DRAWING TITLE
DWG
NO.
INDEX OF DRAWINGS
100%
CONSTRUCTION
DOCUMENTS
FIRE PROTECTION SYMBOL LIST
SYMBOL: DESCRIPTION:
FIRE PROTECTIONFP
SERVICE WATER - POTABLEW
ANGLE VALVE
BUTTERFLY VALVE WITH MONITOR SWITCH
OS&Y GATE VALVE
OS&Y GATE VALVE WITH MONITOR SWITCH
PRESSURE SWITCH
P
NO HATCH LIGHT HAZARD
ORDINARY GROUP 1
SPRINKLER - WALL MOUNTED
SPRINKLER
SPRINKLER - CONCEALED
INSPECTOR TEST AND DRAIN VALVE
MONITOR SWITCH
PIPE CAP
PIPE DOWN
NEW CONNECTION
PIPE UP OR UP/DOWN
SHUTOFF VALVE NORMALLY OPEN
DRAINDFP
NOT ALL SYMBOLS MAY APPLY.
AUTOMATIC DRAIN VALVE
UNION/FLANGE
DIRECTION OF FLOW IN PIPE
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)P
CHECK VALVE
FLOW SWITCH
F
ROUTE TO DRAIN
AREA BOUNDARY
FIRE PROTECTION ABBREVIATION KEY
AD ACCESS DOOR
BFP BACKFLOW PREVENTER
N.C. NORMALLY CLOSED
ABOVE FINISHED FLOORAFF
NC NEW CONNECTION
NOT IN CONTRACTNIC
NORMALLY OPENN.O.
ABBR: DESCRIPTION:
TYPICALTYP
CK CHECK VALVE
GA OS&Y GATE VALVE
JP JOCKEY PUMP
FP FIRE PUMP
GATE VALVE - EXISTINGGA-E
CHECK VALVE - EXISTINGCK-E
JOCKEY PUMP - EXISTINGJP-E
FIRE PUMP - EXISTINGFP-E
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIM
INDICATES SIMILAR DETAIL
REFERENCED IN MULTIPLE LOCATIONS
LEVEL NAME
10' - 0" HEIGHT ABOVE
PROJECT 0' - 0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
N O R
HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
NEW WORK BY THIS CONTRACTOR
(DARK SOLID LINE)
NEW WORK UNDERFLOOR OR UNDERGROUND BY THIS CONTRACTOR
(DARK LONG DASHED LINE)
NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN
(LIGHT SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR
(DARK SHORT DASHED LINE)
LINE TYPE KEY:
BUILDING CODE: IBC 2015 EDITION
FIRE CODE: IFC 2015 EDITION
ELECTRICAL CODE: NFPA 70 (NEC) 2017 EDITION
LOCAL BUILDING CODE: CURRENT EDITION
USDA DESIGN STANDARD: ARS 242.1 FACILITIES DESIGN STANDARDS
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.
CONTACT PERSONS:
PROJECT MANAGER
FIRE PROTECTION
ELECTRICAL
BLAKE O'BRIEN
BLAKE O'BRIEN
SHANE THOMPSON
DESCRIPTION: PERSON:
FIRE PROTECTION CONTRACTORF.P.C.
CONTRACTING OFFICERS REPRESENTATIVECOR
GENERAL CONTRACTORG.C.
ELECTRICAL CONTRACTORE.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
MECHANICAL GENERAL NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO FIRE PROTECTION AND ELECTRICAL.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT AND PIPING ARE DIAGRAMMATIC AND MAY
NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS. DRAWINGS SHOW THE
GENERAL ARRANGEMENT OF PIPING AND EQUIPMENT AND MAY NOT INCLUDE ALL OFFSETS
AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION. THE DRAWINGS SHALL BE
FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHERS
WILL PERMIT.
2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES PHYSICALLY AT
SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE
CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO
VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO
VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES
OR CONFLICTS TO THE ATTENTION OF THE ENGINEER BEFORE PROCEEDING WITH
FABRICATION OR EQUIPMENT ORDERS.
4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE
REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER
ACCESS.
5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO
COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR
EXPENSE TO OTHERS.
6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL
CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF
DESIGN.
7. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS. THE
CONTRACTOR WHOSE WORK CAUSES DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH
ORIGINAL CONSTRUCTION, FIRE RATING, AND FINISH.
8. SEAL ALL WALL PENETRATIONS AIRTIGHT WHERE PIPING PENETRATES.
9. CAULK ALL PIPE PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL AND PARTITIONS.
THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE ROOM TO ANOTHER AND
TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS.
10. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES.
11. MAINTAIN MINIMUM 3'-6” CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS, MOTOR
STARTERS, SWITCHES, AND DISCONNECTS.
12. ANCHORS EMBEDDED IN CONCRETE SHALL BE CRACKED CONCRETE APPROVED IN
ACCORDANCE WITH SPECIFICATIONS.
MECHANICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING PIPING IS SHOWN. VERIFY EXISTING CONDITIONS BEFORE STARTING
WORK. NOTIFY COR OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR PIPING BEFORE FABRICATION. RISES AND
DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK
AND SHALL NOTIFY THE COR PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE
REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF WORK.
5. EACH CONTRACTOR SHALL CUT AND PATCH WALLS AND FLOORS ASSOCIATED WITH HIS
WORK.
6. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH
NEW EQUIPMENT OR PIPING TO BE INSTALLED. EACH CONTRACTOR SHALL EITHER
ARRANGE NEW EQUIPMENT OR PIPING IN SUCH A FASHION THAT IT DOES NOT CONFLICT
WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL SYSTEMS TO ALLOW FOR
INSTALLATION OF NEW EQUIPMENT OR PIPING.
7. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING
CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT
REMAIN ACTIVE.
8. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY
REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW
SYSTEMS ARE INSTALLED.
9. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR
TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND
CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY
DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
10. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT
THAT HAS BEEN REMOVED.
1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR.
CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR
FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.
2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO
THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS
RESPONSIBLE FOR A COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN
THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES
PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER IS THE BASIS OF
DESIGN.
3. FIRE PROTECTION PIPE ROUTING IS SHOWN FOR GENERAL LAYOUT. DETERMINE EXACT
NUMBER OF SPRINKLERS, PIPE SIZING, AND PIPE ROUTING.
FIRE PROTECTION GENERAL NOTES:
NATIONAL LABORATORY FOR AGRICULTURE & THE ENVIRONMENT (NLAE)
FIRE PUMP REMOVAL
AMES, IOWA
#AG-32-SC-D-16-0004
USDA
REAL PROPERTY
USDA
SAFETY & HEALTH
AREA ENGINEER
DRAWN BY
CHECKED BY
DESIGNER
PROJECT MANAGER
EPM
A-E FIRM
USDA PROJECT NO.
DATE
NO. DATE BY
SHEET
DESCRIPTION
Service Research Agricultural
REVISIONS
FACILITIES ENGINEERING SECTION
SOUTH ATLANTIC AREA
950 COLLEGE STATION RD.
P.O. BOX 5677
ATHENS, GEORGIA 30605
100%
CONSTRUCTION
DOCUMENTS U
S D A
C A D
D H
D S G
P M
OF
ALAN TOLAND --
TRISHA VIGIL
DEAN MAGEE
PHOEBE BORDELON
F000
FIRE PROTECTION COVERSHEET
BTO
RML
DJL
17033
08-13-2018 02 07
A B C D E F G H J K L M N P Q R S T U V W X
DN
UP
DN
STORAGE
B18
RADIO ST.
B17
LOCKER
B16
LOCKER
B15
G. CHAMBER
B14
DRYING
B12
PREP
B10
REFRIG.
B11
STORAGE
B07
SOIL GRIND
B05
MECH.
B08
P & R
GRIND
B04
OFFICE
B02
P & R
PREP
B01
TARGET
B26A
INSTRU.
B26B
MECH.
B25D
RHIZOTRON
B22
J.C.
B27
SW. GEAR
B29
OFFICE
B28
EM. GEN.
B30
B25A
SHEET METAL
B25B
WELDING
B25C
MACHINING
B25
MECH. ROOM
B19
4"
BFP-E
FD100
REFER TO 2/F101
FOR CONT.
7 7
EXISTING BASEMENT
LEVEL ZONE CONTROL
VALVE ASSEMBLY.
FP
B-2
FP
B-1
GA-E
GA-E
CK-E
GA-E
GA-E
CK-E
JP-E
FP-E
GA-E (IN VERTICAL)
FIRE PUMP CONTROLLER
JOCKEY PUMP CONTROLLER
6"
NATIONAL LABORATORY FOR AGRICULTURE & THE ENVIRONMENT (NLAE)
FIRE PUMP REMOVAL
AMES, IOWA
#AG-32-SC-D-16-0004
USDA
REAL PROPERTY
USDA
SAFETY & HEALTH
AREA ENGINEER
DRAWN BY
CHECKED BY
DESIGNER
PROJECT MANAGER
EPM
A-E FIRM
USDA PROJECT NO.
DATE
NO. DATE BY
SHEET
DESCRIPTION
Service Research Agricultural
REVISIONS
FACILITIES ENGINEERING SECTION
SOUTH ATLANTIC AREA
950 COLLEGE STATION RD.
P.O. BOX 5677
ATHENS, GEORGIA 30605
100%
CONSTRUCTION
DOCUMENTS U
S D A
C A D
D H
D S G
P M
OF
ALAN TOLAND --
TRISHA VIGIL
DEAN MAGEE
PHOEBE BORDELON
FD100
BASEMENT - FIRE PROTECTION DEMOLITION
BTO
RML
DJL
17033
08-13-2018 03 07
N
O R HT
1/8" = 1'-0"1
BASEMENT - FIRE PROTECTION DEMOLITION
GENERAL FIRE PROTECTION NOTES :
1. REFER TO SHEET F000 - FIRE PROTECTION
COVERSHEET FOR FIRE PROTECTION
GENERAL NOTES AND SYMBOLS LIST.
2. FIRE PROTECTION SYSTEM SHALL BE PLACED
BACK IN SERVICE AT THE END OF EACH
WORKDAY.
3. REMOVAL OF FIRE PUMP REQUIRED IN THIS
SCOPE WILL REQUIRE FUTURE PROJECT TO
REVISE FIRE PROTECTION PIPING IN ADJACENT
BUILDING FOR BUILDING TO REMAIN
PROPERLY PROTECTED. REFER TO IMEG
REPORT DATED 12/15/2017.
N
O R HT
1/4" = 1'-0"2
BASEMENT - FIRE PROTECTION DEMOLITION - ENLARGED PLAN
KEYNOTES :
1. DEMOLISH EXISTING GATE VALVE AND ALL
ASSOCIATED ACCESSORIES.
2. DEMOLISH EXISTING CHECK VALVE AND ALL
ASSOCIATED ACCESSORIES.
3. DEMOLISH EXISTING JOCKEY PUMP, VALVES,
AND ASSOCIATED PIPING.
4. DEMOLISH EXISTING FIRE PUMP AND ALL
ASSOCIATED COMPONENTS.
5. DEMOLISH EXISTING FIRE PUMP CONTROLLER,
PRESSURE SENSING PIPE, AND ALL OTHER
ASSOCIATED COMPONENTS.
6. DEMOLISH EXISTING JOCKEY PUMP
CONTROLLER, PRESSURE SENSING PIPE, AND
ALL OTHER ASSOCIATED COMPONENTS.
7. DEMOLISH EXISTING PIPING BACK TO THIS
POINT. PREPARE EXISTING PIPE FOR NEW
CONNECTION.
REFER TO 1/F101
FOR CONT.
EXISTING BASEMENT LEVEL
ZONE CONTROL VALVE
ASSEMBLY LOCATED IN
MECHANICAL ROOM.
A B C D E F G H J K L M N P Q R S T U V W X
DN
UP
DN
STORAGE
B18
RADIO ST.
B17
LOCKER
B16
LOCKER
B15
G. CHAMBER
B14
DRYING
B12
PREP
B10
REFRIG.
B11
STORAGE
B07
SOIL GRIND
B05
MECH.
B08
P & R
GRIND
B04
OFFICE
B02
P & R
PREP
B01
TARGET
B26A
INSTRU.
B26B
MECH.
B25D
RHIZOTRON
B22
J.C.
B27
SW. GEAR
B29
OFFICE
B28
EM. GEN.
B30
B25A
SHEET METAL
B25B
WELDING
B25C
MACHINING
B25
MECH. ROOM
B19
NC
NC
NC
NC NC
BFP-E
1" 1"
/4
1 1/4"1"1"
1"1"1 1/4"1 1/4"1 1/4"
1"1 1/4"
1"
1 1/4" 1 1/4"
1" 1" 1 1/4" 1 1/4"
1"
8"
1" 1 1/4" 1 1/4"
1 1/4"
1 1/4" 1 1/4"
1 1/4" 1"
1" 1 1/4" 1 1/4"
1 1/4"
1 1/4" 1 1/4" 1 1/4"
1" 1"
1"1 1/4"
/4
1 1/4"1 1/4"1 1/4"1 1/4"1 1/4" 1 1/4"1"
1 1/4" 1"
1 1/4"1 1/4"1 1/4"1"1"
1 1/4"
1 1/4"
1 1/4"1"
1 1/4"
1 1/4"
1 1/4" 1" 1"
1"1"1 1/4"
1 1/4"1 1/4"1 1/4" 1 1/4"
1 1/4"
1 1/4"
/4
1 1/4"1 1/4"1 1/4"
1 1/4"
4"
6"
4" 4"
1 1/4"
1 1/4"1 1/4"1" 1"
1"
/4
1"
1"
6"
1 1/4"
1 1/4"
/4
1"
1" 1 1/4" 1 1/4" 1 1/4"
1 1/4"
1 1/4"
1"1"1"
1"
1" 1 1/4"
/4
1" 1"
1"
1 1/4"
1"
1 1/4" 1 1/4"
1"
1 1/4" 1" 1"
1" 1"
1"1"1 1/4"
1 1/4"
1 1/4"1 1/4"
1 1/4"1 1/4"
1 1/4"1"1"
1 1/4"
1 1/4" 1 1/4" 1 1/4"1 1/4"1 1/4"
1" 1 1/4"
1 1/4"1" 1"
/4
1 1/4"
1 1/4" 1"
1 1/4"
1 1/4"
1" 1 1/4"
1 1/4"1 1/4" 1 1/4"1 1/4"
1 1/4"
1 1/4"1 1/4"
1 1/4"
1"1"
1" 1" 1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/4" 1" 1"
1"1"
1 1/4"
/4
1 1/4"
"F
P
4"FP
"F
P
4"FP
NC
NC
NC
NC NC
BFP-E
EXISTING BASEMENT LEVEL ZONE
CONTROL VALVE ASSEMBLY
LOCATED IN MECHANICAL ROOM.
EXISTING BASEMENT LEVEL ZONE
CONTROL VALVE ASSEMBLY.
FP
B-2
FP
B-1
NATIONAL LABORATORY FOR AGRICULTURE & THE ENVIRONMENT (NLAE)
FIRE PUMP REMOVAL
AMES, IOWA
#AG-32-SC-D-16-0004
USDA
REAL PROPERTY
USDA
SAFETY & HEALTH
AREA ENGINEER
DRAWN BY
CHECKED BY
DESIGNER
PROJECT MANAGER
EPM
A-E FIRM
USDA PROJECT NO.
DATE
NO. DATE BY
SHEET
DESCRIPTION
Service Research Agricultural
REVISIONS
FACILITIES ENGINEERING SECTION
SOUTH ATLANTIC AREA
950 COLLEGE STATION RD.
P.O. BOX 5677
ATHENS, GEORGIA 30605
100%
CONSTRUCTION
DOCUMENTS U
S D A
C A D
D H
D S G
P M
OF
ALAN TOLAND --
TRISHA VIGIL
DEAN MAGEE
PHOEBE BORDELON
F100
BASEMENT - FIRE PROTECTION
BTO
RML
DJL
17033
08-13-2018 04 07
N O R
HT
1/8" = 1'-0"1
BASEMENT - FIRE PROTECTION NEW WORK
GENERAL FIRE PROTECTION NOTES :
1. REFER TO SHEET F000 - FIRE PROTECTION
COVERSHEET FOR FIRE PROTECTION
GENERAL NOTES AND SYMBOLS LIST.
2. REMOVAL OF FIRE PUMP REQUIRED IN THIS
SCOPE WILL REQUIRE FUTURE PROJECT TO
REVISE FIRE PROTECTION PIPING IN ADJACENT
BUILDING FOR BUILDING TO REMAIN
PROPERLY PROTECTED. REFER TO IMEG
REPORT DATED 12/15/2017.
3. FIRE PROTECTION SYSTEM SHALL BE PLACED
BACK IN SERVICE AT THE END OF EACH
WORKDAY.
4. CONTRACTOR SHALL PROVIDE ALL REQUIRED
PROVISIONS TO ISOLATE AND
HYDROSTATICALLY TEST NEW PIPING. EXTENT
OF NEW PIPING IS INDICATED ON THIS SHEET.
NEW PIPING SHALL BE TESTED AT 200 PSI FOR
2 HRS ACCORDING TO NFPA 13.
ELECTRICAL ABBREVIATION KEY
AFF ABOVE FINISHED FLOOR
N.C. NORMALLY CLOSED
N.O. NORMALLY OPEN
ABBR: DESCRIPTION:
TYP TYPICAL
C CONDUIT
1. ##-### INDICATES ELECTRICAL EQUIPMENT DEFINED IN ELECTRICAL SCHEDULES OR
SPECIFICATION. REFER TO DRAWINGS CONTAINING ELECTRICAL SCHEDULES. PERMANENT
NAMEPLATE SHALL MATCH FINAL EQUIPMENT NOMENCLATURE, NOT ELECTRICAL
EQUIPMENT TAG NAME, REFER TO SPECIFICATIONS.
ELECTRICAL GENERAL NOTES:
REFER TO SHEET F000 FOR REQUIRED CODES, LIST OF PROJECT CONTACTS AND PROJECT
VIEW KEY.
1. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE
WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR
BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN
EACH PHASE.
2. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL
BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF
THROUGH-PENETRATION FIRESTOPS. REFER TO 26 05 03 FOR ADDITIONAL INFORMATION
AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.
3. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE
EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR
SEALED INTO OPENINGS.
ELECTRICAL INSTALLATION NOTES:
FA-100 28 31 00 FIRE ALARM CONTROL PANEL
FA-160 28 31 00 FIRE ALARM ADDRESSABLE MONITOR MODULEMM
FA-260 28 31 00 FIRE ALARM FLOW SWITCH TO MONITOR FIRE
PROTECTION SYSTEM
FS
FA-261 28 31 00 FIRE ALARM MONITOR SWITCH TO
MONITOR FIRE PROTECTION SYSTEM
MS
NA NA CIRCUIT BREAKER - SURFACE MOUNTED
NA NA DISCONNECT
ELECTRICAL SYMBOL LIST
SYMBOL: TAG:
SPEC
SECTION:
DESCRIPTION:
ELECTRICAL SYMBOL LIST
SYMBOL: TAG:
SPEC
SECTION:
DESCRIPTION:
JB 26 05 33 JUNCTION BOX
J
J
ECONN 26 05 33 ELECTRICAL CONNECTION
E
E
PANEL '###' NA EXISTING PANELBOARD - SURFACE MOUNT
NA NA EXISTING MANUAL SWITCH / STARTER /
COMBINATION STARTER
ELECTRICAL SYMBOL LIST
SYMBOL: TAG:
SPEC
SECTION:
DESCRIPTION:
NA NA EXISTING TRANSFORMER
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING EQUIPMENT, LUMINARIES, AND CONDUIT ARE SHOWN. VERIFY EXISTING
CONDITIONS AND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR CABLE TRAY, BUSWAY AND CONDUITS
BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING
FIELD CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK
AND SHALL NOTIFY THE CONTRACTING OFFICER REPRESENTATIVE PRIOR TO BIDDING IF
OTHER UTILITIES ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO
HIS/HER AREA OF WORK.
5. EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED
WITH HIS/HER WORK.
6. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW
EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER
ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES
NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO
ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
ELECTRICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
ELECTRICAL PHASING NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
1. THE FIRE PROTECTION AND ELECTRICAL DRAWINGS DO NOT DEPICT THE MEANS AND
METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.
WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY LIGHTING, POWER, SYSTEMS, ETC. AS NEEDED TO MAINTAIN
SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARY LIGHTING, CIRCUITS, ETC. AS NECESSARY TO KEEP ALL OCCUPIED
SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
NATIONAL LABORATORY FOR AGRICULTURE & THE ENVIRONMENT (NLAE)
FIRE PUMP REMOVAL
AMES, IOWA
#AG-32-SC-D-16-0004
USDA
REAL PROPERTY
USDA
SAFETY & HEALTH
AREA ENGINEER
DRAWN BY
CHECKED BY
DESIGNER
PROJECT MANAGER
EPM
A-E FIRM
USDA PROJECT NO.
DATE
NO. DATE BY
SHEET
DESCRIPTION
Service Research Agricultural
REVISIONS
FACILITIES ENGINEERING SECTION
SOUTH ATLANTIC AREA
950 COLLEGE STATION RD.
P.O. BOX 5677
ATHENS, GEORGIA 30605
100%
CONSTRUCTION
DOCUMENTS U
S D A
C A D
D H
D S G
P M
OF
ALAN TOLAND --
TRISHA VIGIL
DEAN MAGEE
PHOEBE BORDELON
E000
ELECTRICAL COVERSHEET
SET
IPS
SET
17033
08-13-2018 05 07
A B C D E F G H J K L M N P Q R S T U V W X
DN
UP
DN
STORAGE
B18
RADIO ST.
B17
LOCKER
B16
LOCKER
B15
G. CHAMBER
B14
DRYING
B12
PREP
B10
REFRIG.
B11
STORAGE
B07
SOIL GRIND
B05
MECH.
B08
P & R
GRIND
B04
OFFICE
B02
P & R
PREP
B01
TARGET
B26A
INSTRU.
B26B
MECH.
B25D
RHIZOTRON
B22
J.C.
B27
SW. GEAR
B29
OFFICE
B28
EM. GEN.
B30
B25A
SHEET METAL
B25B
WELDING
B25C
MACHINING
B25
MECH. ROOM
B19
MS
MS
MS
E
E
MS
MS
MS
BFP-E
PANEL EBA
PANEL NBA
TR-225
TR-30
FIRE PUMP FEEDER
PULL BOX
TR-225
PANEL NB1
PANEL NDPB1PANEL NDPBA
INCOMING UNIT
SUBSTATION SWGEAR B29
EXISTING FIRE ALARM
CONTROL PANEL
HV SWITCH
TRANSFORMER
SWITCHBOARD
NATIONAL LABORATORY FOR AGRICULTURE & THE ENVIRONMENT (NLAE)
FIRE PUMP REMOVAL
AMES, IOWA
#AG-32-SC-D-16-0004
USDA
REAL PROPERTY
USDA
SAFETY & HEALTH
AREA ENGINEER
DRAWN BY
CHECKED BY
DESIGNER
PROJECT MANAGER
EPM
A-E FIRM
USDA PROJECT NO.
DATE
NO. DATE BY
SHEET
DESCRIPTION
Service Research Agricultural
REVISIONS
FACILITIES ENGINEERING SECTION
SOUTH ATLANTIC AREA
950 COLLEGE STATION RD.
P.O. BOX 5677
ATHENS, GEORGIA 30605
100%
CONSTRUCTION
DOCUMENTS U
S D A
C A D
D H
D S G
P M
OF
ALAN TOLAND --
TRISHA VIGIL
DEAN MAGEE
PHOEBE BORDELON
E100
BASEMENT - ELECTRICAL
SET
Checker
SET
17033
08-13-2018 06 07
NATIONAL LABORATORY FOR AGRICULTURE & THE ENVIRONMENT (NLAE)
FIRE PUMP REMOVAL
AMES, IOWA
#AG-32-SC-D-16-0004
USDA
REAL PROPERTY
USDA
SAFETY & HEALTH
AREA ENGINEER
DRAWN BY
CHECKED BY
DESIGNER
PROJECT MANAGER
EPM
A-E FIRM
USDA PROJECT NO.
DATE
NO. DATE BY
SHEET
DESCRIPTION
Service Research Agricultural
REVISIONS
FACILITIES ENGINEERING SECTION
SOUTH ATLANTIC AREA
950 COLLEGE STATION RD.
P.O. BOX 5677
ATHENS, GEORGIA 30605
100%
CONSTRUCTION
DOCUMENTS U
S D A
C A D
D H
D S G
P M
OF
ALAN TOLAND --
TRISHA VIGIL
DEAN MAGEE
PHOEBE BORDELON
E100
BASEMENT - ELECTRICAL
SET
Checker
SET
17033
08-13-2018 06 07
KEY NOTES :
1. FIRE PUMP TAP FROM MAIN SWITCHGEAR.
REMOVE CONDUIT AND WIRE BACK TO
SOURCE. E.C. SHALL PROVIDE A NEW METAL
TOP COVER TO CLOSE UP CONDUIT ENTRY
POINTS. COVER SHALL MATCH EXISTING
MATERIAL AND COLOR OF SWITCHGEAR. E.C.
SHALL COORDINATE SHUTDOWN OF MAIN
ELECTRICAL SERVICE WITH CONTRACTING
OFFICER REPRESENTATIVE.
2. DISCONNECT FIRE ALARM SYSTEM MONITOR
SWITCH. E.C. SHALL COORDINATE WITH
CONTRACTING OFFICER REPRESENTATIVE TO
HAVE FIRE ALARM CONTROL PANEL
REPROGRAMMED TO REFLECT CHANGES TO
SYSTEM. TYPICAL OF 6. REMOVE ALL CONDUIT
AND WIRE BACK TO SOURCE.
3. DISCONNECT EXISTING FIRE PUMP AND
ASSOCIATED CONTROLLER FOR REMOVAL BY
OTHERS.
4. DISCONNECT EXISTING JOCKEY PUMP AND
ASSOCIATED CONTROLLER FOR REMOVAL BY
OTHERS.
N O R
HT
1/8" = 1'-0"1
BASEMENT - ELECTRICAL
3-300E
2000KVA
5 KV, 3-PHASE, 4W
INCOMING 5KV FEEDER
480/277V, 3-PHASE, 4W
N E
U T R
A L
SWGEAR B29
DPM
C.T.'S
(3)
3200AF
2000AT
[LSIG]
GROUND
A
M P
B U
S
(3 )
###A/3P
SPACE
LA
600A/3P
DPM
C.T.'S
4160V
480/277V
800AF
400AT
200A/3P
EMERGENCY GENERATOR
250KW
480/277V
3-PHASE, 4WG
NEUTRALGROUND
400A/3P
TS-1
200A
FIRE PUMP CONTROLLER
800AF
200AT
M
800AF
800AT
M
TO NDPB1
800AF
800AT
M
800AF
800AT
M
800AF
200AT
M
800AF
200AT
M
800AF
350AT
M
800AF
350AT
M
800AF
##AT
M
TO NDPB2
TO MCC#1
TO MCC#2
TO MCC#3
TO NDPBB
TO NDPBA
SPARE
E
FIRE PUMP
60HP
BREAKER FOR FIRE PUMP
TO EDPB1
TO EDPB1-3
3#10 & 1#10 GND
IN 3/4" C.
JOCKEY PUMP
2HP
3#500 KCM & 1#3 GND
IN 3 1/2" C.
4#4/0 & 1#6 GND
IN 2 1/2" C.
3#500 KCM & 1#3 GND
IN 3 1/2" C.
3#500 KCM & 1#3 GND
IN 3 1/2" C.
4#4/0 & 1#6 GND
IN 2 1/2" C.
FIRE PUMP
PULL BOX
E
NATIONAL LABORATORY FOR AGRICULTURE & THE ENVIRONMENT (NLAE)
FIRE PUMP REMOVAL
AMES, IOWA
#AG-32-SC-D-16-0004
USDA
REAL PROPERTY
USDA
SAFETY & HEALTH
AREA ENGINEER
DRAWN BY
CHECKED BY
DESIGNER
PROJECT MANAGER
EPM
A-E FIRM
USDA PROJECT NO.
DATE
NO. DATE BY
SHEET
DESCRIPTION
Service Research Agricultural
REVISIONS
FACILITIES ENGINEERING SECTION
SOUTH ATLANTIC AREA
950 COLLEGE STATION RD.
P.O. BOX 5677
ATHENS, GEORGIA 30605
100%
CONSTRUCTION
DOCUMENTS U
S D A
C A D
D H
D S G
P M
OF
ALAN TOLAND --
TRISHA VIGIL
DEAN MAGEE
PHOEBE BORDELON
ED400
ELECTRICAL-ONE LINE DEMO
SET
Checker
SET
17033
08-13-2018 07 07
NO SCALE1
ELECTRICAL ONE LINE DIAGRAM - DEMOLITION
| G001.pdf |
| Fire Protection Set.pdf |
| Sheets |
| F000 - FIRE PROTECTION COVERSHEET |
| FD100 - BASEMENT - FIRE PROTECTION DEMOLITION |
| F100 - BASEMENT - FIRE PROTECTION |
| Electrical Set.pdf |
| Sheets |
| E000 - ELECTRICAL COVERSHEET |
| E100 - BASEMENT - ELECTRICAL |
| ED400 - ELECTRICAL-ONE LINE DEMO |