Electrical One Line Diagram and Panel Schedule 03_EP-102-EP-102.pdf

PDF 177 KB Posted

Attached to
Y1DA--632-21-122 – Electrical Power Upgrade Federal contract opportunity
Solicitation number
36C24222B0033
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--632-21-122 – Electrical Power Upgrade, newest first.
File Type Posted
Site Visit Sign-in Sheet - Electrical Power Upgrade.pdf PDF
36C24222B0033 0001.docx DOCX document
36C24222B0033_1.docx DOCX document
Electrical Power Plan.pdf PDF
Electrical General Notes and Symbols 01_EG-001-EG-001.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NEW PANEL

VOLTAGE (L-N): ENCLOSURE TYPE: NEMA 1

VOLTAGE (L-L): MOUNTING: RECESSED

PHASES, WIRES: 3PH, 4W AIC RATING (A):

200 A

CKT NO DESCRIPTION WIRE (AWG) TRIP

AMPS POLE

PHASE LOADS (VA)

POLE TRIP

AMPS

WIRE (AWG) DESCRIPTION CKT NO

A B C

43 44 45 400 400 46 47 1 400 400 48 49 400 400 50

51 400 400 1 20 EXIST WIREMOLD C1-76K (SEC1-20) 52

53 400 400 54

CONNECTED LOAD PHASE TOTALS (VA)

23922 22841 21862

CONNECTED LOAD

(VA) DEMAND FACTOR DEMAND LOAD (VA)

UPS EQUIPMENTS 20300

TOTAL: 73424 52275

LOAD (AMPS): 203.8 145.1

FEEDER: 4-3/0+#4G-2"C FROM EXISTING PANEL 'CLB-DD'

2#12+#12G-3/4"C

29000

CL1-D4

22000

MINIMUM BUS CAPACITY (AMPS): NOTES:

MAIN O.C. DEVICE (AMPS): 175 A

400 400

70%

55 400 1000 56 57 1 400 400 1 20 58 59 400 400 60

SPACE 1

SPACE 1

- 400

SPACE 1

- 400

79 - 800 80 81 - 600 82 83 - 300 84

- 400

1 20

1 20 1 20

1 20

EXIST RECEP C1-76J,K (SEC1-22)2#12+#12G-3/4"C

2#12+#12G-3/4"C

61 400 400 62 63 400 400 1 20 64 65 1000 400 66

67 1000 400 68 69 1 1000 400 1 20 70 71 - 400 72

1 20

1 20 1 20

1 20

20 1

2#12+#12G-3/4"C

SPARE - 20

SPARE

SPARE

SPACE

1 1500 1000 2

NEMA L6-30R IN COL A 30 2

1500 1000 4

5 1500 1000 6 7 1500 1000 8 9 1500 1000 10 11 1500 1000 12 13 1000 1000 14 15 1000 1000 16 17 1000 1000 18 19 1000 1000 20 21 22 23 1000 1000 24 25 1000 - 26 27 -

2 20 NEMA L6-20R COL C

29 - - 30 31 - 32 33 34 35 - - 36 37 2918 5404 38

39 AIR COMPRESSOR 40 3 2918 4323 3 100 EXIST PANEL 'CL1-D3A' 40

41 2918 5044 42

2#10+#10G-3/4"C

4#2+#8G-1-1/2"C

2#12+#12G-3/4"C

3#8+#8G-3/4"C

NEMA L6-30R IN COL B 30 22#10+#10G-3/4"C

NEMA L6-30R IN COL D 30 22#10+#10G-3/4"C

NEMA L6-20R IN COL A 20 22#12+#12G-3/4"C

NEMA L6-20R IN COL A 20 22#12+#12G-3/4"C

NEMA L6-20R IN COL A 20 22#12+#12G-3/4"C

NEMA L6-20R IN COL A 20 22#12+#12-3/4"C

SPACE - 2-

SPACE - 2-

2 20 NEMA L6-20R COL C2#12+#12G-3/4"C

2 20 NEMA L6-20R COL C2#12+#12G-3/4"C

2 20 NEMA L6-20R COL D2#12+#12G-3/4"C

2 20 NEMA L6-20R COL D2#12+#12G-3/4"C

2 20 NEMA L6-20R COL E2#12+#12G-3/4"C

2 20 SPARE-

2 20

2 20

SPARE-

SPARE-

DUPLEX RECEP COL C 15 12#12+#12G-3/4"C

DEPLEX RECEP COL A 20 12#12+#12G-3/4"C

DUPLEX RECEP COL C 152#12+#12G-3/4"C

DUPLEX RECEP COL C 152#12+#12G-3/4"C

DUPLEX RECEP COL C 152#12+#12G-3/4"C

DUPLEX RECEP COL C 152#12+#12G-3/4"C

DUPLEX RECEP COL C 152#12+#12G-3/4"C

DUPLEX RECEP COL D 152#12+#12G-3/4"C

DUPLEX RECEP COL D 152#12+#12G-3/4"C

DUPLEX RECEP COL E

REMISOL WORK STATION COL F

EXIST WIREMOLD FREEZER (SEC2-4)

2#12+#12G-3/4"C

EXIST WIREMOLD C1-76J (SEC1-18)2#12+#12G-3/4"C

1 20 EXIST WIREMOLD C1-76E,F,G (SEC1-19)2#12+#12G-3/4"C

1 20

1 20 EXIST RECEP C1-76E,F,G (SEC1-21)2#12+#12G-3/4"C

EXIST WIREMOLD C1-76E,F,G (SEC1-17)2#12+#12G-3/4"C

EXIST WIREMOLD C1-76H,M (SEC1-27)

EXIST WIREMOLD C1-76H,M (SEC1-29)

EXIST RECEP C1-76H,M (SEC1-31)

EXIST WIREMOLD C1-76L (SEC1-23)

EXIST WIREMOLD C1-76L (SEC1-25)

EXIST RECEP C1-76N,O (SEC1-24)

EXIST RECEP C1-76N,O (SEC1-26)

EXIST RECEP C1-76N (SEC1-42)

EXIST GFI RECEP C1-76L (SEC2-17)

EXIST RECEP C1-76N (SEC2-2)

EXIST RECEP C1-76L (SEC2-13)

EXIST RECEP C1-76M (SEC2-15)

EXIST RECEP WAX MACHINE (SEC1-41)

EXIST RECEP HAND WASH (SEC1-34)

EXIST LAB LTS (SEC1-36)

2#12+#12G-3/4"C 2#12+#12G-3/4"C 2#12+#12G-3/4"C 2#12+#12G-3/4"C 2#12+#12G-3/4"C 2#12+#12G-3/4"C 2#12+#12G-3/4"C 2#12+#12G-3/4"C 2#12+#12G-3/4"C 2#12+#12G-3/4"C 2#12+#12G-3/4"C 2#12+#12G-3/4"C 2#12+#12G-3/4"C 2#12+#12G-3/4"C

2#12+#12G-3/4"C

EXIST WIREMOLD FREEZER (SEC2-6) 2#12+#12G-3/4"C

EXIST WIREMOLD FREEZER (SEC2-8) 2#12+#12G-3/4"C

AIR COMPRESSOR 87548754 100%

RECEPTACLES LOAD 845016900 50%

PANEL 'CL1-D3A' 1477114770 100%

PIPE BASEMENT

ELECTRICAL RISER DIAGRAM

N.T.S.

LEGEND:

EXISTING CONDUIT & WIRING OR EQUIPMENT TO REMAIN

EXISTING CONDUIT & WIRING OR EQUIPMENT TO BE REMOVED

NEW CONDUIT & WIRING OR EQUIPMENT

EXISTING

PANEL

NLB-DD

120/208V

DISCONNECT AND REMOVE ALL EXISTING

PANELBOARDS, FEEDERS AND BRANCH CIRCUIT

WIRING AFTER NEW INSTALLATION COMPLETE AND

OPERATIONAL. (TYPICAL)

BASEMENT

1ST FLOOR

SWICHGEAR ROOM

EXISTING

CRITICAL

POWER

SWITCHBOARD

EXISTING

NORMAL

POWER

SWITCHBOARD

EXISTING

PANEL

CLB-DD

120/208V

EXISTING

PANEL

CHB-DD

277/480V

EXISTING

225KV

XFMR

EXISTING FEEDERS TO REMAIN

PROVIDE NEW FEEDER

4#2+#8G IN 1-1/2" CONDUIT

EXISTING

PANEL

CL1-D3A

TO

REMAIN

120/208V

EXISTING

PANEL

CL1-D3B

TO BE

REMOVED

120/208V

EXISTING

PANEL

CL1-D3

TO BE

REMOVED

120/208V

2ND FLOOR

EXISTING

225KV

XFMR

EXISTING

PANEL

NL1-D

120/208V

EXISTING

PANEL

NL1-D5

TO

REMAIN

120/208V

EXISTING

PANEL

CHB-D

277/480V

EXISTING

PANEL

CHB-DD1

277/480V

NEW

PANEL

CL1-D4

SEE

SCHED.

120/208V

PATHOLOGY LAB

EXISTING

PANEL

CH1-DA

TO

REMAIN

277/480V

PROVIDE NEW FEEDER

4#3/0+#4G IN 2" CONDUIT

DISCONNECT AND REMOVE EXISTING

FEEDER TO PANEL 'CL1-D3' AND PROVIDE

NEW FEEDER FROM EXISTING 175A

BRANCH CIRCUIT AS SHOWN

DRAWING TITLE

APPROVED PROJECT DIRECTOR

PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

DRAWING NUMBER

BUILDING NUMBER

PROJECT NUMBER

REVISIONS DATE

NORTHPORT VA

MEDICAL CENTER

ENGINEERING

DEPARTMENT

ISSUED DATE

79 MIDDLEVILLE RD, NORTHPORT, NY 11768

DWG.

ELECTRICAL

ONE LINE DIAGRAM

AND PANEL SCHEDULE

ELECTRICAL POWER

UPGRADE FOR NEW

LABORATORY EQUIPMENT

01-07-22 KC KC

632-21-122

EP-102

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A. FOR EXISTING EQUIPMENT, SUCH AS WIRING DEVICES, CONDUITS, ETC., SHOWN ON FOR EXISTING EQUIPMENT, SUCH AS WIRING DEVICES, CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN THE WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE DEVICE AND REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS. B. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED WIRING. C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS. D. PROVIDE NEW SUPPORTS FOR ANY ELECTRICAL UTILITIES TO REMAIN THAT ARE PROVIDE NEW SUPPORTS FOR ANY ELECTRICAL UTILITIES TO REMAIN THAT ARE CURRENTLY SUPPORTED FROM THE EXISTING CEILING SUPPORT CHANNELS THAT WILL BE REMOVED. E. NO LIVE ELECTRICAL WORK SHALL BE PERMITTED. NO LIVE ELECTRICAL WORK SHALL BE PERMITTED.

AutoCAD SHX Text %%uGENERAL NOTES - DEMOLITION

AutoCAD SHX Text

2 REVISED PER FIELD CONDITION 3-12-21

AutoCAD SHX Text A. THE FEEDER FOR THIS PANELBOARD SHALL BE PROVIDED FROM BASEMENT THE FEEDER FOR THIS PANELBOARD SHALL BE PROVIDED FROM BASEMENT ELECTRICAL CLOSET AND FED FROM BOTTOM OF PANELBOARD. B. PROVIDE EMPTY CONDUITS AND JUNCTION BOXES ON THE CEILING FOR ALL SPARE PROVIDE EMPTY CONDUITS AND JUNCTION BOXES ON THE CEILING FOR ALL SPARE CIRCUIT BREAKERS FOR FUTURE USE.

AutoCAD SHX Text %%uGENERAL NOTES - PANELBOARD