Electrical Plans.pdf
PDF 851 KB Posted
- Attached to
- 472/17433. JAG-Central MI CF-Generator Bldg. Improvements State and local contract opportunity
- Solicitation number
- RFQ 171 190000000608 3
- Issued by
- Gogebic County, Michigan
About this file
This is an electrical plans document prepared for the State of Michigan Department of Technology, Management and Budget, specifically for the Central Michigan Correctional Facility Generator Building Replacement project. The plans were developed by Matrix Consulting Engineers, Inc. and include detailed electrical symbols, abbreviations, site plans, and one-line diagrams for the generator building replacement work. The project involves installation of a new 24'x28' carport, a 1000kVA pad-mounted transformer, temporary generator connections during construction, new LED lighting fixtures, and associated electrical infrastructure modifications at the West Maintenance Building and West Administration Building. The design underwent a 50% design review on May 15, 2019, a 90% design review on June 3, 2019, with bid documents issued on July 29, 2019. The electrical work includes demolition of existing equipment, installation of new circuits and conduit, relocation of light fixtures, and reconnection of the existing 500kW generator to the automatic transfer switch (ATS) upon completion of the enclosure.
The plans specify that the Division 26 electrical contractor must conduct a site visit to determine the exact extent of demolition work required before submitting a bid. Key requirements include sealing all wall and floor penetrations to maintain original ratings, routing all conduits along existing piping and structural steel, removing obsolete exposed conduit and equipment, patching damaged surfaces to match adjacent areas, and field verification of all equipment voltages and loads prior to service installation. The contractor is responsible for patching walls behind surface-mounted equipment and must report any discrepancies between the drawings and field conditions to the engineer for clarification. Asbestos removal, if present, will be handled separately by the owner. The project utilizes existing conduit where possible and requires coordination between electrical work and other trades during the construction and temporary generator phase.
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| Specifications.pdf | ||
| Advertisment.pdf | ||
| Architectural Plans.pdf | ||
| Addendum 1 17433.pdf | ||
| Civil Plans.pdf | ||
| CAJ-1037 DOC LEIN Request REV 04-2018.pdf | ||
| Bid Addendum 2.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
X
X
X
TVSS
VFD
TRANSIENT VOLTAGE SURGE SUPPRESSION
VARIABLE FREQUENCY DRIVEDUPLEX RECEPTACLE
DOCK LIGHT FIXTURE
TELEPHONE / DATA OUTLET
ADDENDUM NOTE
PLAN NOTE
DEMOLITION NOTE
THREE PHASE MOTOR
ELECTRICAL SYMBOLS LEGEND
J
SINGLE RECEPTACLE (120 VOLT)
EMERGENCY RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
FLUSH FLOOR BOX
SURFACE FLOOR BOX
SPECIAL EQUIPMENT RECEPTACLE
TELEPHONE OUTLET
DATA OUTLET
POWER POLE
JUNCTION BOX
WALL JUNCTION BOX
PULL (JUNCTION) BOX
UNDERFLOOR JUNCTION BOX
OUTLETS
LIGHT FIXTURE
STRIP FIXTURE
IN-GRADE LIGHT FIXTURE
SPOTLIGHT (number of heads shown) EXIT SIGN (face & direction as shown)
WALL MOUNT LIGHT FIXTURE
CEILING LIGHT FIXTURE
TRACK & FIXTURE
STREET TYPE POLE FIXTURE
POLE MOUNTED LIGHT FIXTURE
EXTERIOR WALL MOUNT LIGHT FIXTURE
WALLPACK LIGHT FIXTURE
SPECIAL PURPOSE LIGHT FIXTURE
HIGH BAY LIGHT FIXTURE
EMERGENCY EGRESS LIGHT FIXTURE
(number of heads shown)
EMERGENCY LIGHT FIXTURE
FIXTURES
SWITCHES
SINGLE-POLE SWITCH
DIMMER SWITCH
TIME SWITCH
KEY SWITCH
MANUAL MOTOR SWITCH
THERMAL OVERLOAD SWITCH
SWITCH WITH PILOT LIGHT
FOUR-WAY SWITCH
THREE-WAY SWITCH
CIRCUITRY and RACEWAYS
UNDERFLOOR DUCT
BUS DUCT
PLUGMOLD AS SPECIFIED
WIREMOLD AS SPECIFIED
FLEXIBLE PIGTAILS/CONNECTIONS
"CONDUIT RUN CONTINUES" INDICATION
END OF CONDUIT RUN, CAP AND STAKE
END OF CONDUIT RUN
HOME RUN (with circuit numbers)
CONDUIT STUB DOWN
CONDUIT STUB UP
CONDUIT INSTALLED
CONDUIT INSTALLED
MECHANICAL
ELECTRIC WATER HEATER
ELECTRIC UNIT HEATER
PIPE TRACE HEATER
RESISTANCE HEATER, KW SHOWN
SINGLE PHASE MOTOR
SERVICE and EQUIPMENT
THERMOSTAT
CAPACITOR
ENCLOSED CIRCUIT BREAKER
TRANSFER SWITCH
WIREWAY
GROUND CONNECTION PER N.E.C.
TELEPHONE TERMINAL BOARD
GENERATOR, KW SHOWN
CURRENT TRANSFORMERS
UTILITY METER, AS REQUIRED
WEATHERHEAD
PANELBOARD, FLUSH MOUNTED
PANELBOARD, SURFACE MOUNTED
COMB. STARTER (BY x/C U.O.N.)
MAGNETIC STARTER (BY x/C U.O.N.)
DISCONNECT SWITCH (fuse size shown)
TRANSFORMER
CONTROL
xxVA connection by x/C) IRRIGATION CONTROLLER (120 volt
LIGHTING CONTACTOR
CONTROL TRANSFORMER
buttons indicated) PUSHBUTTON STATION (number of TIME CLOCK (24 hour U.O.N.)
PHOTOCELL (voltage as required)
HUMIDISTAT
DESIGNATIONS
(by E.C.)
(by others)
TT
G
WW
PC
CT
TS
T
H
TC
IC
T
1,3
OR
PM
WM
BD
UFD
F S
J
J
D
WH
PP
J
SENSOR SWITCH WSD-PDT SERIES
SWITCH STYLE OCCUPANCY SENSOR
OC
WATT STOPPER TS-400
DIGITAL TIME SWITCH
SENSOR SWITCH MP20 SERIES
POWER PACK
SENSOR SWITCH CMR-PDT SERIES
ULTRASONIC SENSOR - 360° - 500 SQ FT
SENSOR SWITCH CMR-PDT-10
ULTRASONIC SENSOR - 360° - 1000 SQ FT
SENSOR SWITCH CMR-PDT-10-2P
ULTRASONIC SENSOR - 360° - 2 CIRCUIT
SENSOR SWITCH CMR-PC-ADC SERIES
OCCUPANCY SENSOR / PHOTOCELL
SENSOR SWITCH WV-PDT-16 SERIES
WALL MOUNT DUAL TECHNOLOGY SENSOR
OS5
OS4
T
OS2
OS3
OS1
PP
CEILING MOUNTED WIFI
POLE
PUMP
PANEL
P
PNL
PVC
PRV-
P-
PB
POLY VINYL CLORIDE
POWER ROOF VENTILATOR
PULL BOX
GENERAL CONTRACTOR
GROUND
HUMIDIFIERH-
GND
GFI
GC
GROUND FAULT INTERUPTER
ABBREVIATIONS LEGEND
POWER
SWITCH
RECEPT
SF-
SWBD
TCC
SPEC
SW
RGC
RTU-
PWR
VOLTS
WATTS
UF
V
W
UL
VL
UNO
UH-
TS
TYP
TR
ROOF TOP UNIT
RECEPTACLE
SWITCHBOARD
UNDER FLOOR
SPECIFICATIONS
RIGID GALVANIZED STEEL CONDUIT
UNLESS NOTED OTHERWISE
UNDERWRITERS' LABORATORIES, INC.
TAMPER PROOF RECEPTACLE
TAMPER PROOF SWITCH
TEMPERATURE CONTROL CONTRACTOR
VERIFY LOCATION WITH OWNER
TYPICAL
UNIT HEATER
SUPPLY FAN
WITH
WITHOUT
W/
XFMR
W/O
WP
TRANSFORMER
WEATHER PROOF
HOUR
LIGHT
JUNCTION BOX
LIGHT CONTROL
ISOLATED GROUND
HORSEPOWER
MINIMUM
MOUNT
MAKE-UP AIR UNIT
MOTOR CONTROL CENTER
MAIN LUG ONLY
MOUNTED
MOUNTING
MAXIMUM
LIGHTING
LT FLEX
MTD
MUAU-
MTG
MLO
MIN
MT
MC
MAX
MCC
LTG
IG
LC
LT
IMC
JB
HR
HVAC
HOA
HP
NORMALLY CLOSED
NOT IN CONTRACT
NORMALLY OPEN
NOT TO SCALE
NIGHT LIGHTNL
NTS
NO
NIC
NC
HAND-OFF-AUTO SELECTOR SWITCH
HEATING/VENTILATING/AIR CONDITIONING
INTERMEDIATE METAL CONDUIT
LIQUID TIGHT FLEXIBLE METAL CONDUIT
MECHANICAL CONTRACTOR
HID HIGH INTENSITY DISCHARGE
A
AC
AFF
ACU-
AHJ
AHU-
AS
B-
BC
AIC
ATS
BLDG
CHLR-
CND (C)
CKT BKR
CKT
CUH-
CU-
DISC
DFU-
EF-
EC
DWH-
EBB-
DWG
CT-
EXIST (E)
EWC
FLEX
FLA
FLR
FSES
FLUOR
EMT
ABOVE FINISHED FLOOR
AIR CONDITIONING UNIT
AMPS
ABOVE COUNTER
AIR HANDLING UNIT
AUTOMATIC TRANSFER SWITCH
AMPS INTERUPTING CAPACITY
AUTHORITY HAVING JURISDICTION
ABOVE SHELF
BOILER
BUILDING
BELOW COUNTER
CHILLER
DOMESTIC WATER HEATER
CABINET UNIT HEATER
CIRCUIT
CIRCUIT BREAKER
CONDUIT
CONDENSING UNIT
COOLING TOWER
DUCT FURNACE
DRAWING
DISCONNECT
FOOD SERVICE EQUIP. SUPPLIER
ELECTRIC WATER COOLER
ELECTRICAL CONTRACTOR
ELECTRIC BASEBOARD
ELECTRICAL METALLIC TUBING
EXISTING
EXHAUST FAN
FLOOR
FLUORESCENT
FLEXIBLE CONDUIT
FULL LOAD AMPS
EM EMERGENCY
F/S FIRE/SMOKE
FU- FURNACE
1. ALL WALL AND FLOOR PENETRATIONS ARE TO BE SEALED TO MAINTAIN ORIGINAL
RATING.
2. ALL CONDUITS TO BE FIELD ROUTED ALONG EXISTING PIPING AND STRUCTURAL
STEEL.
3. THE DIVISION 26 CONTRACTORS SHALL VISIT THE PROJECT AND DETERMINE THE
EXACT EXTENT OF THE DEMOLITION WORK REQUIRED BEFORE BIDDING THE PROJECT.
4. REMOVE ALL EXISTING OBSOLETE EXPOSED CONDUIT, WIRE AND UNUSED EQUIPMENT
WHERE WORK IS BEING DONE EXCEPT ITEMS NOTED OTHERWISE.
5. WHERE BUILDING SURFACES ARE DAMAGED BY THE REMOVAL OF OLD WORK,
SURFACES SHALL BE PATCHED TO MATCH ADJACENT.
6. EXISTING WORK WHICH IS PRESENTLY CONCEALED AND WHICH WILL REMAIN
CONCEALED AND DOES NOT INTERFERE WITH ANY NEW WORK OF ANY TRADE NEED
NOT BE REMOVED. HOWEVER, ALL CONDUIT SHALL BE CAPPED BELOW FINISH
SURFACE AND THEN PATCHED TO MATCH, OR AS NOTED.
7. EXISTING OPENINGS, WHICH ARE TO BE REUSED, SHALL BE MODIFIED OR ENLARGED
TO SUIT THE NEW SYSTEMS AS REQUIRED. PROVIDE ALL REQUIRED CUTTING AND
PATCHING.
8. IF ASBESTOS IS PRESENT, IT WILL BE REMOVED OR RENDERED HARMLESS UNDER
SEPARATE CONTRACT BY THE OWNER.
9. THE DIVISION 26 CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING THE EXISTING
WALLS TO MATCH THE ADJACENT SURFACES BEHIND ALL SURFACE MOUNTED
EQUIPMENT.
10. CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT VOLTAGES AND LOADS PRIOR TO
INSTALLING SERVICE TO EQUIPMENT.
11. DRAWINGS ARE BASED ON EXISTING RECORD DOCUMENT AND CASUAL FIELD
OBSERVATION. REPORT ANY DISCREPANCIES TO ENGINEER FOR CLARIFICATION.
GENERAL ELECTRICAL NOTES
JC
/E
N G
B Y
PR
O
JE
C
T N
O
IN
D
EX
PC
A
D R
AW
N
B Y
D
ES
IG
N
ED
B
Y
-0
PR
O
JE
C
T D
ES
C
R
IP
TI
O
N
C
EN
TR
AL
M
IC
H
IG
AN
C
O R
R
EC
TI
O
N
AL
F
AC
IL
IT
Y
P
LU
R I
B U
E S
U N
U M
C I
R C
U M
S P
I C
E
S I
Q U
E R
E I
S P
E N
I N
S U
L A
M A
M
OE
N A
M
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
R O
B E
R T
C
H A
L L
R
A
N C
A R
B
D
IR
E C
T O
R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
G
EN
ER
AT
O R
B U
IL
D
IN
G
R
EP
LA
C
EM
EN
T
1/
9.
JA
G
R ev ie w
D
AT
E
M A
T R
I X
D
ES
IG
N
R
EV
IE
W
/1
5/
D
ES
IG
N
R
EV
IE
W
/0
3/
BI
D
D O
C U
M
EN
TS
/2 9/
E-
SY
M
BO
LS
, A
BB
R
EV
IA
TI
O N
S
AN
D N
O
TE
S
BT
F
BT
F
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text K
AutoCAD SHX Text P
AutoCAD SHX Text S
AutoCAD SHX Text
TO
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text M
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text
CONSULTING ENGINEERS, INC
AutoCAD SHX Text
FAX: (517) 487-2544
AutoCAD SHX Text
PHONE: (517) 487-2511
AutoCAD SHX Text
LANSING, MI 48906
AutoCAD SHX Text
1601 E. CEASAR CHAVEZ AVE.
AutoCAD SHX Text administrator@matrixceinc.com
AutoCAD SHX Text Matrix Project No. 19073.00
GENERATOR
3 TO SALLY PORT
PANEL "SP"
PHOTOCELL
TO TEMPORARY
GENERATOR
TO 1000KVA
TRANSFORMER
(E) (E)
TO UPS
XFMR
FIBER RACK
EM ATS
SLT
MA T
E-MDP
MDP
SITE
1000kVA
PAD MTD TRANFORMER
PRIMARY
SWITCH UNIT
WEST MAINTENANCE BUILDING
WEST
ADMINISTRATION
BUILDING
ELECT
ROOM
PANEL "AA"
(LOCATED IN
MECHANICAL ROOM)
E-2
E-2
E-2
ELECTRICAL KEY NOTES
PROVIDE TEMPORARY GENERATOR. FIELD VERIFY EXACT
LOCATION. REFER TO ONE LINE DIAGRAM ON SHEET E-6 FOR
ADDITIONAL INFORMATION.
ROUTE CIRCUITS FOR CARPORT LIGHTING AND
RECEPTACLES AROUND THE BUILDING AS SHOWN. STUB UP
SIDE OF BUILDING UP TO ATTIC LOCATION OF PANEL AA.
GFI
GFI
PHOTOCELL
AA-13
AA-15
AA-13
(TYP)
GENERATOR
TO SALLY PORT
PANEL "SP"
PHOTOCELL
TO 1000KVA
TRANSFORMER
(E) (E)
TO UPS
XFMR
FIBER RACK
EM ATS
SLT
MA T
E-MDP
MDP
SITE
ELECTRICAL KEY NOTES
NEW 24'x28' CARPORT. REFER TO CIVIL DRAWINGS FOR
EXACT LOCATION AND ADDITIONAL INFORMATION.
NEW 120V, VAPOR-TIGHT, LED LIGHT FIXTURE. LITHONIA
PART #:XVML-L48-3500LM-MVOLT-50K-80CRI.
CONNECT NEW CIRCUIT TO A SPARE 20A-1P BREAKER IN
PANEL "AA".
DISCONNECT & REMOVE EXISTING GENERATOR.
DISCONNECT, REMOVE, & RELOCATE EXISTING LIGHT FIXTURES.
REFER TO NEW WORK OF NEW LOCATION.
DISCONNECT, REMOVE, AND REPLACE EXISTING WIRES. REUSE
CONDUIT IF POSSIBLE.
DISCONNECT AND REMOVE EXISTING CONNECTION FROM ATS
TO GENERATOR. CONNECT ATS TO TEMPORARY GENERATOR.
REMOVE ONE EXISTING BUILDING BLOCK FOR INSTALLATION OF
TEMPORARY CABLES TO ATS. PLUG HOLE DURING
CONSTRUCTION, AND REPLACE BLOCK AT COMPLETION OF
PROJECT.
DISCONNECT AND REMOVED ABANDONED ELECTRICAL DEVICE
AND ALL ASSOCIATED CONDUIT AND WIRING.
DEMOLITION NOTES
RE-INSTALL EXISTING GENERATOR TO SAME
LOCATION AND PAD AFTER ENCLOSURE IS
COMPLETED.
RELOCATED LIGHT FIXTURE. CONNECT TO
EXISTING LIGHTING CIRCUIT.
RECONNECT ALL DEVICES ASSOCIATED WITH
EXISTING GENERATOR.
PROVIDE NEW CONDUIT AND JUNCTION
BOXES TO RECONNECT FIBER RACK.
KEY NOTES
JC
/E
N G
B Y
PR
O
JE
C
T N
O
IN
D
EX
PC
A
D R
AW
N
B Y
D
ES
IG
N
ED
B
Y
-0
PR
O
JE
C
T D
ES
C
R
IP
TI
O
N
C
EN
TR
AL
M
IC
H
IG
AN
C
O R
R
EC
TI
O
N
AL
F
AC
IL
IT
Y
P
LU
R I
BU
E
S U
N U M
C I
R C
U M
S P
I C
E
S I
Q U
E R
E I
S P
E N
I N
S U
L A
M A
M
OE
N A
M
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
R O
B E
R T
C H
A L
L R
A N
C A
R B
D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
G
EN
ER
AT
O R
B U
IL
D
IN
G
R
EP
LA
C
EM
EN
T
1/
9.
JA
G
R ev ie w
D
AT
E
M A
T R
I X
D
ES
IG
N
R
EV
IE
W
/1
5/
D
ES
IG
N
R
EV
IE
W
/0
3/
BI
D
D O
C U
M
EN
TS
/2 9/
E-
EL
EC
TR
IC
AL
SI
TE
P
LA
N D
EM
O
A N
D N
EW
BT
F
BT
F
N ELECTRICAL
SITE PLAN - WEST
SCALE: 1/32" =1'-0"
01 5 20 40 75
N 3 ENLARGED CARPORT - NEW
SCALE:1/8"=1'-0"
N 1 ENLARGED MAINTENANCE BUILDING - NEW
SCALE:1/8"=1'-0"
N 2 ENLARGED MAINTENANCE BUILDING - DEMO
SCALE:1/8"=1'-0"
AutoCAD SHX Text
CONSULTING ENGINEERS, INC
AutoCAD SHX Text
FAX: (517) 487-2544
AutoCAD SHX Text
PHONE: (517) 487-2511
AutoCAD SHX Text
LANSING, MI 48906
AutoCAD SHX Text
1601 E. CEASAR CHAVEZ AVE.
AutoCAD SHX Text administrator@matrixceinc.com
DISCONNECT & REMOVE EXISTING GENERATOR,
REMOVE WIRING BACK TO ATS.
CONNECT TEMPORARY GENERATOR TO ATS,
DISCONNECT AND REMOVE AFTER EXISTING
GENERATOR IS BACK IN PLACE AND ENERGIZED.
CONNECT TO A SPARE 20A,1P CIRCUIT IN
EXISTING PANEL MA.
DEMOLITION NOTES
SSTB MB MR EM
T
SL EMDP
MDP
T
MA
G
GENERATOR
EXISTING 500KW
75kVA 112.5kVA
G
GENERATOR
TEMPORARY
ONE LINE DIAGRAM - DEMO
ELECTRICAL KEY NOTES
REINSTALL AND RECONNECT EXISTING GENERATOR TO ATS
AND ALL ASSOCIATED DEVICES. REUSE EXISTING CONDUIT
AND WIRING IF NOT DAMAGED DURING CONSTRUCTION.
SSTB MB MR EM
T
SL EMDP
MDP
T
MA
G
GENERATOR
EXISTING 500KW
75kVA 112.5kVA
ONE LINE DIAGRAM - NEW
1000kVA
PAD MOUNTED
TRANSFORMER
T
1000kVA
PAD MOUNTED
TRANSFORMER
T
ATS
ATS
TO PANEL MA
(GEN START)
TO PANEL
(BLOCK HEATER)
TO PANEL
(BATTERY CHARGER)
JC
/E
N G
B Y
PR
O
JE
C
T N
O
IN
D
EX
PC
A
D R
AW
N
B Y
D
ES
IG
N
ED
B
Y
-0
PR
O
JE
C
T D
ES
C
R
IP
TI
O
N
C
EN
TR
AL
M
IC
H
IG
AN
C
O R
R
EC
TI
O
N
AL
F
AC
IL
IT
Y
P
LU
R I
BU
E
S U
N U M
C I
R C
U M
S P
I C
E
S I
Q U
E R
E I
S P
E N
I N
S U
L A
M A
M
OE
N A
M
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
R O
B E
R T
C H
A L
L R
A N
C A
R B
D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
G
EN
ER
AT
O R
B U
IL
D
IN
G
R
EP
LA
C
EM
EN
T
1/
9.
JA
G
R ev ie w
D
AT
E
M A
T R
I X
D
ES
IG
N
R
EV
IE
W
/1
5/
D
ES
IG
N
R
EV
IE
W
/0
3/
BI
D
D O
C U
M
EN
TS
/2 9/
E-
O N
E
LI
N E
D
IA
G R
AM
BT
F
BT
F
AutoCAD SHX Text
CONSULTING ENGINEERS, INC
AutoCAD SHX Text
FAX: (517) 487-2544
AutoCAD SHX Text
PHONE: (517) 487-2511
AutoCAD SHX Text
LANSING, MI 48906
AutoCAD SHX Text
1601 E. CEASAR CHAVEZ AVE.
AutoCAD SHX Text administrator@matrixceinc.com
| E-1-1907300-24x36 |
| E-2-1907300-24x36 |
| E-6-1907300-24x36 |