This document is an architect's addendum providing revised notes for plans to insulate exterior walls and replace windows at the John D Dingell VA Medical Center in Detroit, Michigan. The addendum specifies that existing backer rod and sealant will be removed and new backer rod and sealant installed around storefront perimeters. Interior finishes such as fin tube covers and resilient base will be removed and replaced. Window jambs will be filled with spray foam insulation and holes patched and painted to match existing. Blast resistant film will be installed on interior windows of the first floor only, as outlined in specification section 08 80 00. The related federal contract opportunity is solicitation number 36C25023B0024 from the Department of Veterans Affairs for insulating exterior walls, replacing windows, and completing associated interior work at the medical center.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25023B0024 0002.pdf | ||
| 553-21-106 Pre-Bid Site Visit Agenda_.pdf | ||
| 553-21-106 Pre-bid Site Visit Attendance Log.pdf | ||
| 36C25023B0024 0001.pdf | ||
| 36C25023B0024 0001.docx | DOCX document | |
| _36C25023B0024_.pdf | ||
| Specifications - Project 553-21-106 - Volume I.pdf | ||
| Drawings - Project 553-21-106.pdf | ||
| Specifications - Project 553-21-106 - Volume II.pdf | ||
| S02 - RFI Form 553-21-106.pdf | ||
| S02 - Contractor EMR Certification Form - 553-21-106.pdf | ||
| WD GDN MI20230101 Mod 2 -02-24-2023 - Building - Wayne County.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARCHITECT’S ADDENDUM
Project: Insulate Exterior Walls &
Replace Windows
Owner: John D Dingell VA Medical Center
4646 John R. St., Detroit, MI. 48201
To:
(Client) c/o: Kristopher Steis
Architect’s Addendum No: 001
Date of Issuance: January, 31, 2023
Architect: Guidon Design Inc.
Contract For: Bid Architect’s Project
No: 18.1008.15
Description:
Replace Plan Notes with the attached plan notes on the following sheets:
AE101
AE102
AE103
AE104
AE105
AE106
AE107
1. EXTERIOR: EXISTING BACKER ROD AND SEALANT TO BE REMOVED. NEW
BACKER ROD AND SEALANT TO BE INSTALLED ALONG PERIMETER OF
STOREFRONT.
INTERIOR: EXISTING FIN TUBE COVER TO BE REMOVED AND DISPOSED OF.
FIN TUBE TO BE CLEANED/COMBED. WINDOW JAMBS TO BE FILLED WITH
SPRAY FOAM INSULATION. HOLES IN JAMB TO BE PATCHED AND PAINTED TO
MATCH EXISTING. NEW FIN TUBE COVER TO BE INSTALLED
(SEE SPEC 23 82 00 CHECKLIST). RESILENT BASE AT FIN TUBE COVER
LOCATION TO BE REMOVED AND REPLACED. RESILIENT BASE TO MATCH
EXISTING. SEE A/AE600 FOR EXTENT OF RESILIENT BASE REPLACEMENT.
BLAST RESISTANT FILM TO BE INSTALLED ON INTERIOR OF WINDOWS
ON FIRST FLOOR ONLY. SEE SPEC SECTION 08 80 00 FOR RESISTANT FILM.
PLAN NOTES
EXTERIOR: EXISTING BACKER ROD AND SEALANT TO BE REMOVED. NEW
BACKER ROD AND SEALANT TO BE INSTALLED ALONG PERIMETER OF
STOREFRONT / CURTAIN WALL.
INTERIOR: EXISTING GRILLE VENT TO BE REMOVED. FIN TUBE TO BE
CLEANED/COMBED. GRILLE TO BE REINSTALLED. WINDOW JAMBS TO BE
FILLED WITH SPRAY FOAM INSULATION. HOLES IN JAMB TO BE PATCHED AND
PAINTED TO MATCH EXISTING. BLAST RESISTANT FILM TO BE INSTALLED ON
INTERIOR OF WINDOWS ON FIRST FLOOR ONLY. SEE SPEC SECTION 08 80 00
FOR RESISTANT FILM.
2.
S ON FIRST FLOOR ONLY. SEE SPEC SECTION 08 80 00
FOR
RESISTANT FILM.
FOR RESISTANT FILM.
EXTERIOR: EXISTING BACKER ROD AND SEALANT TO BE REMOVED. NEW
BACKER ROD AND SEALANT TO BE INSTALLED ALONG PERIMETER OF
STOREFRONT.
INTERIOR: WINDOW JAMBS TO BE FILLED WITH SPRAY FOAM INSULATION.
HOLES IN JAMB TO BE PATCHED AND PAINTED TO MATCH EXISTING.
EXTERIOR: EXISTING BACKER ROD AND SEALANT TO BE REMOVED. NEW
BACKER ROD AND SEALANT TO BE INSTALLED ALONG PERIMETER OF
STOREFRONT.
INTERIOR: EXISTING CURVED/SEGMENTED FIN TUBE COVER TO BE
REMOVED AND DISPOSED OF. FIN TUBE TO BE CLEANED/COMBED. WINDOW
JAMBS TO BE FILLED WITH SPRAY FOAM INSULATION. HOLES IN JAMB TO BE
PATCHED AND PAINTED TO MATCH EXISTING. NEW CURVED/SEGMENTED
FIN TUBE COVER TO BE CONSTRUCTED AND INSTALLED TO MATCH EXISTING
DIMENSIONS. RESILENT BASE AT FIN TUBE COVER LOCATION TO BE
REMOVED AND REPLACED. RESILIENT BASE TO MATCH EXISTING. SEE
A/AE600 FOR EXTENT OF RESILIENT BASE REPLACEMENT. BLAST RESISTANT
FILM TO BE INSTALLED ON INTERIOR OF WINDOW AT FIRST FLOOR
STOREFRONT LOCATIONS.
EXTERIOR: BLAST RESISTANT FILM TO BE INSTALLED ON INTERIOR OF
WINDOWS ON FIRST FLOOR ONLY. SEE SPEC SECTION 08 80 00
FOR
RESISTANT FILM.
S
RESISTANT FILM.
3.
4.
5.