Child Development Center (CDC)

SECTION 01 10 10

8/4/2009

15.5.1 Unshielded Twisted Pair (UTP) Tests: All metallic cable pairs shall be tested for proper identification and continuity. All opens, shorts, crosses, grounds, and reversals shall be corrected. Correct color coding and termination of each pair shall be verified in the communication room and at the outlet. All UTP circuits shall be tested using a test set that meets the Class II accuracy requirements of EIA/TIA-568- B.2. Testing shall use the Basic Link Test procedure of EIA/TIA-568-B.2. Cables and connecting hardware that contains failed circuits shall be replaced and retested to verify the standards are met. All installed UTP cable shall be tested for attenuation loss at 250 megahertz and results reported in dB. All installed UTP cable shall be tested in both directions (TC to outlet, outlet to TC) for near end cross talk (NEXT) and far end cross talk (FEXT) at 250 megahertz and results reported. All of the pairs in each installed copper backbone cable shall be tested for continuity.

15.5.2 Fiber Optic Cable: Attenuation tests shall be performed from both ends of each circuit. Connectors shall be visually inspected for scratches, pits or chips and terminations shall be remade if any of these conditions exist. Each circuit leg and complete circuit shall be tested for insertion loss at 850, and 1310 nm. All multimode fiber optic testing shall be in compliance with EIA/TIA-568-B.3.

15.5.3 Test Reports: Contractor shall provide test report in booklet form with witness signatures verifying execution of tests. Reports shall show the field tests performed to verify compliance with the specified performance criteria. Test reports shall include record of the physical parameters verified during testing. Test report shall be submitted within 7 days after completion of testing to the Contracting Officer’s Representative.

15.6 INTERCOMMUNICATIONS SYSTEM

Provide two way hands free communication from room to room and from room to master station. Provide master station at reception area and remote units at:

- Administrative Offices

- Child Activity Rooms

- Training Room

- Outdoor Play Environments

- Kitchen

- Laundry Rooms

- Break Room

- Front Desk

- Isolation Room

All remote units shall be wall mounted, located near a room entrance and at 54-inches above finished floor.

Outdoor play environment units shall be weatherproof and located adjacent to the emergency supply cabinet.

System shall have controls that allow private conversations.

Main Door Intercom: Provide an-after-hours, stand alone intercom system from the main entrance to the attending personnel location which may be at a location other then the reception area.