Exhibit B - Logan Mingo HVAC Replacement-1.pdf
PDF 21 MB Posted
- Attached to
- Construction - Logan/ Mingo AFRC HVAC System Replacement State and local contract opportunity
- Solicitation number
- CRFQ 0603 ADJ2600000024 1
- Issued by
- Kanawha County, West Virginia
About this file
This document is an exhibit of technical specifications and equipment schedules for the West Virginia Army National Guard's Logan/Mingo AFRC HVAC Replacement project located in Logan, West Virginia. The project involves the complete removal and replacement of existing HVAC equipment and associated controls with a Variable Refrigerant Flow (VRF) system. The scope includes demolition of existing rooftop units, installation of new Mitsubishi and Trane equipment, electrical modifications, natural gas line connections, direct digital controls, air balance services, crane services, and comprehensive training. The equipment bill of materials specifies 62 remote controllers (TAR-43MAAUB), 7 outdoor units including three 168,000 BTU/H units (TURYE1684AMM0AN), three 120,000 BTU/H units (TURYE1204AMM0AN), and two 96,000 BTU/H units (TURYE0964AMM0AN), along with numerous indoor units of varying capacities ranging from 8,000 to 30,000 BTU/H in ceiling cassette and wall-mounted configurations. The contractor must coordinate a mandatory pre-bid site inspection and walk-through to analyze existing conditions and prepare accurate bids. Additional components include branch controllers, refrigerant piping materials in multiple sizes totaling over 1,800 linear feet, condensate pumps, ball valves, grilles, and snow/hail guards.
The contractor is responsible for all costs associated with permits, materials, labor, equipment, waste disposal, and site cleanup to produce a fully functional system. All work must comply with Federal, State, and Local regulations, State Fire Marshall requirements, and ATFP standards. The West Virginia Army National Guard reserves the right to retain selected removed equipment, which will be identified prior to work commencement. The successful contractor must provide an eight-hour on-site training session with owner's designated staff covering system operation and maintenance, submit a one-year warranty letter beginning at substantial completion, and deliver field notes and as-built drawings within 30 days of final acceptance. Contractor shall maintain progress meeting schedules on a bi-weekly basis with minutes provided within three business days. Access to the facility requires two business days' notice, and all contractor personnel must meet Army installation access and background check requirements. The owner allows 14 business days to review and respond to contract submittals and 7 business days for Requests for Information.
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| CRFQ ADJ26_24 Solicitation Documents.pdf | ||
| Final_CRFQ_0603_ADJ2600000024_1_WV_CRFQ_FORM.PDF |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WEST VIRGINIA ARMY NATIONAL GUARD
Logan / Mingo AFRC HVAC Replacement
Logan, West Virginia
Division 1 - General Requirements
00200 Instructions to Bidders
• Any and all contractual documents, information and procedures distributed by, or by any other means conveyed, by WV State Purchasing or the office of; supersedes the language in this document.
01100 Summary
Full HVAC and associated controls replacements.
GENERAL: Remove existing equipment and replace all equipment according to specifications. Please see the Bill of Materials for information on total number of units and associated materials required to complete the project. Please note that existing equipment’s electrical, natural gas lines and refrigerant lines may need to be modified to accommodate the new equipment. It is the contractor’s responsibility to make all modifications to ensure a fully functioning system.
SITE INSPECTION: A mandatory pre-bid meeting and walk-through shall be held. Contractors shall come prepared to fully analyze existing site conditions as required to prepare an accurate bid.
DEMOLITION REQUIREMENT: All units shall be disconnected from the electrical service, control connections, natural gas service, and any applicable ductwork and shall be removed from the roof and removed from the premises. All equipment, materials and refrigerant shall be disposed of in a manner consistent with all laws and ordinances governing such matters in this jurisdiction. Openings to the building shall be secured from weather penetration until such time as new units can be installed.
INSTALLATION OF NEW UNITS:
1. CURB ADAPTER – Provide new curb adapters that shall sit atop existing unit curb. Contractor shall coordinate required curb adapter based on consultation with equipment manufacturer. It is the contractor’s responsibility to ensure compatibility with the curb adapters and to make any necessary modifications to curbs and ductwork required for a fully functional system.
2. ELECTRICAL SERVICE – New Units shall utilize single circuit power connections from existing equipment.
Units shall have a disconnect and be fused in accordance with the manufacturer’s specifications. Existing units have “through the curb” electrical service. Contractor shall move conduit as necessary to supply new units. It is the contractor’s responsibility to provide all wiring, conduit, breakers, disconnects, fittings, etc. for necessary electrical service meeting the current edition of the National Electrical Code. Contractor to verify all existing unit voltages.
3. NATURAL GAS SERVICE – It shall be the contractor’s responsibility to connect existing natural gas service to the new equipment. Existing units have “through the curb natural gas service”. It is the contractor’s responsibility to move the gas line as necessary to connect back to the new equipment. The use of a pressure regulator shall be required as necessary in order to provide natural gas pressure in the range acceptable to the RTU manufacturer. Any and all new piping shall be included in this bid.
4. DIRECT DIGITAL CONTROLS- – Basis of Design is ASI Controls or equal for all units. A field-installed stand-alone direct digital controller shall be provided for the new equipment. Contractor shall also provide the owner with a licensed copy of any manufacturer’s proprietary programming software, all necessary cables and interface hardware as required to interface the system and make fundamental programming changes from owner’s laptop computer.
5. AIR BALANCE SERVICE – Contractor to employ the services of an independent, certified air balance company. Airflow for the new equipment (individual diffusers shall not be balanced) shall be set in accordance to manufacture’s specifications. Air balance contractor shall submit a written report of all settings and any deficiencies found.
6. CRANE SERVICE – Contractor is responsible for all crane services required for the project. Contractor shall coordinate the dates and times of onsite crane usage so that owner’s operations can be accordingly adjusted.
7. PROJECT CLOSEOUT REQUIREMENTS: Provide eight (8) hours on-site with owner’s designated staff for training on operation and maintenance requirements of the system. Provide letter stating that the warranty period will extend for a period of 1 year beginning at substantial completion date. Warranty letter shall disclose the warranty start and end dates and provide contact information of the installing contractor, the equipment supplier’s warranty and technical support departments, and the controls contractor.
8. NEW HVAC EQUIPMENT REQUIREMENTS: Basis of design is Trane and Mitsubishi or equal for all units.
Provided documentation within this document gives full details of all makes, models and quantities of equipment needed to complete the project. Please see documentation within this document for further details. Drawings of existing conditions can be provided upon request.
9. Due to design of controls and HVAC equipment, any contractor wishing to submit equivalents and seeking approval of their substitution, must do so during the question period for proper evaluation.
01300 Administrative Requirements
PROJECT COORDINATION
• Coordinate construction activities included in Contract Documents to assure efficient and orderly installation of each part of the Work.
• Where availability of space is limited, coordinate installation of different components to assure maximum accessibility for required maintenance, service, and repair.
• Where necessary prepare memoranda for distribution to each party involved outlining special procedures required for coordination. Include such items as required notices, reports, and attendance at meetings. Prepare similar memoranda for Owner and separate Contractors where coordination of their Work is required.
ADMINISTRATIVE PROCEDURES
• Coordinate scheduling and timing of required administrative procedures with other construction activities to avoid conflicts and ensure orderly progress of the Work. Such administrative activities include, but are not limited to:
• Preparing schedules.
• Delivering and processing submittals.
• Progress meetings.
• Project Close-out activities.
CONSERVATION
• Coordinate construction activities to ensure that operations are carried out with consideration given to conservation of energy, water, and materials.
PROGRESS MEETINGS
• Contractor will conduct progress meetings at site agreed upon by the Owner/Owner’s Representative at regularly scheduled intervals, generally bi-weekly.
• Progress meeting minutes are to be provided by the contractor within 3 business days of conclusion of the meeting. The meeting minutes shall be approved at the next meeting.
• The progress agenda shall include:
• Review and correct or approve minutes of previous progress meeting.
• Review and discuss old business
• Review and discuss new business
• Review and discuss contractor’s issues and concerns
• Review and discuss owner’s issues and concerns
• Review and discuss progress since last meeting.
• Review of where each activity is in relation to Contractor's Construction Schedule, whether on time or ahead or behind schedule, will be determined.
• Contractor to present a new updated schedule at each progress meeting; to include a two-week look ahead.
• Contractor shall provide meeting minutes of each progress meeting within three days after each progress meeting date. Contractor will distribute copies of minutes of meeting to the Owner.
GENERAL RESPONSIBILITIES
• The successful contractor is responsible for providing all parts, labor, equipment, and materials required to provide a finished fully functional product as described in the objectives.
• The contractor is responsible for the cost and obtaining of all required permits.
• The contactor is responsible to ensure all work is in compliance with all Federal, State, Local
Municipalities, State Fire Marshall and ATFP requirements.
• Contractor is responsible for all permits; the contractor shall obtain all required permits prior to initiation of any work. The contractor shall be responsible for the associated costs or permitting.
• Contractor is responsible for field verifying all distances and quantities of materials and components necessary for completion.
• The contractor is responsible for cleaning up the work site and repairing the site to original conditions once work is completed.
• Contractor responsible for keeping the work site clean daily, free from excess debris and safety hazards.
• Contractor responsible for providing waste disposal for the project; contractor is responsible for removing all construction waste debris off site at the contractor’s expense.
• All materials shall be submitted and approved by the WVARNG prior to installation.
• The West Virginia Army National Guard reserves the right to claim removed equipment from the project. A list of equipment to be retained will be provided to the contractor prior to beginning work. Contractor to make every effort to remove these items without damage.
• The contractor will provide a schedule of values broken down per line item with material and labor.
• Owner has 7 business days to review and respond to Requests For Information (RFI)s.
• Owner has 14 business days to review and respond to contract submittals.
• Owner has 14 business days to review and respond to review drawings.
SITE ACCESS REQUIREMENTS
• Access and general protection/security policy and procedures. This standard language is for contractor employees with an area of performance within Army controlled installation, facility, or area. Contractor and all associated sub-contractors employees shall provide all information required for background checks to meet installation access requirements.
• Contractor is responsible for coordinating with the Owner/Owner’s Representative, for access and deliveries. The Owner requires two (2) business days’ notice to approve access to the facility.
01400 Quality Requirements
• The successful contractor will be required to provide a one-year warranty on all parts, labor and materials on the entire project.
01500 Temporary Facilities and Controls
• Successful contractors will be required to provide their own temporary facilities. The West Virginia Army National Guard will provide an area for the contractor to have a lay down area, and a place for a job trailer.
• The West Virginia Army National Guard will make every effort to provide electricity and water for the contractor’s lay down and job trailer site; however, it is not guaranteed.
01700 Execution Requirements
• Within 30 days of the government Final Acceptance of the project; the contractor shall be responsible for providing all field notes, as-built drawings, or any other associated records to the Owner.
Division 2 - Site Construction
02073 PARTIAL DEMOLITION FOR REMODELING
GENERAL DEMOLITION
• Review, confirm and coordinate all demolition work and full extent of Owner's requirements prior to starting demolition work.
• Deliver salvageable materials requested by Owner.
• Perform all demolition in a manner acceptable to the Owner and regulatory agencies.
• Protect and maintain conduits, drains, sewers, pipes, and wires that are to remain on the property.
• Protect existing construction indicated to remain.
• Where existing construction is damaged by demolition operations, make repairs equal to or better than condition prior to start of demolition work.
CLEANING
• Promptly remove materials, rubbish, and debris from building and from property.
SALVAGEABLE MATERIALS
• Review with Owner at Preconstruction meeting about salvaged materials the Owner wishes to retain from building renovation project.
• Remove with care materials to be retained by Owner and store on site where directed for pickup by owner.
HANDLING
• Deliver materials and other components so they will not be damaged or deformed
• Exercise care in unloading, storing, and erecting materials to prevent bending, warping, twisting, and surface damage.
• Stack materials on platforms/pallets, covered with suitable weather tight ventilated covering.
WARRANTY
• Furnish manufacturer's written warranty covering materials installed. This warranty shall be in addition to and not a limitation of other rights the Owner may have against the Contractor under the Contract Documents.
PRODUCTS
• Will be in accordance with attached specifications
INSTALLATION
• General: Comply with manufacturers' instructions and recommendations for installation, as applicable to project.
Quantities Qty Model Description Tag
62 TAR-43MAAUB MA remote controller
CTR1-CC-1A1,CTR2-CC-1A2,CTR3-CC-1A3,CTR4-CC-
1A4,CTR5-CC-1A5A,CTR6-CC-1A6,CTR1-CC-
2A1,CTR2-CC-2A2,CTR3-CC-2A3,CTR4-CC-2A4,CTR5-
CC-2A5,CTR6-CC-2A6,CTR7-CC-2A7,CTR8-CC-
2A8,CTR9-CC-2A9,CTR10-CC-2A10,CTR11-CC-
2A11,CTR1-CC-3A1A,CTR2-CC-3A2A,CTR3-CC-
3A3A,CTR4-CC-3A1B,CTR5-CC-3A2B,CTR6-CC-
3A3B,CTR7-CC-3A4,CTR1-CC-1B1,CTR2-CC-
1B2,CTR3-CC-1B3,CTR4-CC-1B4,CTR5-CC-1B5,CTR6-
CC-1B6A,CTR7-CC-1B7,CTR8-CC-1B8,CTR9-CC-
1B9,CTR10-CC-1B10,CTR11-CC-1B11,CTR12-CC-
1B12,CTR13-CC-1B13,CTR14-CC-1B14,CTR15-CC-
1B15,CTR16-CC-1B16,CTR1-CC-2B1,CTR2-CC-
2B2,CTR3-CC-2B3,CTR4-CC-2B4,CTR5-CC-2B5,CTR6-
CC-2B6,CTR7-CC-2B7,CTR8-CC-2B8,CTR9-CC-
2B9,CTR10-CC-2B10,CTR11-CC-2B11,CTR1-DOAS-
1,CTR2-DOAS-3B2,CTR1-CC-1C1,CTR2-CC-1C2,CTR3-
CC-1C3,CTR4-CC-1C4,CTR5-CC-1C5,CTR6-CC-
1C6B,CTR7-CC-1C7,CTR8-CC-1C8,CTR9-CC-1C9
2 TURYE1684AMM0AN R32 R2 Series Outdoor Unit VRF-1A,VRF-1B 3 TURYE1204AMM0AN R32 R2 Series Outdoor Unit VRF-2A,VRF-2B,VRF-3B 2 TURYE0964AMM0AN R32 R2 Series Outdoor Unit VRF-3A,VRF-1C 3 CMB-M108NU-MA-SV BC Controller Main BC-1A,BC-3A,BC-1B1 3 CMB-M1012NU-MA-SV BC Controller Main BC-2A,BC-2B,BC-1C 1 CMB-M108NU-MB-SV BC Controller Sub BC-1B2 1 CMB-M104NU-MA-SV BC Controller Main BC-3B 1 CMY-R170M-E Joint Pipe VRF-3B 3 TPLFYP030EM1M0A Ceiling-Cassette (Four-Way) Indoor Unit CC-1A1,CC-1A2,CC-1A3
43 TPLFYP008FM1M0A Ceiling-Cassette (Four-Way) Indoor Unit
CC-1A4,CC-1A5A,CC-1A5B,CC-2A1,CC-2A2,CC-
2A3,CC-2A4,CC-2A5,CC-2A6,CC-2A7,CC-2A8,CC-
2A9,CC-2A11,CC-3A4,CC-1B1,CC-1B2,CC-1B3,CC-
1B5,CC-1B6A,CC-1B6B,CC-1B8,CC-1B9,CC-1B10,CC-
1B11,CC-1B12,CC-1B13,CC-1B14,CC-1B15,CC-2B1,CC-
2B2,CC-2B3,CC-2B5,CC-2B6,CC-2B7,CC-2B8,CC-
1C1,CC-1C2,CC-1C3,CC-1C4,CC-1C5,CC-1C7,CC-
1C8,CC-1C9
5 TPLFYP012FM1M0A Ceiling-Cassette (Four-Way) Indoor Unit CC-1A6,CC-3A2A,CC-3A3A,CC-3A2B,CC-3A3B 1 TPKFYP024KM1M0A Wall -Mounted Indoor Unit CC-2A10 3 TPLFYP018FM1M0A Ceiling-Cassette (Four-Way) Indoor Unit CC-3A1A,CC-3A1B,CC-2B4 2 TPLFYP024EM1M0A Ceiling-Cassette (Four-Way) Indoor Unit CC-1B4,CC-1B7 3 TPKFYP008LM1M0A Wall -Mounted Indoor Unit CC-1B16,CC-2B9,CC-2B10 1 TPKFYP018LM1M0A Wall -Mounted Indoor Unit CC-2B11 1 TPEFYP072MH1M0A Ceiling-Concealed (Ducted) Indoor Unit DOAS-1 1 TPEFYP048MH1M0A Ceiling-Concealed (Ducted) Indoor Unit DOAS-3B2 2 TPKFYP004LM1M0A Wall -Mounted Indoor Unit CC-1C6A,CC-1C6B 3 CMY-Y102SS-G2R1 Branch Joint ODU-A1,ODU-D1,ODU-G1 2 TE-C400A System Remote Controller CTR1,CTR2 1 LIC-BACNET-MASTER Software License 7 B9731-1-BF Bigfoot Stand XL Multi-Frame, 13 - 26" Tall 7 SGX-1 Side Snow/Hail Guards 2 SGX-2 Front and Rear Snow/Hail Guards 2 SHX-1 Snow Hood
51 BV14BBSI Ball Valve 1/4" BC-1A,BC-2A,BC-3A,BC-1B1,BC-1B2,BC-2B,BC-1C 51 BV12BBSI Ball Valve 1/2" BC-1A,BC-2A,BC-3A,BC-1B1,BC-1B2,BC-2B,BC-1C 12 BV38BBSI Ball Valve 3/8" BC-1A,BC-2A,BC-1B1,BC-3B,BC-1C 12 BV58BBSI Ball Valve 5/8" BC-1A,BC-2A,BC-1B1,BC-3B,BC-1C
8 COMBI Condensate Pump BC-1A,BC-2A,BC-3A,BC-1B1,BC-1B2,BC-2B,BC-3B,BC- 1C
5 SGX-3 Front and Rear Snow/Hail Guards 5 SHX-2 Snow Hood 5 TLP-41EAEU Grille with 3D i-see Sensor™ CC-1A1,CC-1A2,CC-1A3,CC-1B4,CC-1B7
51 TLP-18FAU Decoration Panel
CC-1A4,CC-1A5A,CC-1A5B,CC-1A6,CC-2A1,CC-
2A2,CC-2A3,CC-2A4,CC-2A5,CC-2A6,CC-2A7,CC-
2A8,CC-2A9,CC-2A11,CC-3A1A,CC-3A2A,CC-3A3A,CC-
3A1B,CC-3A2B,CC-3A3B,CC-3A4,CC-1B1,CC-1B2,CC-
1B3,CC-1B5,CC-1B6A,CC-1B6B,CC-1B8,CC-1B9,CC-
1B10,CC-1B11,CC-1B12,CC-1B13,CC-1B14,CC-
1B15,CC-2B1,CC-2B2,CC-2B3,CC-2B4,CC-2B5,CC-
2B6,CC-2B7,CC-2B8,CC-1C1,CC-1C2,CC-1C3,CC-
1C4,CC-1C5,CC-1C7,CC-1C8,CC-1C9
7 GOBI-II Wall Mount Unit Condensate Pump CC-2A10,CC-1B16,CC-2B9,CC-2B10,CC-2B11,CC-
1C6B,CC-1C6A
1 FBH4-4 Filter Box DOAS-1 1 FBH2-3 Filter Box DOAS-3B2
Refrigerant Piping Materials Pipe Size (inch) Total Length (feet) Number of Bends
3/8 151 26 5/8 143 24 1/4 661 114 1/2 661 114 7/8 100 16
1-1/8 125 20 3/4 158 26
Equipment Bill Of Material
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
TURYE1684AMM0AN
168,000 BTU/H HIGH EFFICIENCY HEAT RECOVERY OUTDOOR UNIT
Job Name:
System Reference: Date:
Specifications System Unit Type TURYE1684AMM0AN
Cooling Capacity (Nominal) Cooling Capacity (Nominal)1 Btu/h 168,000 Heating Capacity (Nominal) Heating Capacity (Nominal)2 Btu/h 188,000
Guaranteed Operating Range Cooling °F [ °C ] 23 ~ 125.60 [ -5 ~ 52 ] Heating °F [ °C ] -22 ~ 59.90 [ -30 ~ 15.50 ]
Extended Operating Range Heating °F [ °C ] -27.4 ~ 59.90 [ -33 ~ 15.50 ]
External Dimensions (H x W x D) In. [ mm] 70-13/16 x 47-15/16 x 29-7/16 [ 1,798 x 1,217 x 747 ]
Net Weight lbs [ kg ] 745 [ 338 ] External Finish MUNSELL 5Y 8/1 Electrical Power Requirements Voltage, Phase, Hertz, Power Tolerance 460 , 3 -phase, 60 Hz, ±10% Minimum Circuit Ampacity A 31 / 31 Maximum Overcurrent Protection A 50 / 50 Recommended Fuse Size A 35 / 35 Recommended Minimum Wire Size AWG [ mm] 8 / 8 [ 8.40 / 8.40 ] SCCR kA 5
Refrigerant Piping Diameter Liquid (High Pressure) In. [ mm ] Brazed 7/8 [ 22.23 ] Brazed Gas (Low Pressure) In. [ mm ] Brazed 1 1/8 [ 28.58 ] Brazed
Max. Total Refrigerant Line Length Ft. [ m ] 2,050 [ 625 ] Max. Refrigerant Line Length (Between ODU & IDU) Ft. [ m ] 541 [ 165 ] Max. Control Wiring Length Ft. [ m ] 3,280 [ 1,000 ]
Indoor Unit Connectable Total Capacity M252 Model/Quantity M04~M96 / 34
Sound Power Levels dB(A) / dB(A) 88.50 / 88.50
Fan
Type x Quantity Propeller fan x 2 Fan Motor Output kW 0.46 Airflow Rate CFM 10,593
External Static Pressure In. WG Selectable; 0.00, 0.12, 0.24, 0.32, In. WG; factory set to 0 In. WG
Compressor Operating Range 11%~100% Compressor Type x Quantity Scroll x 1 Refrigerant Type x Original Charge lbs , oz [ kg ] R32 x 13 , 15 [ 6.30 ]
Protection Devices High Pressure Protection High pressure switch,pressure sensor at 4.15MPa Inverter Circuit (Comp./Fan) overcurrent protection
AHRI Ratings (Ducted/Non-ducted)
EER 11.50 / 11.80
IEER 20.70 / 22.90
COP 3.48 / 3.77
SCHE 24.70 / 28.30
NOTES
1Nominal cooling conditions (Test conditions are based on AHRI 1230-2023) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2Nominal heating conditions (Test conditions are based on AHRI 1230-2023) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
Harsh weather environments may demand performance enhancing equipment. Ask your Mitsubishi Electric representative for more details about your region
For details on extended cooling operation range down to -10° F DB, see Low Ambient Kit Submittal
When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating
Unit will continue to operate in extended operating range, but capacity is not guaranteed
GENERAL FEATURES
• ASTM B117: Outdoor unit has passed ASTM B117 testing for 2,000hrs with additional coating on PCB and base panel
• DLC coating on Compressor sleeve: DLC (Diamond Like Carbon) coating has been added to the compressor sleeve for improved durability
• Improved Cooling Performance at High Ambient: Can maintain cooling capacity up to 109.4°F (43°C) through Dip Switch setting
• Vertical Flat Tube Heat Exchanger: Outdoor units are equipped with a new
3-way Vertical Flat Tube Heat Exchanger. This patented technology that improves efficiency and reduces refrigerant charge while also improving serviceability
• Improved Heating Operation Range: Heating Operating Range has been extended to -22°F (-30°C)
Submittal Documents
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
OUTDOOR UNIT ACCESSORIES: TURYE1684AMM0AN
Branch Pipe (Joint) Total down-stream Indoor capacity less than 72,000 Btu/h CMY-Y102SS-G2R1 Total down-stream Indoor capacity from 73,000 to 144,000 Btu/h CMY-Y102LS-G2R1
Control Wire M-Net Control Wire 1000 Roll 16-AWG Standard Twisted Pair Shielded Jacketed- Plenum rated CW162S-1000 M-Net Control Wire 250 Roll 16-AWG Standard Twisted Pair Shielded Jacketed- Plenum rated CW162S-250
Low Ambient Kit
Low Ambient Hood Assembly (main) with damper control box (Large Chassis) LAHX-3 Side Wind Deflector (Small, Large, and Extra Large Chassis) SWDX-1 Front/Rear Wind Deflector (2x required for the Large Chassis) WDX-2 (two pieces required)
Snow Guards
Snow Hood for Snow/Hail Protection (Large Chassis) SHX-1 Front and Rear Snow/Hail Guards (Large Chassis) SGX-2 Side Snow/Hail Guards (Small, Large, and Extra Large Chassis) SGX-1
Terminal Signal Adapter Connector and wire for Operation status/error using CN51 PAC-725AD 3-Pin Connector PAC-715AD
NOTES
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
METUS_2026-02_PROPIN Variable Refrigerant Flow (VRF) Multi-Split AC and HP AHRI Standard 1230
1340 Satellite Boulevard Suwanee, GA 30024 Toll Free: 800-433-4822 https://mitsubishicomfort.com
OUTDOOR UNIT DIMENSIONS: TURYE1684AMM0AN
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
TURYE1204AMM0AN
120,000 BTU/H HIGH EFFICIENCY HEAT RECOVERY OUTDOOR UNIT
Job Name:
System Reference: Date:
Specifications System Unit Type TURYE1204AMM0AN
Cooling Capacity (Nominal) Cooling Capacity (Nominal)1 Btu/h 120,000 Heating Capacity (Nominal) Heating Capacity (Nominal)2 Btu/h 135,000
Guaranteed Operating Range Cooling °F [ °C ] 23 ~ 125.60 [ -5 ~ 52 ] Heating °F [ °C ] -22 ~ 59.90 [ -30 ~ 15.50 ]
Extended Operating Range Heating °F [ °C ] -27.4 ~ 59.90 [ -33 ~ 15.50 ] External Dimensions (H x W x D) In. [ mm] 70-13/16 x 36-1/4 x 29-7/16 [ 1,798 x 920 x 747 ] Net Weight lbs [ kg ] 637 [ 289 ] External Finish MUNSELL 5Y 8/1 Electrical Power Requirements Voltage, Phase, Hertz, Power Tolerance 460 , 3 -phase, 60 Hz, ±10% Minimum Circuit Ampacity A 27 / 27 Maximum Overcurrent Protection A 45 / 45 Recommended Fuse Size A 30 / 30 Recommended Minimum Wire Size AWG [ mm] 10 / 10 [ 5.30 / 5.30 ] SCCR kA 5
Refrigerant Piping Diameter Liquid (High Pressure) In. [ mm ] Brazed 3/4 [ 19.05 ] Brazed Gas (Low Pressure) In. [ mm ] Brazed 1 1/8 [ 28.58 ] Brazed
Max. Total Refrigerant Line Length Ft. [ m ] 1,886 [ 575 ] Max. Refrigerant Line Length (Between ODU & IDU) Ft. [ m ] 541 [ 165 ] Max. Control Wiring Length Ft. [ m ] 3,280 [ 1,000 ]
Indoor Unit Connectable Total Capacity M180 Model/Quantity M04~M96 / 24
Sound Power Levels dB(A) / dB(A) 83.50 / 83.50
Fan
Type x Quantity Propeller fan x 1 Fan Motor Output kW 0.92 Airflow Rate CFM 7,062
External Static Pressure In. WG Selectable; 0.00, 0.12, 0.24, 0.32, In. WG; factory set to 0 In. WG
Compressor Operating Range 13%~100% Compressor Type x Quantity Scroll x 1 Refrigerant Type x Original Charge lbs , oz [ kg ] R32 x 11 , 11 [ 5.30 ]
Protection Devices High Pressure Protection High pressure switch,pressure sensor at 4.15MPa Inverter Circuit (Comp./Fan) overcurrent protection
AHRI Ratings (Ducted/Non-ducted)
EER 12.70 / 13.30
IEER 23.10 / 24.10
COP 3.73 / 4.08
SCHE 25.30 / 29.10
NOTES
1Nominal cooling conditions (Test conditions are based on AHRI 1230-2023) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2Nominal heating conditions (Test conditions are based on AHRI 1230-2023) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
Harsh weather environments may demand performance enhancing equipment. Ask your Mitsubishi Electric representative for more details about your region
For details on extended cooling operation range down to -10° F DB, see Low Ambient Kit Submittal
When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating
• ASTM B117: Outdoor unit has passed ASTM B117 testing for 2,000hrs with additional coating on PCB and base panel
• DLC coating on Compressor sleeve: DLC (Diamond Like Carbon) coating has been added to the compressor sleeve for improved durability
• Improved Cooling Performance at High Ambient: Can maintain cooling capacity up to 109.4°F (43°C) through Dip Switch setting
• Vertical Flat Tube Heat Exchanger: Outdoor units are equipped with a new
3-way Vertical Flat Tube Heat Exchanger. This patented technology that improves efficiency and reduces refrigerant charge while also improving serviceability
• Improved Heating Operation Range: Heating Operating Range has been extended to -22°F (-30°C)
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
OUTDOOR UNIT ACCESSORIES: TURYE1204AMM0AN
Branch Pipe (Joint) Total down-stream Indoor capacity less than 72,000 Btu/h CMY-Y102SS-G2R1 Total down-stream Indoor capacity from 73,000 to 144,000 Btu/h CMY-Y102LS-G2R1
Control Wire M-Net Control Wire 250 Roll 16-AWG Standard Twisted Pair Shielded Jacketed- Plenum rated CW162S-250 M-Net Control Wire 1000 Roll 16-AWG Standard Twisted Pair Shielded Jacketed- Plenum rated CW162S-1000
Low Ambient Kit
Side Wind Deflector (Small, Large, and Extra Large Chassis) SWDX-1 Front/Rear Wind Deflector (1x required for Small Chassis, 2x required for the Extra Large Chassis) WDX-1 Low Ambient Hood Assembly (main) with damper control box (Small Chassis) LAHX-1
Snow Guards
Front and Rear Snow/Hail Guards (Small and Extra Large Chassis) SGX-3 Side Snow/Hail Guards (Small, Large, and Extra Large Chassis) SGX-1 Snow Hood for Snow/Hail Protection (Small and Extra Large Chassis) SHX-2
Terminal Signal Adapter Connector and wire for Operation status/error using CN51 PAC-725AD 3-Pin Connector PAC-715AD
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
AHRI Standard 1230
1340 Satellite Boulevard Suwanee, GA 30024 Toll Free: 800-433-4822 https://mitsubishicomfort.com
OUTDOOR UNIT DIMENSIONS: TURYE1204AMM0AN
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
TURYE0964AMM0AN
96,000 BTU/H HIGH EFFICIENCY HEAT PUMP OUTDOOR UNIT
Job Name:
System Reference: Date:
Specifications System Unit Type TURYE0964AMM0AN
Cooling Capacity (Nominal) Cooling Capacity (Nominal)1 Btu/h 96,000 Heating Capacity (Nominal) Heating Capacity (Nominal)2 Btu/h 108,000
Guaranteed Operating Range Cooling °F [ °C ] 23 ~ 125.60 [ -5 ~ 52 ] Heating °F [ °C ] -22 ~ 59.90 [ -30 ~ 15.50 ]
Extended Operating Range Heating °F [ °C ] -27.4 ~ 59.90 [ -33 ~ 15.50 ] External Dimensions (H x W x D) In. [ mm] 70-13/16 x 36-1/4 x 29-7/16 [ 1,798 x 920 x 747 ] Net Weight lbs [ kg ] 633 [ 287 ] External Finish MUNSELL 5Y 8/1 Electrical Power Requirements Voltage, Phase, Hertz, Power Tolerance 460 , 3 -phase, 60 Hz, ±10% Minimum Circuit Ampacity A 22 / 22 Maximum Overcurrent Protection A 35 / 35 Recommended Fuse Size A 25 / 25 Recommended Minimum Wire Size AWG [ mm] 10 / 10 [ 5.30 / 5.30 ] SCCR kA 5
Refrigerant Piping Diameter Liquid (High Pressure) In. [ mm ] Brazed 3/4 [ 19.05 ] Brazed Gas (Low Pressure) In. [ mm ] Brazed 7/8 [ 22.23 ] Brazed
Max. Total Refrigerant Line Length Ft. [ m ] 1,886 [ 575 ] Max. Refrigerant Line Length (Between ODU & IDU) Ft. [ m ] 541 [ 165 ] Max. Control Wiring Length Ft. [ m ] 3,280 [ 1,000 ]
Indoor Unit Connectable Total Capacity M144 Model/Quantity M04~M96 / 19
Sound Power Levels dB(A) / dB(A) 80 / 80
Fan
Type x Quantity Propeller fan x 1 Fan Motor Output kW 0.92 Airflow Rate CFM 6,532
External Static Pressure In. WG Selectable; 0.00, 0.12, 0.24, 0.32, In. WG; factory set to 0 In. WG
Compressor Operating Range 13%~100% Compressor Type x Quantity Scroll x 1 Refrigerant Type x Original Charge lbs , oz [ kg ] R32 x 11 , 11 [ 5.30 ]
Protection Devices High Pressure Protection High pressure switch,pressure sensor at 4.15MPa Inverter Circuit (Comp./Fan) overcurrent protection
AHRI Ratings (Ducted/Non-ducted)
EER 13.50 / 14.60
IEER 23.20 / 26.70
COP 3.97 / 4.43
SCHE 23.50 / 28.30
NOTES
1Nominal cooling conditions (Test conditions are based on AHRI 1230-2023) Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2Nominal heating conditions (Test conditions are based on AHRI 1230-2023) Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
Harsh weather environments may demand performance enhancing equipment. Ask your Mitsubishi Electric representative for more details about your region
For details on extended cooling operation range down to -10° F DB, see Low Ambient Kit Submittal
When applying product below -4°F, consult your design engineer for cold climate application best practices, including the use of a backup source for heating
• ASTM B117: Outdoor unit has passed ASTM B117 testing for 2,000hrs with additional coating on PCB and base panel
• DLC coating on Compressor sleeve: DLC (Diamond Like Carbon) coating has been added to the compressor sleeve for improved durability
• Improved Cooling Performance at High Ambient: Can maintain cooling capacity up to 109.4°F (43°C) through Dip Switch setting
• Improved Heating Operation Range: Heating Operating Range has been extended to -22°F (-30°C)
• Vertical Flat Tube Heat Exchanger: Outdoor units are equipped with a new
3-way Vertical Flat Tube Heat Exchanger. This patented technology that improves efficiency and reduces refrigerant charge while also improving serviceability
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
OUTDOOR UNIT ACCESSORIES: TURYE0964AMM0AN
Branch Pipe (Joint) Total down-stream Indoor capacity from 73,000 to 144,000 Btu/h CMY-Y102LS-G2R1 Total down-stream Indoor capacity less than 72,000 Btu/h CMY-Y102SS-G2R1
Control Wire M-Net Control Wire 1000 Roll 16-AWG Standard Twisted Pair Shielded Jacketed- Plenum rated CW162S-1000 M-Net Control Wire 250 Roll 16-AWG Standard Twisted Pair Shielded Jacketed- Plenum rated CW162S-250
Low Ambient Kit
Side Wind Deflector (Small, Large, and Extra Large Chassis) SWDX-1 Front/Rear Wind Deflector (1x required for Small Chassis, 2x required for the Extra Large Chassis) WDX-1 Low Ambient Hood Assembly (main) with damper control box (Small Chassis) LAHX-1
Snow Guards
Front and Rear Snow/Hail Guards (Small and Extra Large Chassis) SGX-3 Snow Hood for Snow/Hail Protection (Small and Extra Large Chassis) SHX-2 Side Snow/Hail Guards (Small, Large, and Extra Large Chassis) SGX-1
Terminal Signal Adapter Connector and wire for Operation status/error using CN51 PAC-725AD 3-Pin Connector PAC-715AD
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
AHRI Standard 1230
1340 Satellite Boulevard Suwanee, GA 30024 Toll Free: 800-433-4822 https://mitsubishicomfort.com
OUTDOOR UNIT DIMENSIONS: TURYE0964AMM0AN
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
CMB-M108NU-MA-SV
8 BCBRANCH BC CONTROLLER
Job Name:
System Reference: Date:
Specifications System Unit Type CMB-M108NU-MA-SV
Indoor Unit Capacity Connectable to 1 Branch M54 Number Of Branches 8 Connectable Outdoor / Heat Source Unit Capacity M72 to M384
Electrical
Voltage, Phase, Frequency V AC , ø , Hz 208 / 230 , 1 , 60 Power Input Cooling (208/230V) kW 0.02 / 0.02 Power Input Heating (208/230V) kW 0.01 / 0.01 Current Input Cooling (208/230V) A 0.09 / 0.10 Current Input Heating (208/230V) A 0.06 / 0.06
MCA A 0.13
MOCP A 15
Indoor Unit External Finish Color Galvanized Steel Unit Dimensions (W x D x H) inch [ mm ] 41 x 38 4/16 x 9 15/16 [ 1,040 x 970 x 252 ] Unit Weight lbs [ kg ] 139 [ 63 ]
Refrigerant Type R32 Sound Pressure Level (Measured in anechoic room) Defrost dB (A) 56
Piping Drain Pipe Size O.D. inch 3/4 NPT
NOTES
1The equipment is for use with R32 refrigerant only.
2When possible, avoid installing the BC controller within 15 Ft. of sound sensitive areas.
3Rated operation sound data is based on cooling mode. Sound data may vary depending on outdoor unit capacity and operation mode.
4Sound pressure/power levels obtained via testing in an anechoic chamber. Actual sound pressure levels may be greater due to ambient noise and/or deflection.
5Sound pressure values were obtained at a test location approximately 5 Ft. from the unit.
6The unit is intended for installation in an indoor environment only.
7For details regarding installation specifics, please refer to the product’s Installation Manual.
| • | Simultaneous Operation : Provides simultaneous heating and cooling |
| • | Single BC Functionality : Main BC Controllers can be used on their own, or |
in combination with Sub BC Controllers
• Outdoor Unit Flexibility : Can be paired with Air Source or Water Source outdoor units
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
INDOOR UNIT ACCESSORIES: CMB-M108NU-MA-SV
Ball Valve
Ball Valve (5/8” SAE Brazed) BV58BBSI Ball Valve (1/4” SAE Brazed) BV14BBSI Ball Valve (3/8” SAE Brazed) BV38BBSI Ball Valve (1/2” SAE Brazed) BV12BBSI
Branch Pipe (Joint)
Total down-stream Indoor capacity less than 72,000 Btu/h CMY-Y102SS-G2R1 Total down-stream Indoor capacity from 73,000 to 144,000 Btu/h CMY-Y102LS-G2R1 Total down-stream Indoor capacity from 145,000 to 240,000 Btu/h CMY-Y202S-G2R1
Condensate
Blue Diamond MaxiBlue Condensate Pump with Reservoir Sensor 115-230V up to 48k BTU/h X88-721 Blue Diamond MicroBlue Condensate Pump 115-230V up to 18k BTU/h X86-003 Refco Condensate Pump 100-240V up to 120k BTU/h COMBI Sauermann Condensate Pump 120-230V up to 60k BTU/h SI30-230
Control Wire M-Net Control Wire - 250 Foot Roll CW162S-250 M-Net Control Wire - 1,000 Foot Roll CW162S-1000
Cover Plug Cover Plug PAC-KA01PS-E
Joint and Reducer
Between Main BC controller and Sub BC controller for total down-stream indoor unit capacity 127,000 to 216,000 Btu/h CMY-R202S-G Between Main BC controller and Sub BC controller for total down-stream indoor unit capacity 235,000 to 360,000 Btu/h CMY-R204S-G Between Main BC controller and Sub BC controller for total down-stream indoor unit capacity 217,000 to 234,000 Btu/h CMY-R203S-G Between Main BC controller and Sub BC controller for total down-stream indoor unit capacity less than 126,000 Btu/h CMY-R201S-G Between Main BC controller and Sub BC controller for total down-stream indoor unit capacity greater than 361,000 Btu/h CMY-R205S-G
Port Adaptor Joint Pipe Adapter CMY-R170M-E
Reducer
Between outdoor units and BC controller for MA type (Outdoor unit capacity: M72-M336) CMY-R302S-G1 Between Main BC controller and Sub BC controller for MA and MB type CMY-R306S-G Between Main BC controller and Sub BC controller for MA and MB type (When using the Sub BC controller) CMY-R303S-G1 Between outdoor units and BC controller for MA type (Outdoor unit capacity: M72-M120) CMY-R301S-G Between outdoor units and BC controller for MA type (Outdoor unit capacity: M72-M432) CMY-R304S-G1 Between Main BC controller and Sub BC controller for MA and MB type (When using the Sub BC controller) CMY-R305S-G1
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
METUS_2025-09_PROPIN
1340 Satellite Boulevard Suwanee, GA 30024 Toll Free: 800-433-4822 https://mitsubishicomfort.com
INDOOR UNIT DIMENSIONS: CMB-M108NU-MA-SV
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
TPLFYP030EM1M0A
30,000 BTU/H CEILING CASSETTE INDOOR UNIT
Job Name:
System Reference: Date:
Specifications System Unit Type TPLFYP030EM1M0A
Cooling Capacity (Nominal)1 Cooling Capacity (Nominal) Btu/h 30,000 Heating Capacity (Nominal)1 Heating Capacity (Nominal) Btu/h 34,000
Electrical
Voltage, Phase, Frequency V AC , ø , Hz 208 / 230 , 1 , 60 Power Consumption Cooling kW 0.04 Power Consumption Heating kW 0.04 Current Cooling A 0.45 Current Heating A 0.40
MCA A 0.56
MOCP A 15
Recommended Fuse Size A 15
Indoor Unit
External Finish Color Galvanized Steel MUNSELL ( 1.0Y 9.2/0.2 ) Unit Dimensions (W x D x H) inch [ mm ] 33-3/32 x 33-3/32 x 11-3/4 [ 840 x 840 x 298 ] Unit Weight lbs [ kg ] 57 [ 26 ] Heat Exchanger Cross fin (Aluminum fin and Copper Tube) Dual Barrier Coating on HEX No
Refrigerant Type R-32 / R-454B
Fan
Type x Quantity Turbo fan x 1 Motor Type DC Motor Motor Output W 120 Motor FLA A 0.45 Airflow Rate CFM 636 , 706 , 777 , 812
Sound Pressure Level (Measured in anechoic room) dB (A) 28 , 31 , 33 , 35
Piping Liquid Pipe Size O.D. inch [ mm ] 3/8 [ 9.52 ] Gas Pipe Size O.D. inch [ mm ] 5/8 [ 15.88 ] Drain Pipe Size O.D. inch [ mm ] 1-1/4 [ 32 ]
NOTES
• *1. Cooling / Heating capacity indicated at operation under the following conditions:
• Cooling: Indoor 81°F (27°C) DB / 68°F (19°C) WB; Outdoor 95°F (35°C) DB
• Heating: Indoor 68°F (20°C) DB; Outdoor 45°F (7°C) DB / 43°F (6°C) WB
• Auto Vane Control : Auto Vane Control allows the indoor unit vanes to be moved left, right, up, and down to provide even temperatures throughout a space.
• Condensate Life Mechanism : A built-in condensate lift mechanism removes water that is collected during operation and reduces the need for an additional pump to remove condensate water.
• Dual Compatible Refrigerant : Indoor unit is dual compatible with both R-32 and R-454B
• Dual Set Point : The controller can be used to program two different set points. The unit will automatically adjust between the set points for optimum comfort.
• Dual Vane : Dual-Vane feature allows for airflow direction to be set independently using two vanes, which can then deliver airflow across wide areas of a room, levels of a zone, or to two people in different locations at the same time.
• Four Speed Fan : Adjust the fan between four speed settings to optimal comfort.
• Leak Detection Sensor Built-in : Dual Compatible (R32/R454B) Refrigerant Leak Sensor built-in
• Swing Mode : An indoor unit with this capability can move air throughout the room like an oscillating fan.
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
INDOOR UNIT ACCESSORIES: TPLFYP030EM1M0A
3D Flow 3D Total Flow Unit PLP-U160ELR-E
Alarm Kit Power supply interface for Alarm Kit PAC-IF55AL-E Alarm kit PAC-SL54AL-E
Casement Multi-function casement PAC-SJ41TM-E
Condensate
Sauermann Condensate Pump 120-230V up to 60k BTU/h SI30-230 Blue Diamond MegaBlue Condensate Pump with Reservoir Sensor 115-230V up to 170k BTU/h X87-835 Blue Diamond Sensor Extension Cable 15 Ft C13-103 Refco Condensate Pump 100-240V up to 120k BTU/h COMBI Blue Diamond MaxiBlue Condensate Pump with Reservoir Sensor 115-230V up to 48k BTU/h X88-721 Blue Diamond MultiTank collection tank for use with MegaBlue C21-014
Control Interface
Thermostat Interface PAC-US446CN-1 kumo station® for Comfort app PAC-WHS01HC-E Procon BACnet® and Modbus® Interface PAC-UKPRC001-CN-1 IT Extender PAC-WHS01IE-E Wireless Interface 2 for Comfrot app PAC-USWHS002-WF-2
Control Wire
MA Control Wire - 1,000 Feet CW222-1000 MA Control Wire - 250Feet CW222-250 M-Net Control Wire - 1,000 Foot Roll CW162S-1000 M-Net Control Wire - 250 Foot Roll CW162S-250
Filter High efficiency filter element (requires PAC-SJ41TM-E) PAC-SH59KF-E
Grille Grille (3D i-See sensor panel) (required) PLP-41EAEU (one piece required)
Lineset
3/8 x 5/8 Lineset Twin-Tube Insulation - 10 feet MPLS385812T-10 3/8 x 5/8 Lineset Twin-Tube Insulation - 65 feet MPLS385812T-65 3/8 x 5/8 Lineset Twin-Tube Insulation - 15 feet MPLS385812T-15 3/8 x 5/8 Lineset Twin-Tube Insulation - 50 feet MPLS385812T-50 3/8 x 5/8 Lineset Twin-Tube Insulation - 100 feet MPLS385812T-100 3/8 x 5/8 Lineset Twin-Tube Insulation - 30 feet MPLS385812T-30
Remote Sensor
Wall Mount Remote Temperature Sensor PAC-SE42TS-E Flush Mount Remote Temperature Sensor PAC-USSEN002-FM-2 Wireless temperature and humidity sensor for Comfort app PAC-USWHS003-TH-1
Shutter Plate Air outlet shutter plate PAC-SJ37SP-E
Terminal Signal Adapter
Connector and wire for On/Off and Error status using CN51 and CN52 PAC-725AD Backup Heat Relay Kit CN24RELAY-KIT-CM3 Connector and wire for On/Off and Fan command using CN32 PAC-715AD
Wired Remote Controller
Deluxe MA Remote Controller PAR-43MAAUB Simple Direct Wired Remote Controller PAC-SDW01RC-2 Smart ME Remote Controller PAR-U01MEDU-K Simple MA Remote Controller PAC-YT53CRAU-J Touch MA Remote Controller PAR-CT01MAU-SB
Wireless Remote Controller
Wireless MA Handheld Remote Controller (requires PAR-FA32MA-E) PAR-FL32MA-E Wireless RedLINK™ Remote Controller MHK2 Wireless Universal Handheld Remote Controller (requires PAR-SA9CA-E) PAR-SL101A-E Wireless MA Signal Receiver (for PAR-FL32MA-E) PAR-FA32MA Wireless signal receiver (corner panel) (for PAR-SL101A-E / PAR-FL32MA) PAR-SR4LU-E
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
1340 Satellite Boulevard Suwanee, GA 30024 Toll Free: 800-433-4822 https://mitsubishicomfort.com
① ②
ΦΦΦ
ΦΦ
ΦΦΦ
ΦΦ
ΦΦΦ
ΦΦ
ΦΦΦ
ΦΦ
φφ
ΦΦΦ
ΦΦΦ
INDOOR UNIT DIMENSIONS: TPLFYP030EM1M0A
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
TPLFYP008FM1M0A
8,000 BTU/H CEILING CASSETTE INDOOR UNIT
Job Name:
System Reference: Date:
Specifications System Unit Type TPLFYP008FM1M0A
Cooling Capacity (Nominal)1 Cooling Capacity (Nominal) Btu/h 8,000 Heating Capacity (Nominal)1 Heating Capacity (Nominal) Btu/h 9,000
Electrical
Voltage, Phase, Frequency V AC , ø , Hz 208 / 230 , 1 , 60 Power Consumption Cooling kW 0.02 Power Consumption Heating kW 0.02 Current Cooling A 0.22 Current Heating A 0.17
MCA A 0.28
MOCP A 15
Recommended Fuse Size A 15
Indoor Unit
External Finish Color Galvanized Steel MUNSELL ( 1.0Y 9.2/0.2 ) Unit Dimensions (W x D x H) inch [ mm ] 22-1/2 x 22-1/2 x 8-1/4 [ 570 x 570 x 208 ] Unit Weight lbs [ kg ] 29 [ 13.10 ] Heat Exchanger Cross fin (Aluminum fin and Copper Tube) Dual Barrier Coating on HEX No
Refrigerant Type R-32 / R-454B
Fan
Type x Quantity Turbo fan x 1 Motor Type DC Motor Motor Output W 50 Motor FLA A 0.29 Airflow Rate CFM 230 , 280 , 315
Sound Pressure Level (Measured in anechoic room) dB (A) 26 , 30 , 33
Piping Liquid Pipe Size O.D. inch [ mm ] 1/4 [ 6.35 ] Gas Pipe Size O.D. inch [ mm ] 1/2 [ 12.72 ] Drain Pipe Size O.D. inch [ mm ] 1-1/4 [ 32 ]
NOTES
• *1. Cooling / Heating capacity indicated at operation under the following conditions:
• Auto Vane Control : Auto Vane Control allows the indoor unit vanes to be moved left, right, up, and down to provide even temperatures throughout a space.
• Condensate Life Mechanism : A built-in condensate lift mechanism removes water that is collected during operation and reduces the need for an additional pump to remove condensate water.
• Dual Compatible Refrigerant : Indoor unit is dual compatible with both R-32 and R-454B
• Dual Set Point : The controller can be used to program two different set points. The unit will automatically adjust between the set points for optimum comfort.
• Dual Vane : Dual-Vane feature allows for airflow direction to be set independently using two vanes, which can then deliver airflow across wide areas of a room, levels of a zone, or to two people in different locations at the same time.
• Leak Detection Sensor Built-in : Dual Compatible (R32/R454B) Refrigerant Leak Sensor built-in
• Ventilation Air Intake: A duct opening is provided, which allows outside air to be brought inside so it can be heated or cooled.
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
INDOOR UNIT ACCESSORIES: TPLFYP008FM1M0A
Alarm Kit Alarm kit PAC-SL54AL-E Power supply interface for Alarm Kit PAC-IF55AL-E
Condensate
Blue Diamond MaxiBlue Condensate Pump with Reservoir Sensor 115-230V up to 48k BTU/h X88-721 Blue Diamond MicroBlue Condensate Pump 115-230V up to 18k BTU/h X86-003 Refco Condensate Pump 100-240V up to 120k BTU/h COMBI Sauermann Condensate Pump 120-230V up to 60k BTU/h SI30-230
Control Interface
Wireless Interface 2 for Comfrot app PAC-USWHS002-WF-2 IT Extender PAC-WHS01IE-E kumo station® for Comfort app PAC-WHS01HC-E Procon BACnet® and Modbus® Interface PAC-UKPRC001-CN-1 Thermostat Interface PAC-US446CN-1
Control Wire
MA Control Wire - 1,000 Feet CW222-1000 M-Net Control Wire - 1,000 Foot Roll CW162S-1000 MA Control Wire - 250Feet CW222-250 M-Net Control Wire - 250 Foot Roll CW162S-250
Grille Grille (Decoration panel) (required) SLP-18FAU (one piece required) Grille (3D i-see Sensor panel) SLP-18FAEU
Lineset
1/4 x 1/2 Lineset Twin-Tube Insulation - 15 feet MLS141212T-15 1/4 x 1/2 Lineset Twin-Tube Insulation - 30 feet MLS141212T-30 1/4 x 1/2 Lineset Twin-Tube Insulation - 50 feet MLS141212T-50 1/4 x 1/2 Lineset Twin-Tube Insulation - 100 feet MLS141212T-100 1/4 x 1/2 Lineset Twin-Tube Insulation - 65 feet MLS141212T-65
Remote Sensor
Flush Mount Remote Temperature Sensor PAC-USSEN002-FM-2 Wall Mount Remote Temperature Sensor PAC-SE42TS-E Wireless temperature and humidity sensor for Comfort app PAC-USWHS003-TH-1
Terminal Signal Adapter
Connector and wire for On/Off and Error status using CN51 and CN52 PAC-725AD Connector and wire for On/Off and Fan command using CN32 PAC-715AD Backup Heat Relay Kit CN24RELAY-KIT-CM3
Wired Remote Controller
Simple Direct Wired Remote Controller PAC-SDW01RC-2 Smart ME Remote Controller PAR-U01MEDU-K Touch MA Remote Controller PAR-CT01MAU-SB Deluxe MA Remote Controller PAR-43MAAUB Simple MA Remote Controller PAC-YT53CRAU-J
Wireless Remote Controller
Wireless MA Signal Receiver (for PAR-FL32MA-E) PAR-FA32MA Wireless signal receiver (corner panel) (For PAR-SL101A-E / PAR-FL32MA) PAR-SF9FA-E Wireless RedLINK™ Remote Controller MHK2 Wireless Universal Handheld Remote Controller (requires PAR-SA9CA-E) PAR-SL101A-E Wireless MA Handheld Remote Controller (requires PAR-FA32MA-E) PAR-FL32MA-E i-see Sensor® Panel 3D i-see sensor corner panel PAC-SF1ME-E
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
1340 Satellite Boulevard Suwanee, GA 30024 Toll Free: 800-433-4822 https://mitsubishicomfort.com
INDOOR UNIT DIMENSIONS: TPLFYP008FM1M0A
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
TPLFYP012FM1M0A
12,000 BTU/H CEILING CASSETTE INDOOR UNIT
Job Name:
System Reference: Date:
Specifications System Unit Type TPLFYP012FM1M0A
Cooling Capacity (Nominal)1 Cooling Capacity (Nominal) Btu/h 12,000 Heating Capacity (Nominal)1 Heating Capacity (Nominal) Btu/h 13,500
Electrical
Voltage, Phase, Frequency V AC , ø , Hz 208 / 230 , 1 , 60 Power Consumption Cooling kW 0.02 Power Consumption Heating kW 0.02 Current Cooling A 0.23 Current Heating A 0.18
MCA A 0.29
MOCP A 15
Recommended Fuse Size A 15
Indoor Unit
External Finish Color Galvanized Steel MUNSELL ( 1.0Y 9.2/0.2 ) Unit Dimensions (W x D x H) inch [ mm ] 22-1/2 x 22-1/2 x 8-1/4 [ 570 x 570 x 208 ] Unit Weight lbs [ kg ] 31 [ 14.20 ] Heat Exchanger Cross fin (Aluminum fin and Copper Tube) Dual Barrier Coating on HEX No
Refrigerant Type R-32 / R-454B
Fan
Type x Quantity Turbo fan x 1 Motor Type DC Motor Motor Output W 50 Motor FLA A 0.29 Airflow Rate CFM 245 , 280 , 335
Sound Pressure Level (Measured in anechoic room) dB (A) 26 , 30 , 34
Piping Liquid Pipe Size O.D. inch [ mm ] 1/4 [ 6.35 ] Gas Pipe Size O.D. inch [ mm ] 1/2 [ 12.72 ] Drain Pipe Size O.D. inch [ mm ] 1-1/4 [ 32 ]
NOTES
• *1. Cooling / Heating capacity indicated at operation under the following conditions:
• Auto Vane Control : Auto Vane Control allows the indoor unit vanes to be moved left, right, up, and down to provide even temperatures throughout a space.
• Condensate Life Mechanism : A built-in condensate lift mechanism removes water that is collected during operation and reduces the need for an additional pump to remove condensate water.
• Dual Compatible Refrigerant : Indoor unit is dual compatible with both R-32 and R-454B
• Dual Set Point : The controller can be used to program two different set points. The unit will automatically adjust between the set points for optimum comfort.
• Dual Vane : Dual-Vane feature allows for airflow direction to be set independently using two vanes, which can then deliver airflow across wide areas of a room, levels of a zone, or to two people in different locations at the same time.
• Leak Detection Sensor Built-in : Dual Compatible (R32/R454B) Refrigerant Leak Sensor built-in
• Ventilation Air Intake: A duct opening is provided, which allows outside air
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
INDOOR UNIT ACCESSORIES: TPLFYP012FM1M0A
Alarm Kit Power supply interface for Alarm Kit PAC-IF55AL-E Alarm kit PAC-SL54AL-E
Condensate
Blue Diamond MaxiBlue Condensate Pump with Reservoir Sensor 115-230V up to 48k BTU/h X88-721 Sauermann Condensate Pump 120-230V up to 60k BTU/h SI30-230 Blue Diamond MicroBlue Condensate Pump 115-230V up to 18k BTU/h X86-003 Refco Condensate Pump 100-240V up to 120k BTU/h COMBI
Control Interface kumo station® for Comfort app PAC-WHS01HC-E Wireless Interface 2 for Comfrot app PAC-USWHS002-WF-2 Thermostat Interface PAC-US446CN-1 Procon BACnet® and Modbus® Interface PAC-UKPRC001-CN-1 IT Extender PAC-WHS01IE-E
Control Wire
MA Control Wire - 1,000 Feet CW222-1000 MA Control Wire - 250Feet CW222-250 M-Net Control Wire - 250 Foot Roll CW162S-250 M-Net Control Wire - 1,000 Foot Roll CW162S-1000
Grille Grille (Decoration panel) (required) SLP-18FAU (one piece required) Grille (3D i-see Sensor panel) SLP-18FAEU
Lineset
1/4 x 1/2 Lineset Twin-Tube Insulation - 100 feet MLS141212T-100 1/4 x 1/2 Lineset Twin-Tube Insulation - 15 feet MLS141212T-15 1/4 x 1/2 Lineset Twin-Tube Insulation - 65 feet MLS141212T-65 1/4 x 1/2 Lineset Twin-Tube Insulation - 50 feet MLS141212T-50 1/4 x 1/2 Lineset…