Drawings Addendum 1 Notes.pdf

PDF 438 KB Posted

Attached to
Z1DA--Insulate Exterior Walls, Replace Windows 553-21-106 Federal contract opportunity
Solicitation number
36C25023B0024
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

This document is an architect's addendum providing revised notes for plans to insulate exterior walls and replace windows at the John D Dingell VA Medical Center in Detroit, Michigan. The addendum specifies that existing backer rod and sealant will be removed and new backer rod and sealant installed around storefront perimeters. Interior finishes such as fin tube covers and resilient base will be removed and replaced. Window jambs will be filled with spray foam insulation and holes patched and painted to match existing. Blast resistant film will be installed on interior windows of the first floor only, as outlined in specification section 08 80 00. The related federal contract opportunity is solicitation number 36C25023B0024 from the Department of Veterans Affairs for insulating exterior walls, replacing windows, and completing associated interior work at the medical center.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--Insulate Exterior Walls, Replace Windows 553-21-106, newest first.
File Type Posted
36C25023B0024 0002.pdf PDF
553-21-106 Pre-Bid Site Visit Agenda_.pdf PDF
553-21-106 Pre-bid Site Visit Attendance Log.pdf PDF
36C25023B0024 0001.pdf PDF
36C25023B0024 0001.docx DOCX document
_36C25023B0024_.pdf PDF
Specifications - Project 553-21-106 - Volume I.pdf PDF
Drawings - Project 553-21-106.pdf PDF
Specifications - Project 553-21-106 - Volume II.pdf PDF
S02 - RFI Form 553-21-106.pdf PDF
S02 - Contractor EMR Certification Form - 553-21-106.pdf PDF
WD GDN MI20230101 Mod 2 -02-24-2023 - Building - Wayne County.pdf PDF
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ARCHITECT’S ADDENDUM

Project: Insulate Exterior Walls &

Replace Windows

Owner: John D Dingell VA Medical Center

4646 John R. St., Detroit, MI. 48201

To:

(Client) c/o: Kristopher Steis

Architect’s Addendum No: 001

Date of Issuance: January, 31, 2023

Architect: Guidon Design Inc.

Contract For: Bid Architect’s Project

No: 18.1008.15

Description:

Replace Plan Notes with the attached plan notes on the following sheets:

AE101

AE102

AE103

AE104

AE105

AE106

AE107

1. EXTERIOR: EXISTING BACKER ROD AND SEALANT TO BE REMOVED. NEW

BACKER ROD AND SEALANT TO BE INSTALLED ALONG PERIMETER OF

STOREFRONT.

INTERIOR: EXISTING FIN TUBE COVER TO BE REMOVED AND DISPOSED OF.

FIN TUBE TO BE CLEANED/COMBED. WINDOW JAMBS TO BE FILLED WITH

SPRAY FOAM INSULATION. HOLES IN JAMB TO BE PATCHED AND PAINTED TO

MATCH EXISTING. NEW FIN TUBE COVER TO BE INSTALLED

(SEE SPEC 23 82 00 CHECKLIST). RESILENT BASE AT FIN TUBE COVER

LOCATION TO BE REMOVED AND REPLACED. RESILIENT BASE TO MATCH

EXISTING. SEE A/AE600 FOR EXTENT OF RESILIENT BASE REPLACEMENT.

BLAST RESISTANT FILM TO BE INSTALLED ON INTERIOR OF WINDOWS

ON FIRST FLOOR ONLY. SEE SPEC SECTION 08 80 00 FOR RESISTANT FILM.

PLAN NOTES

EXTERIOR: EXISTING BACKER ROD AND SEALANT TO BE REMOVED. NEW

BACKER ROD AND SEALANT TO BE INSTALLED ALONG PERIMETER OF

STOREFRONT / CURTAIN WALL.

INTERIOR: EXISTING GRILLE VENT TO BE REMOVED. FIN TUBE TO BE

CLEANED/COMBED. GRILLE TO BE REINSTALLED. WINDOW JAMBS TO BE

FILLED WITH SPRAY FOAM INSULATION. HOLES IN JAMB TO BE PATCHED AND

PAINTED TO MATCH EXISTING. BLAST RESISTANT FILM TO BE INSTALLED ON

INTERIOR OF WINDOWS ON FIRST FLOOR ONLY. SEE SPEC SECTION 08 80 00

FOR RESISTANT FILM.

2.

S ON FIRST FLOOR ONLY. SEE SPEC SECTION 08 80 00

FOR

RESISTANT FILM.

FOR RESISTANT FILM.

EXTERIOR: EXISTING BACKER ROD AND SEALANT TO BE REMOVED. NEW

BACKER ROD AND SEALANT TO BE INSTALLED ALONG PERIMETER OF

STOREFRONT.

INTERIOR: WINDOW JAMBS TO BE FILLED WITH SPRAY FOAM INSULATION.

HOLES IN JAMB TO BE PATCHED AND PAINTED TO MATCH EXISTING.

EXTERIOR: EXISTING BACKER ROD AND SEALANT TO BE REMOVED. NEW

BACKER ROD AND SEALANT TO BE INSTALLED ALONG PERIMETER OF

STOREFRONT.

INTERIOR: EXISTING CURVED/SEGMENTED FIN TUBE COVER TO BE

REMOVED AND DISPOSED OF. FIN TUBE TO BE CLEANED/COMBED. WINDOW

JAMBS TO BE FILLED WITH SPRAY FOAM INSULATION. HOLES IN JAMB TO BE

PATCHED AND PAINTED TO MATCH EXISTING. NEW CURVED/SEGMENTED

FIN TUBE COVER TO BE CONSTRUCTED AND INSTALLED TO MATCH EXISTING

DIMENSIONS. RESILENT BASE AT FIN TUBE COVER LOCATION TO BE

REMOVED AND REPLACED. RESILIENT BASE TO MATCH EXISTING. SEE

A/AE600 FOR EXTENT OF RESILIENT BASE REPLACEMENT. BLAST RESISTANT

FILM TO BE INSTALLED ON INTERIOR OF WINDOW AT FIRST FLOOR

STOREFRONT LOCATIONS.

EXTERIOR: BLAST RESISTANT FILM TO BE INSTALLED ON INTERIOR OF

WINDOWS ON FIRST FLOOR ONLY. SEE SPEC SECTION 08 80 00

FOR

RESISTANT FILM.

S

RESISTANT FILM.

3.

4.

5.