the building (or critical space)?
A3-Please see the attached Maintenance Schedule for the number and size of all equipment including the UPS Q4- What are the quantities of cabinets?
A4-IT load cabinets for 519= 20 & 523= 60
Q5-What is the size of the generator serving the building?
A5-519= 300KW & 523= 750KW
Q6-SCOPE OF WORK: Does the Base have Items 4.b.i., ii. and iii, and will these documents and studies be available to WTA?
A6-See the attached on-line diagram for 4.b.i but ii, and iii are unavailable at this time.
Q7-Do current record drawings for the building exist and will these drawings be available to WTA?
A7-Current records do not exist