Response to questions (post amendment) 6 Aug 19
Contractor question: Will the government coordinate insuring the system is safe during installation (either rendering it temporarily inoperable or verifying with the OEM that work like the fan/light installation won’t accidently trigger the system)?
The Government can schedule an outtage with CE/FD to have the system temporarily turned off during the installation of the fans and lights. This must be coordinated atleast two weeks in advance of the contractor’s work. This allows all department to review and address any concerns.