This document includes a federal contract opportunity for the installation of a backup generator at a U.S. Geological Survey facility. The contractor shall install a generator set, automatic transfer switches, electrical service disconnect switch, concrete mounting pad, and underground conduit and wiring from the generator set to the transfer switch. The magnitude of construction is estimated between $250,000 and $500,000. A Request for Proposal will be issued on August 16, 2021 with proposals due on or around September 15, 2021. A bid guarantee is required and bonds will be required. All contractors are strongly encouraged to attend a mandatory site visit. The North American Industry Classification System code is 238210 with a size standard of $16.5 million. This acquisition is set aside for small businesses. To be eligible for award, vendors must be registered in the System for Award Management. Proposals must be submitted electronically to the point of contact by the due date.

View the file

Other files for this federal contract opportunity

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2401 Bernadette Drive, Suite 201 Columbia, Missouri 65203

573 - 234 - 4492 phone www.j-squaredeng.com

SHEET NUMBER

SHEET TITLE

J2 PROJECT No: J20379

J2 DESIGN: JAP

ISSUE TITLE DATE

M ec ha ni ca l -

E lec tri ca l - P lu m bi ng

D es ign D ra wi ng s f or

US

GS

G en er at or

E

N ew

H av en R d Co lu m bi a, Bo on e C ou nt y, M O

Feb. 3rd, 2021James Watson, P.E.

PE-2015017071

MO Certificate of Authority # 2018029680

E101

POWER PLAN

POWER RISER KEY NOTES:

EXISTING 240V, 3PH, 800 AMP MCB PANEL1

POWER PLAN SYMBOL LEGEND

TIE INTO EXISTING

CIRCUIT WIRING

PX-XX CIRCUIT TAG

SITE POWER PLAN

SCALE: 1" = 20 ft

EXISTING CONDUITS

EXISTING TRANSFORMER

BANK ON POLE

NEW 120/240V, 1PH,

1200 AMP, SERVICE RATED

TRANSFER SWITCH

NEW 240V, 3PH,

800 AMP, SERVICE RATED

TRANSFER SWITCH

NEW 240V, 3PH,

500 KW GENERATOR ON

NEW CONCRETE PAD

EXISTING 120/240V, 1PH, 1200 AMP MCB PANEL.2

NEW 1200 AMP, 120/240V, 1PH, NEMA 3R SERVICE RATED TRANSFER SWITCH WITH SWITCHED

NEUTRAL.

NEW 800 AMP, 240V, 3PH DELTA , NEMA 3R SERVICE RATED TRANSFER SWITCH WITH SWITCHED

NEUTRAL.

INTERCEPT (2) EXISTING 4" UNDERGROUND CONDUIT & CONDUCTORS. PULL BACK/INSTALL NEW CONDUIT & CONDUCTORS NEEDED TO CONNECT TO NEW TRANSFER SWITCH. EXISTING 4" CONDUITS

HAVE (3) #500 MCM COPPER CONDUCTORS.

INTERCEPT (4) EXISTING 3" UNDERGROUND CONDUITS & CONDUCTORS. PULL BACK/ INSTALL NEW CONDUIT & CONDUCTORS AS NEEDED TO CONNECT NEW TRANSFER SWITCH. EXISTING 3" CONDUITS

HAVE (3) #350 COPPER.

EXISTING TRANSFORMER

BANK ON POLE

800 1200

POWER RISER

1 2

NEW 120/240V, WYE, 3PH, 500 KW GENSET

EQUAL TO CAT #C15 PG AM WITH 48 HOURS

RUN TIME DUEL WALL BELLY TANK &

WEATHER PROOF ENCLOSURE

4 3

6 6

5 5

ELECTRICAL SPECIFICATIONS

1. GENERAL

1.1. THE ENTIRE ELECTRICAL SYSTEM SHALL BE CONTINUOUSLY GROUNDED. EVERY BRANCH

CONDUIT SHALL INCLUDE A GREEN GROUND CONDUCTOR SIZED PER NEC.

1.2. ARC-FAULT CIRCUITS SHALL BE RUN WITH A DEDICATED NEUTRAL AS REQUIRED BY

MANUFACTURER.

1.3. PROVIDE PERMANENT ARC-FLASH LABEL AFFIXED TO EVERY DISCONNECT AND PANEL.

1.4. PROVIDE TYPE WRITTEN PANEL SCHEDULE FOR EACH PANEL.

2. MATERIALS

2.1. CONDUIT & CONDUCTORS

2.1.1. ALL CONDUCTORS SIZES INDICATED ON PLANS ARE COPPER UNLESS NOTED

OTHERWISE.

2.1.2. ABOVE GRADE CONDUCTORS SHALL BE THHN COPPER. BELOW GRADE CONDUCTORS

SHALL BE XHHW-2.

2.1.3. MINIMUM CONDUCTOR SIZE SHALL BE #12 UNLESS NOTED OTHERWISE. 120V, 20 AMP

CIRCUITS WITH CONDUCTOR LENGTH GREATER THAN 100' SHALL BE MINIMUM #10.

ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR MEASURING ACTUAL CONDUCTOR

LENGTH AND INCREASING CONDUCTOR SIZE TO COMPENSATE FOR VOLTAGE DROP AS

REQUIRED BY NEC.

2.1.4. RIGID GALVANIZED OR SCHEDULE 40 PVC CONDUIT SHALL BE USED FOR SERVICE

WIRING, BELOW GRADE INSTALLATIONS, OR WHERE EXPOSED TO WEATHER.

2.1.5. IN APPLICATIONS OTHER THAN THOSE LISTED IN 2.1.4, EMT OR MC CABLE IS

ACCEPTABLE. WHERE CONDUCTORS ARE PROTECTED FROM DAMAGE, ENCLOSED IN

BUILDING MATERIALS, AND CONSTRUCTION IS OF A PERMITTED TYPE, NM CABLE MAY

BE USED.

2.2. DEVICES

2.2.1. CONTRACTOR TO PROVIDE J-BOXES, COVER PLATES, AND ANY ACCESSORIES REQUIRED

TO PROVIDE A COMPLETE SYSTEM. SEE ARCHITECTURAL PLANS FOR DEVICE COLORS.

2.2.1. DUPLEX RECEPTACLES SHALL BE TAMPER RESISTANT, 20 AMP, EQUAL TO LEVITON

CR20.

2.2.2. TOGGLE WALL SWITCHES SHALL BE EQUAL TO LEVITON CS120-2

2.2.3. DIMMER SWITCHES SHALL BE TESTED WITH FIXTURES AND LAMPS FOR

COMPATIBILITY.

3. EMERGENCY LIGHTING

3.1. THE BRANCH CIRCUIT FEEDING THE EMERGENCY FIXTURE SHALL BE THE SAME BRANCH

CIRCUIT AS THAT SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD

OF ANY LOCAL SWITCHES.

120/240V, 1PH BREAKER.7

240 DELTA 3PH BREAKER. GENERATOR MANUFACTURER TO RETAP IN FIELD TO GENERATE 240

DELTA FOR THIS BREAKER.

8 7

(2) 4" UNDERGROUND PVC CONDUIT WITH (3) #500 MCM & (1) # 1/0 EQ. GRD.COPPER CONDUCTORS IN

EACH.

(4) 3" UNDERGROUND PVC CONDUIT WITH (3) #350 CU & (1) 3/0 EQ. GRD IN EACH10

TWO EXISTING 4" UNDERGROUND PVC CONDUIT WITH NEW CONDUCTORS. CONDUCTORS SHALL BE

(4) #500 MCM & (1) 1/0 EQ. GRD.COPPER CONDUCTORS IN EACH CONDUIT.

FOUR EXISTING 3" UNDERGROUND PVC CONDUITS WITH NEW CONDUCTORS. NEW CONDUCTORS

SHALL BE (3) #350 CU & (1) 3/0 EQ. GRD IN EACH CONDUIT.

SEPARATE NEUTRALS & GROUNDS.13

13 13

#6 TO 8' GROUND ROD AND #3/0 TO

GROUNDING ELECTRODE SYSTEM INSIDE OF

BUILDING WITH 800 AMP & 1200 AMP PANEL.

REFERENCED CODES IN EFFECT

2017 NATIONAL ELECTRIC CODE Sheet List Table

Sheet # Sheet Title

E501 ELECTRICAL DETAILS & SCHEDULES

GENERATOR PAD - PLAN VIEW

SCALE: 1/4" = 1'-0"

18'-0"

8'- 0"

F1

FROST FOOTING SECTION

SCALE: 1/2" = 1'-0"

F1

2'- 6"

8"

1'-0"

FINISH GRADE

(3) #4 REBAR CONT.

EQ. EQ.

#4 REBAR @ 2'-0" O.C.

FIELD BENT INTO SLAB

2" CLR.

6" SLAB W/ #4 REBAR

EACH WAY @ 1'-6" O.C.

TYP. @

PERIMETER

SAW CUT

CONTRACTOR WILL NEED TO RUN A NEW 60 AMP 3 POLE CIRCUIT FROM EXISTING 240V 3PH PANEL

INSIDE OF BUILDING BACK TO GENERATOR FOR BATTERY CHARGER AND BLOCK HEATER INSIDE

EXISTING 4" UNDERGROUND CONDUIT. CONTRACTOR TO INCLUDE COST OF INSTALLING NEW

BREAKER.

3/0 GROUNDING ELECTRODE.