SOW_Bldg_Facilities__HVAC_Controls_07JUN17.pdf

PDF 253 KB Posted

Attached to
Building Automation System Marine Operations Center - Atlantic Federal contract opportunity
Solicitation number
EA-133M-17-RQ-01192
Issued by
Department of Commerce National Oceanic and Atmospheric Administration

About this file

Statement of Work

View the file

Other files for this federal contract opportunity

Other files attached to Building Automation System Marine Operations Center - Atlantic, newest first.
File Type Posted
SF-30_No._0003__EA-133M-17-RQ-01192.pdf PDF
SF-30_No._0002_EA-133M-17-RQ-01192.pdf PDF
SF-30_EA-133M-17-RQ-01192.pdf PDF
RFQ_Combined_Synopsis_Solicitation_Controls.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NOAA/OMAO/MOC-A

HVAC Automation Controls

STATEMENT OF WORK

HVAC Automat ion Controls

Marine Operations Center - Atlantic (MOC-A) Norfolk, Virginia

BACKGROUND

The Marine Operations Center - Atlantic (MOC-A), residing at 439 West York St, Norfolk, VA is owned by the National Oceanic and Atmospheric Administration (NOAA) and is comprised of two buildings.

The primary purpose of the facility is to provide personnel and logistics support to sixteen ships and more than 500 wage mariners. NOAA’s “research and survey ships comprise the largest fleet of federal research ships in the nation. Ranging from large oceanographic research vessels capable of exploring the world’s deepest ocean, to smaller ships responsible for charting the shallow bays and inlets of the United States, the fleet supports a wide range of marine activities including fisheries research, nautical charting, and ocean and climate studies. “ www.omao.noaa.gov

STATEMENT OF WORK

This request is for the replacement and upgrade to the existing Building Automation System (BAS) for MOC-A. The current BAS is a proprietary Java Based Controls System (JACE). NOAA prefers a non-proprietary replacement. For the purposes of this contract, NOAA is focused on heating and air conditioning equipment. A properly configured BAS senses air flow, temperatures and controls the operation of the chiller, fans, pumps, louvers and other HVAC components in response to both preset instructions, occupied/unoccupied conditions and outside air temperatures. This request is for a BAS and associated equipment necessary to properly control the heating, ventilation and air conditioning (HVAC) system throughout MOC-A’s Buildings 1 and 2. Currently there is a separate smaller BAS for building 2 and NOAA seeks a solution to combine both buildings into one system for centralized control and system management.

The Marine Center’s HVAC controls need to be replaced by a new BAS meeting the following requirements with an emphasis on non-proprietary technology to ensure ease of monitoring, maintenance, expansion and system updates. The below requirements shall not limit the vendor’s responsibility to provide a comprehensive solution that will meet the objective of this project. The period of performance will end September 15, 2017.

The successful offeror shall meet the following requirements:

1. The product will provide NOAA with the ability to control the internal office space climate of both building’s 1 and 2 to within OSHA recommended limits of 68-76F with a humidity of 20-60%. Set points for each zone will be able to be changed and adjusted from the controls program by the facilities manager.

2. The system will be off the shelf compatible with the existing heating and air conditioning equipment including split units, roof top units, thermostats, air handlers, hot water boiler systems, radiators, air pressure regulators, water pumps, valves, Variable Valve Volume boxes (VAVs) and the fire alarm system. The existing wall mounted radiators are to be included in this project either as an independent system or centrally controlled by the BAS.

3. The unit will connect, control and monitor new and existing equipment. The preferred option will be BACnet compatible because of its open source format and prevalence throughout the industry. Currently the system is primarily LONworks and moving to a single non-proprietary configuration ensures NOAA’s ability to maintain, trouble shoot, update, replace or add additional equipment.

i. The system will be non-proprietary so that a properly trained or certified technician can interface, download and update or modify software to the controls.

ii. The unit will not require special interface drivers or software to access, monitor and control equipment.

iii. Will be an open standard protocol and any licensed features will be licensed to the National Oceanic and Atmospheric Administration.

4. Throughout the facility, there are multiple wall mounted radiators that are still functional but are not regulated by the JACE or wall mounted thermostats. The adjacent thermostats are either not functional or do not control temperature valves in the units. If a BACnet solution to integrate the existing wall mounted radiators into the BAS is not available, the vendor will provide NOAA with the best alternative to ensure functionality and adjustment for proper workplace climate control.

i. The vendor proposed solution will complement the ventilation system and a properly configured BAS will use less energy to maintain a temperature in these zones rather than overrunning equipment or competing to control the climate in the zoned space.

ii. The primary goal is to reduce unnecessary wear and tear on equipment and increase the serviceable life of HVAC equipment, maintain habitability and reduce energy consumption.

5. The controls will have safety features and alarms programmed into the package to prevent over running and burning out of equipment due to low pressure, temperature or electrical and current issues external to the component.

a. The BAS computer itself will have an integrated Uninterruptible Power Supply (UPS) to condition power and keep the unit online during a power outage.

b. The unit will be able to monitor temperatures which ensure each Roof Top Unit (RTU), split system and chiller/boiler pumps will not overrun themselves in the event of a low pressure or high temperature condition.

c. Include relative alarms to notify the facilities manager of an event where a piece of equipment is no longer working and or needs service.

6. Program the system for occupied and unoccupied requirements.

a. Collaborate with NOAA to develop the best plan and ensure onsite facilities management can adjust as needed.

7. Integrate all heating and air conditioning equipment in both buildings. This includes recently installed or existing equipment that was never integrated into the JACE or BAS in Building 2. The following are examples however it is incumbent on the contractor to do a thorough inspection of the latest building drawings and perform a site visit to become familiar with the facility prior to bidding on this project. (This requirement excludes the mini split units in the downstairs offices spaces of building’s 1 and 2)

a. A 15 ton RTU on the roof of Building 2

b. A split system mounted on the roof of building 2 for the server room on the second floor

c. Four split systems for building 2, first and second floors

d. A boiler for building 2, associated valves, plumbing and hot water coils in the duct work or AHU’s.

e. A boiler in building 1, associated valves, plumbing and hot water coils in the

AHU’s, wall mounted radiators, and ceiling mounted radiators in the warehouse

i. Ceiling mounted heating coils in the warehouse (6 each)

f. A 60 ton Trane Air Cooled Chiller for building 1

g. 2 RTU’s on the west wing of Building 1

h. An Air Handling Unit (AHU) above the warehouse conference room

i. VAV’s throughout the duct work in both buildings.

i. Integrate existing VAV’s and associated thermostats located throughout the duct work to provide the best solution for balancing the ventilation needs of each zoned space.

1. Add additional VAV’s as needed to meet the OSHA recommended habitability requirement previously mentioned.

2. Install bypass or air pressure relief duct work for inline VAV’s or as needed with other equipment.

8. As needed, add additional thermostats to provide necessary data points for the BAS to better manage each of the zones.

i. A robust wireless solution will be considered on a case by case basis as long as it meets the DOC and NOAA IT Security requirements.

9. As needed, add control valves and or feedback loops in the hot and chill water plumbing to better manage the delivery to AHU’s, radiators and other existing equipment throughout the facility.

10. The system shall be web-enabled and accessible from almost any PC or Mac based systems through standard web browsers such as Internet Explorer, Google Chrome or Safari.

a. Internet Protocol or IP based interface

b. Able to isolate access and monitor over the existing NOAA Network per DOC IT protocol.

c. Must be able to clearly identify failure codes related to HVAC equipment. This ensures the user understands the nature of component failure resulting in the timeliness of repair and or adjustment to set points of equipment without the assistance from a contractor.

11. Connect both buildings through wired or wireless connection.

a. Preferred option will be robust and secure meeting DOC and NOAA IT security requirements.

12. Install variable frequency drives for fan motors to reduce energy consumption.

a. There a various generations of AHU’s at MOC-A and it is incumbent on the vendor to determine which units have single speed fans and will need variable speed drives.

13. Install air pressure sensors to properly balance the ventilation.

14. Install variable speed drives for pumps to reduce energy consumption of the hot and cold water systems

15. Verify existing duct work is functional and meets the needs of the system

a. Known issue 1: The existing return duct work in the first floor of building 2 is not connected to the drop down ceiling. Connect using a three foot section of pickup line to the drop down ceiling in these two places.

16. Install sensors for outside air temperature and humidity

a. To ensure the HVAC systems in buildings 1 and 2 are operated in a slightly positive air pressure.

b. To ensure the boilers and air conditioning equipment are regulated based on seasonal changes and are not competing with one another. Properly configure the system to turn the boiler system on as needed and properly regulate the chill water temperature in accordance with manufacturers recommendations.

17. Integrate with existing fire alarm systems to shut down ventilation in the case of fire or smoke detected in the facility.

a. Meets National Fire Protections Association (NFPA) standards for federal buildings with fire protection and ventilation emergency shut offs.

18. Provide a minimum of 8 hours of onsite training from a certified technician.

19. Include firmware and software updates with technical support of interface programs and user applications for two years.

a. Provide a minimum of 8 hours expert user training to 3 ea. MOC-A designated employees from a well-experienced certified HVAC technician.

20. Two year warranty on hardware and software package with one year warranty on labor to remove and replace failed equipment.

DELIVERABLES

1. Ability for MOC-A facilities manager to adjust the indoor temperature of office and meeting spaces to OSHA recommended parameters described in the previous section.

2. Operator’s manual and basic troubleshooting guide for commonly occurring problems with the BAS and associated equipment.

3. Provide updated as-built control drawings.

4. Provide complete and correct System Graphics.

5. Provide eight hours of user training.

6. One year labor and two year materials warranty on all work performed.

7. Two years of software updates and technical support for operating and managing the

BAS.

8. Backup software CD’s with fully developed trending screens.

GENERAL

1. Summary: Contractor shall provide all labor, tools, equipment, supervision, hauling, cleanup, and insurance needed for this project.

2. Safety Assurance: Contractor shall prepare and continuously monitor the work area to ensure safety and compliance with all OSHA safety regulations, as well as any pertinent county or state safety standards.

3. Worksite Management: Contractor shall provide a competent work foreman who is authorized to act for the contractor and who is on site daily to direct and oversee the work.

4. Work that will interrupt the daily operations of the facility such as extended down times with HVAC will be coordinated with the facilities manager or their designee to ensure minimal impact to employees

5. Warranty: Contractor shall provide a two-year parts and one year workmanship warranty. In addition to the two year warranty from the manufacturer, include two years of technical support for the system while equipment is adjusted to provide optimal operation.

PREPARATION

1. Access: NOAA/MOC-A will provide the Contractor with unobstructed access to all interior and exterior areas as needed. Contractor shall provide all equipment necessary to remove and install equipment. All unnecessary equipment such as thermostats will be removed. Any holes in the walls will be patched, primed and painted to match adjacent materials.

2. Documentation: NOAA/MOC-A will provide the Contractor with all available documentation, drawings, and historical information on the existing HVAC equipment, as requested or available. MOC-A recently had drawings updated for the facility HVAC system however, there still may be equipment abandoned in place not represented on the drawings and will be documented on updated AS BUILT drawings provided by the contractor.

a. Contractor provides detailed documentation on all newly installed equipment to include connections to existing equipment on updated drawings.

b. User manuals and any technical documentation.

c. Contractor will provide a general how-to guide on system operation, basic troubleshooting and maintenance.

WORK ITEMS

1. Provide, Install, and Program one Building Automation System in the “Boiler Room” to control the following:

a. All new HVAC equipment for both buildings 1 and 2

b. All existing HVAC equipment for both buildings 1 and 2

c. Wall mounted radiators if they are BACNET compatible. If they are not compatible, then proceed with the alternative described in the SOW above.

2. Provide, Install, and Program BACNET Communication equipment throughout the system.

3. Provide and install Variable Frequency Drives (VFDs) on hot and cold water pumps

4. Provide and install VFDs on AHU fans

5. Modify programming instructions to system controllers and other components to ensure their proper and effective operation.

6. Provide and Install air pressure sensors

7. Verify functionality of the controllers for variable air volume (VAV) boxes and AHU’s throughout the system.

a. Identify units that must be adjusted and make the needed adjustments or repairs for optimum performance.

8. Run conduit from the controller to new and existing equipment as needed. Please see previous section on wireless technologies.

9. Provide, Install, and Program Outdoor Air Temperature Sensor.

10. Provide, Install, and Program one Outdoor Air Humidity Sensor.

11. Programming and Software set-up by Controls Technician.

a. Provide software operating instructions to manage heating, ventilation and air conditioning (HVAC) equipment.

b. Provide instructions to add new components and configure system changes.

12. Confirm the proper response of all HVAC equipment to commands from the BAS.

13. Operationally test the smoke detection system and verify the operation of all fans and dampers throughout the system.

a. Resolve related issues with the fire detection system.

14. Review system reports, alarms and error logs.

a. Resolve system all alarms and errors before project completion.

15. Balance ventilation system in both buildings.

16. Ensure all components that require a license for access are licensed to “National Oceanic and Atmospheric Administration, Office of Marine and Aviation Operations”.

WORK RESTRICTIONS AND REQUIREMENTS

1. Scheduling Requirements: Conduct the work so as to avoid conflict with normal on-

--going facility operations. The schedule of work will be submitted prior to beginning work and shall be approved by the Chief of Operations to ensure coordination with facility operations.

2. Communications: Furnish a list of Contractor contact personnel including addresses and telephone numbers for use in the event of emergency.

3. Working Hours: Regular working hours shall consist of a 9---hour period, between 7 AM and 4:30 PM, Monday through Friday, excluding Government holidays. Work outside regular working hours including weekends and evenings requires approval of the Chief of Operations and will be considered on a case by case basis and availability of the contractor.

4. Storage: Equipment and materials may be stored on site. Tools may be stored on site if they are in a locked cabinet. MOC-A shall assume no liability for these materials.

5. Security: Contractor’s employees must check in with MOC-A security if they enter the building.

6. Cleanliness and Order: All tools and equipment shall be secured at the end of each workday. The work site shall be cleaned of trash and debris on a daily basis.

CONTACT LIST

a) LT Joseph Carrier Chief of Operations

439 West York St, Norfolk VA 23510 Chiefops.moa@noaa.gov

(757) 284-9747

b) Alexander Cooper

Contracting Specialist 200 Granby Street, Norfolk VA 23510 alexander.cooper@noaa.gov

(757) 441-3409

------ END OF STATEMENT OF WORK ---------

mailto:Chiefops.moa@noaa.gov mailto:alexander.cooper@noaa.gov

Marine Operations Center - Atlantic (MOC-A)
BACKGROUND
STATEMENT OF WORK
DELIVERABLES
GENERAL
PREPARATION
WORK ITEMS
WORK RESTRICTIONS AND REQUIREMENTS
CONTACT LIST
a) LT Joseph Carrier
Chief of Operations

File details come from the government source that posted it. Updated .