Delivery
1 ea. temp. controlled at JBSA- Lackland Building 7385 (delivery only during business hours 0700-1500)
1 ea temp. controlled at JBSA-Sam Houston Building 4060 (delivery only during business hours 0700-1500)
1 ea temp. controlled at JBSA-Randolph Building 37 (delivery only during business hours 0700-1500)
And 4 ea Chemical storage Conex Box at JBSA-Sam Houston Building 4060 (delivery only during business hours 0700-1500)
Salient Characteristics
(4) Chemical Storage Conex Boxes Nominal Ext. Dimensions 20'L X 6'W X 10'H Sump Capacity (Gal): 300 8P Swinging Door Set (Front and Rear Wall) 8P Upper Tier Secondary Containment 8P Galvanized Steel Grating, Per Tier
STANDARD FEATURES
- Exterior Wall Construction: Noncombustible steel sheets attached to corrosion-protected structural steel tubing for maximum durability and weather resistance.
- Roof/Ceiling: Noncombustible continuously welded steel sheets attached to structural steel tubing. Corrosion protected for maximum durability and weather resistance
- Sump Wall Construction: Noncombustible continuously welded sheet sheets for maximum spill containment Protection
- Upper Tier Secondary Containment, P-Series
- Base of Unit: Open channel construction providing visual Inspection.
- Swinging Doors - P-Series (Outward Swinging, Padlockable,
- Safety Chains (when optional doors are not ordered)
- Steel pallet loading supports (3 per pallet), corrosion-protected for maximum durability and weather resistance
- One (1) exterior static grounding connection
- Built-in 6-inch deep secondary containment sump on bottom level with chemical-resistant coating
- Interior & Exterior Primer Coat: high solids chemical-resistant epoxy (white semigloss)
- Interior & Exterior Finish: high solids gloss-white aliphatic Polyurethane
- Four (4) Hold-down Brackets
(3) Temperature controlled Chemical Storage Conex Boxes 8L x 8W x 9H "S" Series Storage Building 1 Door 60 In. W X 80 In. H Sump Capacity (Gal): 191-200 R 10 Insulation
502 CONS/JBKAA
JBSA Lackland, TX FA301620U0103 Chemical Storage Conex Boxes
Attachment 1 1 of 2
- 1.00 R10 Insulation, Double Door (Fire-Rated & Noncombustible Steel Models)
- 1.00 Load Center, Single Phase (Nema R); - UL Listed,208 /120 V or240 / 120 V, single-phase load center (NEMA R) with circuit breaker(s) and main breaker.
- 1.00 Air Conditioners (Class I, Division 2 Grp A-D), UL and cUL Listed,14,500 / 14,000
(BTU/hr), 230/ 208V
- 1.00 Heater (Convection, 7.6 kW,240 / 208 V,1 -Phase, 24,000 BTU/HR) (Explosion-
Proof) (Class I, Division 1 Groups C&D)
- 1.00 Exhaust Ventilation, Exterior Low Mount (Explosion Proof) (Class I, Division 1
Groups C&D) with Snap-Type Switch (Non Explosion-Proof)
- 1.00 Dry Chemical Fire Suppression System (Rated for Class A, B and C fires)
- 1.00 Interior Lighting ( 135 W Lamp) (Explosion-Proof) (Class I, Division 1 Groups C&D)
1 Fixture, 1 Switch
"S" Series STANDARD FEATURES:
- Exterior Wall Construction: Weatherproof unitized noncombustible steel construction
- Roof/Ceiling Construction: Weatherproof unitized noncombustible steel construction, same as exterior walls, Roof/ceiling assembly permanently attached to exterior walls.
- 60"W x 80"H, steel double door(s) located on front wall of building. Active door leaf
(36"W x 80"H) is equipped with an exterior UL Listed keyed security lock, and passive door (24"W x 80"H) is equipped with manually operated top and bottom UL Listed surface bolts. Both door leafs equipped with hold open door latches.
- Screened Air Vent(s): Air inlet vent(s) equipped with louvers and screens. The vent openings are arranged to provide air movement and prevent accumulation of hazardous vapors.
- Building Base: Open channel construction for forklift and/or crane slings and under building inspections.
- Internal Spill Containment Capacity: Minimum 30% of total storage Capacity
- Interior Finish: High solids, chemical-resistant epoxy undercoat with a heat reflective white aliphatic polyurethane topcoat.
- Exterior Finish: High solids, chemical-resistant epoxy undercoat with a heat reflective white aliphatic polyurethane topcoat.
- Four (4) Hold-down Brackets (structural steel angles) for bolting to purchaser's foundation for seismic and wind load anchoring.
- Static Grounding System: One (1) exterior grounding connection, one (1) 10-foot long
5/8" diameter copper-clad steel grounding rod, one (1) #4AWG copper conductor, and grounding lug(s).
- Signage: D.O.T. hazard classification placard with rust-proof aluminum holder & stainless steel clips; and pressure sensitive NFPA 704 Hazard Rating Sign(s)
502 CONS/JBKAA
JBSA Lackland, TX FA301620U0103 Chemical Storage Conex Boxes
Attachment 1 2 of 2