Attachment D.3 Eaton Study.pdf
PDF 8 MB Posted
- Attached to
- J059--Triannual Electrical Testing BCVAMC Federal contract opportunity
- Solicitation number
- 36C25022Q0675
About this file
This solicitation is for triannual electrical testing services at the Battle Creek Veterans Affairs Medical Center in Michigan. The requirement includes testing of all electrical distribution equipment and systems to ensure safety and performance. The solicitation is a 100% verified service-disabled veteran-owned small business set-aside issued by the Department of Veterans Affairs Veterans Health Administration Networks 10. The anticipated award date is unspecified. Pricing terms and contract duration are not discussed in the provided documentation.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment D.2 SOW Appendices A-K.pdf | ||
| 36C25022Q0675.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Electrical Services & Systems 5265 W River Dr. NE Suite 200
Comstock Park, MI 49321 (616)-559-3514
GENERAL ORDER NUMBER: GOEIN675.001
REPORT NUMBER: TQSIIN675
SUBMITTED BY: B. BRIEGEL
www.EatonElectrical.com
SHORT-CIRCUIT, PROTECTIVE DEVICE COORDINATION, &
ARC FLASH INCIDENT ENERGY ANALYSIS
FOR
VETERANS AFFAIRS MEDICAL CENTER - BATTLE CREEK
FINAL REPORT
BATTLE CREEK, MI
REVISION 2
OCTOBER 2017
http://www.eatonelectrical.com/
REVISION HISTORY
Rev # Issued Revision / Modification Description
- 12/2009 Initial study report issue 1 03/2010 Post report comments applied
2 08/2017
Updated existing study to include expansions and renovations of the facility including, but not limited to Buildings 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 12, 13 ,14, 17, 20, 22, 25, 26 ,27, 28, 29, 30, 39, 82, 83, 84, 101, 134, 135, 136, 138, 141, 145, 157, 169, and 300.
All of the building’s equipment, existing and new, short-circuit, coordination, and arc flash results were re-evaluated.
VA Battle Creek i
TABLE OF CONTENTS
EXECUTIVE SUMMARY ......................................................................................... 1-1 1.0
1.1 General ......................................................................................................... 1-1
1.2 Objectives ..................................................................................................... 1-1
1.3 Results and Recommendations .................................................................... 1-1
SHORT-CIRCUIT ANALYSIS .................................................................................. 2-1 2.0
2.1 General ......................................................................................................... 2-1
2.2 Objectives ..................................................................................................... 2-3
2.3 Equipment Evaluation ................................................................................... 2-4
2.4 Short-Circuit Results ..................................................................................... 2-5
PROTECTIVE DEVICE COORDINATION STUDY .................................................. 3-1 3.0
3.1 General ......................................................................................................... 3-1
3.2 Objectives ..................................................................................................... 3-1
3.3 Codes and Standards ................................................................................... 3-1
3.4 Coordination Data ......................................................................................... 3-2
3.5 Coordination Results .................................................................................... 3-2
3.6 Time-Current Characteristic Plots ................................................................ 3-4
RECOMMENDED PROTECTIVE DEVICE SETTINGS ........................................... 4-1 4.0
ARC FLASH INCIDENT ENERGY ANALYSIS ....................................................... 5-1 5.0
5.1 General ......................................................................................................... 5-1
5.2 Objectives ..................................................................................................... 5-2
5.3 Arc Flash Incident Energy Analysis Results ................................................. 5-3
5.4 Arc Flash Summary Table Heading Descriptions ......................................... 5-5
5.5 Arc Flash Labels ........................................................................................... 5-6
5.6 Arc Flash Incident Energy Analysis Recommendations ............................... 5-7
SYSTEM DATA ........................................................................................................ 6-1 6.0
SHORT-CIRCUIT INPUT REPORT ......................................................................... 7-1 7.0
SHORT-CIRCUIT RESULTS ................................................................................... 8-1 8.0
UTILITY DATA ......................................................................................................... 9-1 9.0
APPLICABLE CODES AND STANDARDS .......................................................... 10-1 10.0
ONE-LINE DIAGRAM INDEX ................................................................................ 11-1 11.0
APPENDIX ............................................................................................................. 12-1 12.0
12.1 Picture of Damaged Cable in MDP-5 in Building 2 ..................................... 12-2
12.2 Picture of Damaged Disconnect for Panel 003 PANEL 3-1 in Building 3 ... 12-3
12.3 Meeting Minutes ......................................................................................... 12-4
VA Battle Creek ii
EXECUTIVE SUMMARY 1.0
1.1 General
This summary report contains the results of analyses performed on the electrical distribution system for the Veterans Affairs Medical Center in Battle Creek, MI. The purpose of this study is to evaluate the new additions and existing electrical system.
System data and necessary modeling assumptions are provided under Section 6.0.
1.2 Objectives
1. Short-Circuit Analysis
Perform a short-circuit study on the electrical distribution system shown in order to determine the available fault current at pertinent locations throughout the distribution system. The scope of the study includes:
• Analysis begins at the incoming 4.8 kV utility service to the hospital and 14.4 kV service to Building 145, the laundry building, and continues through the medium and low voltage substations, and ends at the low voltage panelboards and motor control centers throughout the campus.
The available fault currents determined by the short-circuit study will be used in the electrical distribution analyses.
2. Equipment Evaluation
Evaluate the short-circuit ratings of new and existing protective devices and other distribution equipment throughout the campus.
3. Coordination Study
Review the existing system overcurrent protection and coordination. Where applicable, provide suggestions for improvement. Develop time-current coordination plots to derive coordinated settings for new protective devices.
4. Arc Flash Analysis
Perform an arc flash incident energy analysis per NFPA 70E on the electrical distribution system as per Eaton’s scope of work.
An incident energy analysis is defined by NFPA 70E to be a component of an arc flash risk assessment used to predict the incident energy of an arc flash for a specified set of conditions.
5. Recommendations
Provide specific recommendations for improving the electrical distribution system performance and correcting any deficiencies found by the studies.
1.3 Results and Recommendations
1. Short-Circuit Study
The system was modeled for worst-case fault currents. Short-circuit currents were calculated for a three-phase bolted fault and single-line-to-ground fault at each bus
VA Battle Creek 1-1 shown on the one-line diagrams found in Section 11.0. See Section 2.0, Section 7.0, and Section 8.0 for more information.
2. Equipment Evaluation
The Equipment Evaluation is based on the power system worst-case short-circuit current configuration. The short-circuit ratings of protective devices and other distribution equipment are evaluated in Section 2.0, Table 2.1.
In summary of Table 2.1, specific equipment has failed the equipment evaluation and are considered overdutied. It is recommended that the overdutied panelboards be reviewed for breaker and/or panelboard replacement to comply with the short-circuit current ratings required.
The short-circuit withstand ratings of low voltage disconnect switches are not evaluated in this study. Care should be taken in order to ensure that these devices are applied within their UL listed short-circuit withstand ratings. The typical withstand ratings for Eaton disconnect switches (safety switches) range from 10,000A to 200,000A for certain fused types.
See Section 2.0 for detailed analysis and evaluation results.
3. Coordination Study
The time-current coordination plots of the protective overcurrent devices are shown in Section 3.0. In developing the device settings, consideration was given to the isolation of faults, protection of cables, and protection of transformers.
Efforts were made to provide the best coordination possible with the new and existing protective devices. It should be understood that coordination between two instantaneous trip units cannot be achieved for fault levels above the instantaneous pickup of the upstream device. There is some overlapping of curves that cannot be avoided.
All of the adjustable low voltage electronic trip and thermal magnetic circuit breakers and medium voltage equipment should be tested and adjusted according to the recommended settings given in Section 4.0.
4. Protective Device Settings
Settings for the protective devices at all medium and low voltage protective devices should be set as shown and recommended in Section 4.0.
The referenced plot illustrates the coordination of the listed device with the relevant “upstream” and “downstream” protective devices.
5. Arc Flash Incident Energy Analysis
Details of the arc flash incident energy analysis are shown in Section 5.0. Please note for this study, the arc flash hazard has been calculated by performing an incident energy analysis. The results of this study can be used by qualified workers to determine the arc flash boundary and select appropriate arc flash PPE as part of an overall arc flash risk assessment. NFPA 70E Table H.3(b) provides guidance on the selection of arc rated clothing and other PPE based on the results of an incident energy analysis. It is the responsibility of the employer and qualified person(s) to conduct an overall arc flash risk assessment as detailed in NFPA 70E-2015 Article
VA Battle Creek 1-2
130.5 before the commencement of work on electrical equipment. The risk associated with performing energized electrical work will vary based on the work being performed as well as the condition of the equipment and other factors that can be best determined by a qualified person in the field.
In summary, there are several locations that have incident energy levels that are above 40 cal/cm2, refer to Section 5.0 for detailed information.
According to NFPA 70E Article 130.7(A), Informational Note 3, it may be necessary to place greater emphasis on establishing an electrically safe work condition when working within the limited approach boundary at locations where the incident energy exceeds 40 cal/cm2. The greater emphasis is due to additional hazards created from blast pressure associated with a possible arc. The PPE requirements outlined in NFPA 70E only address the thermal hazards associated with arc flash events and do not provide protection against other possible physical trauma resulting from an arc flash event. See NFPA 70E Article 120 for details on establishing an electrically safe work condition.
a) Reducing Incident Energy Levels: The calculated incident energy at a particular location is dependent on three main factors: short-circuit current, distance, and time. These three factors directly affect the incident energy in the following manner:
Short-circuit current: The short-circuit current for a given power system is dependent on the system impedance and source fault current, and cannot be easily reduced.
Distance: IEEE Std 1584™ provides a table with typical working distances.
Increasing the working distance reduces the amount of incident energy that reaches the worker; however it becomes difficult to perform many work tasks with an increased working distance, therefore, this is not an optimal solution for most cases.
Time: The incident energy decreases when reducing the exposure time of the arc. This exposure time is directly related to the clearing time of the protective device(s) which feed the fault location.
Based on the preceding summary, arc flash mitigation techniques are most effective and feasible when they involve reducing the arc exposure time. In many locations, the setting of the protective device can be adjusted in order to decrease the interrupting time, resulting in a decreased incident energy.
However, in this study, settings for protective devices have not been adjusted to reduce incident energy if the chance of nuisance trips within critical circuits is introduced.
The other option involving reducing the arc exposure time is to consider equipment modifications and upgrades. Several solutions include upgrading trip units, installing “maintenance switches”, and using relays with multiple settings groups. Each specific location needs to be analyzed to determine which reduction method is best employed.
NFPA 70E requires that the arc flash analysis be updated:
• Every five years (at minimum)
VA Battle Creek 1-3
• When the electrical system is modified, including renovations, additions, or subtractions to the system
6. Testing and Preventative Maintenance
The 2015 edition of NFPA 70E Section 205.3 and 205.4 requires that regularly scheduled testing and preventative maintenance is performed to ensure that the electrical distribution equipment continues to perform at an optimum level. Testing should entail primary injection testing of all circuit breakers to verify proper tripping ranges, contact resistance testing, insulation resistance testing and complete switchgear and transformer cleaning and inspection. Refer to NFPA-70B for specific types of testing and interval recommendations. The industry generally performs breaker testing every 3-5 years.
7. Predictive Diagnostics Using Continuous Partial Discharge Measurements
Eaton recommends conducting Continuous Partial Discharge measurements on most medium voltage power transformers, bus ducts, switchgear, motors, generators, terminations, and splices of transmission and distribution cables. Partial Discharge (PD) analysis is a non-invasive, online method of collecting, filtering, and evaluating PD occurring in electrical apparatus. The goals are:
• To detect partial discharges as a result failing or compromised insulation
• To analyze the partial discharge activity, and if an insulation defect is detected:
• Make conclusions as to the severity of the defect.
• Advise as to possible defect locations and possible cause(s) of the defect.
• Advise as to urgency of inspection.
• Suggest preventive measures both immediate and long term.
Electrical insulation is very important to monitor as it defines a major item in the reliability of electrical machines. Continuous Partial Discharge on-line monitoring using the Eaton InsulGard™ is the most sensitive and reliable method for detecting failing insulation. PD monitoring when used in conjunction with Eaton’s RM™ system offers customers the added benefit of prompt expert analysis and recommendation.
8. National Electric Code (NEC) 2017 Violations
a) MDP-5 feeding panel 002 RP-CB5 in Building 2 contains a damaged cable that appears to have flashed over. It is recommended that that cable is replaced immediately with the same size #4/0 copper conductor. Refer to section 12.1 in the Appendix for a picture of the damaged cable.
b) The disconnect for panel 003PANEL 3-1 in the crawl space of Building 3 is rusted over which may effect the integrity of the enclosure and its feeds. It is recommended the disconnect is replaced. Refer to section 12.2 in the Appendix for a picture of the damaged disconnect.
c) According to NEC 240.21(B), the tap in Building 28 that feeds the pipe and carpenter shop panels are undersized. The carpenter shop feed also violates the 25’ length specified in 240.21(B)(2). It is recommended a 175A fused disconnect is added within 25’ of the junction box feeding the carpenter shop panels. Also, it
VA Battle Creek 1-4 is recommended the 028 PANEL A DISC fuse is replaced with a 175A fuse to protect the cable.
d) According to NEC 240.21(B), the tap in Building 30 that feeds 030 DISC FWP requires a disconnect within 25’ of 030 ATS-30-1. The disconnect must be sized to 200A to protect the cable.
e) Undersized Cables Per NEC Table 310.16 based on 60° & 75° lugs, copper
• The following list of cables are undersized per the existing system model, new system locations that were verified in the field, or cables specified in design one lines where cables could not be field verified. Efforts were made to protect the cable by setting the upstream.
Building Fed From Feeding To # of Sets Size Recommended # of Sets
Recommended Size
002 T-002 D 002 MDP 1 2 #500 2 #600
003 T-003 003 MDP-3 NORM
DISC 1 #500 1 #600
004 T-004 004 MDP 1 #350 2 #350
005 T-005 005 SWBD-1 5 #750 6 #750
005 005 DP-A 005 AHU-5B-1 1 #4 1 #3
017 T-023 017 MDP-17 MAIN 1 #500 1 #600
020 T-029 020 MDP-20 MAIN 1 #500 1 #600
025 T-025 025 MDP-25 1 #2/0 2 #250
026 T-026 026 MDP 2 #350 2 #600
027 027 PNL JMJ 028 AC SHOP PNL 1 #4 1 #3
030 171 GEN-030 171 DISC ATS-30-2-E 1 #3/0 1 #4/0
030 171 DISC ATS-30-
2-E 030 ATS-30-2 1 #3/0 1 #4/0
030 030 ATS-30-2 030 PNL PP1 1 #3/0 1 #4/0
030 030 ATS-30-1 030 DISC FWP 1 #3/0 1 #4/0
039 039 MDP-39 039 PANEL A 1 #3/0 1 #4/0
039 039 MDP-39 039 ATS-LP-B 1 #500 1 #600
039 039 ATS-LP-B 039 LP-B 1 #500 1 #600
039 039 LP-A 039 PANEL DD 1 #1/0 1 #3/0
039 039 LP-A 039 PANEL AA 1 #1/0 1 #3/0
082 082 MDP-82 082 PANEL LP-L 1 #400 1 #500
082 082 MDP-82 082 ATS-82-2-N 1 #1/0 1 #3/0
082 082 ATS-82-2-N 082 EC-82 1 #1/0 1 #3/0
082 082 LS-82 161 PNL LP 1 #4 1 #3
083 PANEL KK 083 AC PANEL 19E 1 #4 1 #3
084 T-084 084 MDP-200 3 #500 3 #600
084 084 84-MCC-1 084 MTR CH-1 2 #4/0 3 #3/0
084 084 84-MCC-1 084 PANEL B-1 1 #1/0 1 #3/0
084 084 PANEL B-1 084 DISC AC-1 1 #1/0 1 #2/0
VA Battle Creek 1-5
Building Fed From Feeding To # of Sets Size Recommended # of Sets
Recommended Size
084 084 PANEL B-1 084 DISC AC-2 1 #1/0 1 #2/0
134 134 MDP-134 134 PANEL C 1 #8 1 #6
136 136 MDP-136 T-136-4 1 #1 1 #2/0
145 PPN-145-101 145-EXT 1 1 #3 1 #1/0
145 PPN-145-101 145-EXT 2 1 #3 1 #1/0
145 PPN-145-102 145-COMP-1 (FMR
HA2) 1 #4 1 #2
145 PPN-145-102 145-COMP-2 (FMR
HA2) 1 #4 1 #2
145 TN-145-106 LPE-145-102 1 #6 1 #4
300 300 DQH-2 300 CT-1 1 #4 1 #2
300 300 DQH-2 300 CT-2 1 #4 1 #2
300 300 DQH-2 300 CP-1 1 #2/0 1 #3/0
300 300 DQH-2 300 CP-2 1 #2/0 1 #3/0
300 300 T-SL-1 300 SL-1 1 #4 1 #3
• Existing feed in Building 5 from 005 MDP-1 to 005 MDP-1A is recommended to have a protective device sized up to 1,520A installed in 005 MDP-1 to protect the cable.
• The #1/0 cables from 082 BKR ATS-82-2-N to 082 ATS-82-2 and 082 ATS-82-2 to 082 EC-82 are undersized per the 200A type CA breaker feeding them. To protect the cable, it is recommended that the type CA breaker is changed to 150A or the #1/0 cables are upsized to #3/0, copper.
• Eaton recommends these cables to be field verified and either the replace and upsize the cables per NEC Table 310.15(B)(16), or change the size of the upstream protective device(s) to protect the cable. The latter recommendation may not be an option where the branch load size cannot be lowered.
VA Battle Creek 1-6
SHORT-CIRCUIT ANALYSIS 2.0
2.1 General
The short-circuit study determines the fault currents that flow in the system during various fault conditions. A system model was created using SKM Systems Analysis software. The calculated fault currents are used in the device evaluation and coordination studies. See Section 7.0 and Section 8.0 for the computer generated input data and output data. NEC-2014, Article 110.24(A) requires that service entrance equipment is labeled with the following pieces of information:
• Maximum available fault current
• Date on which the fault current was calculated
Article 110.24(B) adds that if there is a modification that may change this fault current value, it must be recalculated. The field marking must be updated to reflect the new value of maximum fault current.
Separate “Z” (complex), “X” (reactive), and "R" (resistive) networks are used for the short-circuit analysis. Complex network reduction and the relationship E/Z are used to calculate the fault current magnitude and angle at each faulted bus. The complex equivalent circuit impedance, Z, is calculated by the reduction of the “Z” (complex) network. The X/R ratios calculated for each fault condition are based on the separate reduction of the X and R networks. These X/R ratios are used for the calculation of fault duty multipliers, to evaluate the short-circuit ratings of system components.
The software is capable of generating three types of short-circuit reports for both balanced (three-phase bolted) and unbalanced (line-to-ground) faults. The reports that are generated depend on the system that is being evaluated.
The three types of short-circuit reports are:
• Fault Report (for low voltage)
• Momentary Duty Report (for medium voltage)
• Interrupting Duty Report (for medium voltage)
1. Fault Report
The fault currents reported in the “Fault Report” are applicable to low voltage devices and components. The fault currents calculated in this report are based on the contribution data derived from IEEE Std C37.13™. The fault currents are calculated as follows:
• Motor and generator subtransient reactance values (Xd”) are adjusted per the first cycle duty multipliers described in IEEE Std 141™.
• The complex equivalent circuit impedance, Z, is calculated by network reduction of the “Z” (complex) network.
• The momentary symmetrical current = E/Z.
• The X/R ratio is equal to the equivalent circuit reactance, X, divided by the equivalent circuit resistance, R. As discussed above, X is calculated by the reduction of the “X” (reactive) network and R is calculated by the reduction of the “R” (resistive) network.
VA Battle Creek 2-1
Multiplying factors are determined, and used to adjust the calculated symmetrical fault current. The adjusted current is used to evaluate low voltage protective devices. Low voltage output algorithms and output reports reflect NEMA AB-1 molded case breaker de-rating multipliers. Breakers are de-rated for circuits where the power factor is lower than the NEMA test circuit (higher X/R ratio). The multipliers adjust the symmetrical fault current to the value associated with the systems fault point X/R ratio. The adjusted value listed on the report may then be compared directly with the manufacturer's published interrupting rating.
2. Momentary Duty Report
The “Momentary Duty Report” contains the calculated fault currents that occur during the first half-cycle of the fault. The momentary fault currents are used to evaluate medium and high voltage fuses, and the “closing and latching” capability (momentary rating) of medium and high voltage breakers. The fault currents reported in the “Momentary Duty Report” are calculated as follows:
• Motor and generator subtransient reactance values (Xd”) are adjusted per the first cycle duty multipliers described in IEEE Std 141.
• The complex equivalent circuit impedance, Z, is calculated by network reduction of the “Z” (complex) network.
• The momentary symmetrical current = E/Z.
• The X/R ratio reported is equal to the equivalent circuit reactance, X, divided by the equivalent circuit resistance, R. As discussed above, X is calculated by the reduction of the “X” (reactive) network and R is calculated by the reduction of the “R” (resistive) network.
• The momentary asymmetrical current is calculated and reported in two different ways, once as “sym*1.6” and again as “momentary based on X/R”. The “sym*1.6” value is the momentary symmetrical current multiplied by 1.6. The “momentary based on X/R” value is the momentary symmetrical current multiplied by
( )( )e RX21 2+ − π
3. Interrupting Duty Report
The fault currents reported in the “Interrupting Duty Report” are used to evaluate the interrupting rating of medium- and high-voltage breakers. The interrupting symmetrical current is calculated as follows:
• Motor and generator subtransient reactance values (Xd”) are adjusted per the interrupting duty multipliers described in IEEE Std 141.
• The complex equivalent circuit impedance, Z, is calculated by network reduction of the “Z” (complex) network.
• The interrupting symmetrical current = E/Z.
• The X/R ratio reported is equal to the equivalent circuit reactance, X, divided by the equivalent circuit resistance, R. As discussed above, X is calculated by the reduction of the “X” (reactive) network and R is calculated by the reduction of the “R” (resistive) network.
VA Battle Creek 2-2
• The calculated X/R ratio is used to determine the minimum contact parting time multiplying factors for 2, 3, 5, and 8 cycle breakers. The multiplying factors are based on IEEE Std C37.5™ and IEEE Std C37.010™ standards. The multiplying factors are applied to the interrupting symmetrical current in order to calculate the RMS short-circuit current interrupting duty for 2, 3, 5, and 8 cycle breakers. This duty is compared to the symmetrical current interrupting rating of the circuit breaker. NACD (No AC Decrement) ratios are calculated with consideration of generator "Local" and "Remote" contributions as outlined in IEEE Std C37.010™.
• Motor and generator impedance multipliers for the short-circuit calculations are summarized in the following table. This is based on the recommended combination network for comprehensive multi-voltage system calculations (from IEEE Std 141:
Machine Type Impedance
(First Cycle Duty) Impedance
(Interrupting Duty)
Turbine generators, Condensers, Hydrogenerators with amortisseur windings
1.0 Xd" 1.0 Xd"
Synchronous motors 1.0 Xd" 1.5 Xd"
Induction motors > 1000 hp at speed ≤ 1800 RPM, or > 250 hp at 3600 RPM.
1.0 Xd" 1.5 Xd"
Induction motors ≥ 50 hp not covered above. 1.2 Xd" 3.0 Xd"
Induction motors < 50 hp 1.67 Xd" Neglect
Note: Xd" is the subtransient reactance of the rotating machine.
2.2 Objectives
The objective of the short-circuit analysis is to calculate the maximum short-circuit currents produced by balanced three-phase and unbalanced faults at each bus shown on the one-line diagrams.
1. Short-Circuit System Model
The system was modeled for worst-case fault currents. Short-circuit currents were calculated for a three-phase bolted fault and single-line-to-ground fault at each bus shown on the study one-line diagrams.
For closed transition type automatic transfer switches which parallel more than one voltage source, even for a short time (< 100 ms), the available fault currents of the two sources have been considered for a combined fault current value that represents the contribution from both sources. NEC Article 110.9 states that equipment which is used to interrupt a fault must be properly rated for both the nominal voltage and the available fault current at the line side of that device. Furthermore, NEC Article
VA Battle Creek 2-3
705.16 states that all fault currents from all power sources must be considered when examining the interrupting rating of a device. Location of the analyzed fault with respect to the switching devices, such as circuit breakers, was taken into consideration when determining the appropriate device interrupting current ratings.
2.3 Equipment Evaluation
The purpose of the equipment evaluation is to compare the maximum calculated short-circuit currents to the short-circuit ratings of protective devices. The comparison is made in order to determine if the device can interrupt or withstand the available fault currents of the electrical system to which the device is applied, as required by NEC Articles 110.9 and 110.10. The device evaluation follows the evaluation procedures outlined in IEEE Std C37.13, IEEE Std C37.010, IEEE Std C37.5, IEEE Std C37.41™, IEEE Std 1015™, and applicable ANSI, NEMA, and UL standards.
The results of the short-circuit equipment evaluation are summarized in Table 2.1 and Table 2.2. The tables indicate “Bus I.D.” (corresponds to bus designations used in the one-line diagrams, “Manufacturer”, “Status” (Pass, fail, unknown, or marginal), “Type” (equipment category), “Equip Volts”, calculated short-circuit duty, the equipment short-circuit rating, the series rating (if applicable), and the maximum duty rating.
The maximum duty rating is calculated by:
RatingCDeviceS dutyCS
If the short-circuit rating of a device is not known, and/or short-circuit rating information is not available, a Minimum Required short-circuit rating is listed. All short-circuit current values are reported in units of kA.
1. For low voltage devices:
The calculated short-circuit duty is reported under “Calc Isc (kA)" and the device short-circuit rating is reported under "Equip Isc (kA)". The calculated duty has been adjusted accordingly per the system X/R and device test X/R.
2. For medium/high voltage breakers:
The calculated interrupting short-circuit duty is reported under "Calc Isc (kA)" and the breaker short-circuit interrupting rating is reported under "Equip Isc (kA)". The interrupting duty has been adjusted per multiplying factors based on the breaker clearing time and system X/R. The calculated momentary duty (i.e. close-and-latch duty) is reported under "Calc Mom (kA)".
3. For medium/high voltage fuses, switches, and motor starters:
The calculated momentary symmetrical short-circuit duty is reported under "Calc Isc (kA)" and the device's momentary symmetrical short-circuit rating is reported under "Equip Isc (kA)". The calculated momentary asymmetrical duty is reported under "Calc Mom (kA)". The device's momentary asymmetrical short-circuit rating is reported under "Equip Mom (kA)".
VA Battle Creek 2-4
2.4 Short-Circuit Results
Information used in modeling the power system to provide conservative, worst-case results is listed in Section 6.0. The results of the short-circuit analysis, including calculated branch contributions, are provided under Section 8.0. The one-line diagrams with referenced bus identification are included in Section 11.0.
VA Battle Creek 2-5
Table 2.1 – Low-Voltage Equipment Evaluation
Bus I.D. Manufacturer Status Type Bus Calc Equip Rating % Voltage (V) Isc (kA) Isc (kA)
001 MDP-1 WESTINGHOUSE Pass LV Switchboard 208 4.80 25.00 19.19 001 PANEL 1 GE Pass LV Panelboard 208 4.94 (*N1) 10.00 49.39 001 PANEL 2 GE Pass LV Panelboard 208 4.44 (*N1) 10.00 44.38 001 PANEL 2A GE Pass LV Panelboard 208 4.23 (*N1) 10.00 42.33 001 PANEL 2B GE Pass LV Panelboard 208 4.07 (*N1) 10.00 40.67 001 PANEL 3 GE Pass LV Panelboard 208 2.95 10.00 29.51 002 CAT SCAN DISC GE Pass LV Disconnect Switch 480 4.46 25.00 17.85 002 DENTAL CLINIC A/C WESTINGHOUSE Pass LV Panelboard 208 11.38 42.00 27.09 002 DISC ELEV #1 UNKNOWN Pass LV Disconnect 208 9.39 100.00 9.39 002 DISC ELEV #2 SIEMENS Pass LV Panelboard 208 8.76 10.00 87.60 002 DISC ELEV #3 UNKNOWN Pass LV Disconnect 208 9.39 100.00 9.39 002 EDP EATON Fail LV Panelboard 208 *29.15 (*N1) 10.00 *291.47 002 LP-CB1 SIEMENS Pass LV Panelboard 208 9.09 10.00 90.86 002 LP-CB2 SIEMENS Pass LV Panelboard 208 9.87 10.00 98.65 002 LP-CB3 SQUARE D Fail LV Panelboard 208 *10.46 10.00 *104.56 002 LP-CB3A SQUARE D Fail LV Panelboard 208 *10.18 10.00 *101.84 002 LP-CB4 EATON Pass LV Panelboard 208 9.79 10.00 97.87 002 LP-CB5 EATON Pass LV Panelboard 208 7.94 10.00 79.37 002 LP-CB6 EATON Fail LV Panelboard 208 *32.34 (*N1) 10.00 *323.43 002 LP-CB7 EATON Fail LV Panelboard 208 *17.98 (*N1) 10.00 *179.77 002 MDP 1 SIEMENS Pass LV Switchboard 480 12.62 (*N1) 65.00 19.41 002 MDP-1 SIEMENS Fail LV Panelboard 208 *19.42 18.00 *107.89 002 MDP-2 SIEMENS Fail LV Panelboard 208 *19.38 18.00 *107.68 002 MDP-3 SIEMENS Fail LV Panelboard 208 *20.51 18.00 *113.94 002 MDP-4 EATON Fail LV Panelboard 208 *30.05 18.00 *166.96 002 MDP-5 EATON Fail LV Panelboard 208 *19.23 18.00 *106.81 002 MDP-6 EATON Pass LV Switchboard 208 33.04 100.00 33.04
VA Battle Creek 2-6
Voltage (V) Isc (kA) Isc (kA)
002 PANEL A-1 SIEMENS Fail LV Panelboard 208 *13.59 10.00 *135.86 002 PANEL A-2 SIEMENS Fail LV Panelboard 208 *13.00 10.00 *130.01 002 PANEL A-3 GE Fail LV Panelboard 208 *17.65 (*N1) 10.00 *176.46 002 PANEL A-4 SIEMENS Fail LV Panelboard 208 *14.91 10.00 *149.09 002 PANEL A-5 SIEMENS Pass LV Panelboard 208 9.68 10.00 96.83 002 PANEL A-6 SQUARE D Fail LV Panelboard 208 *13.06 10.00 *130.57 002 PANEL A-7 SIEMENS Fail LV Panelboard 208 *15.15 10.00 *151.47 002 PANEL A-8 SIEMENS Fail LV Panelboard 208 *14.74 10.00 *147.45 002 PANEL A-9 GE Fail LV Panelboard 208 *12.51 10.00 *125.14 002 PANEL B-1 SIEMENS Fail LV Panelboard 208 *11.69 10.00 *116.92 002 PANEL B-2 SIEMENS Fail LV Panelboard 208 *13.55 10.00 *135.50 002 PANEL B-3 SQUARE D Fail LV Panelboard 208 *10.01 10.00 *100.08 002 PANEL B-4 SIEMENS Pass LV Panelboard 208 9.72 10.00 97.17 002 PANEL B-5 SIEMENS Fail LV Panelboard 208 *10.99 10.00 *109.88 002 PANEL B-6 SIEMENS Pass LV Panelboard 208 8.89 10.00 88.90 002 PANEL B-7 SIEMENS Pass LV Panelboard 208 8.23 10.00 82.26 002 PANEL C-1 SIEMENS Fail LV Panelboard 208 *10.93 10.00 *109.34 002 PANEL C-10 SIEMENS Pass LV Panelboard 208 7.47 10.00 74.74 002 PANEL C-11 SIEMENS Pass LV Panelboard 208 7.67 10.00 76.69 002 PANEL C-12 SIEMENS Pass LV Panelboard 208 8.31 10.00 83.14 002 PANEL C-13 SIEMENS Pass LV Panelboard 208 8.61 10.00 86.09 002 PANEL C-2 SIEMENS Fail LV Panelboard 208 *10.93 10.00 *109.34 002 PANEL C-3 SIEMENS Fail LV Panelboard 208 *11.69 10.00 *116.92 002 PANEL C-4 EATON Pass LV Panelboard 208 8.73 10.00 87.34 002 PANEL C-5 SIEMENS Fail LV Panelboard 208 *10.93 10.00 *109.34 002 PANEL C-6 SIEMENS Fail LV Panelboard 208 *11.30 10.00 *113.01 002 PANEL C-7 GE Pass LV Panelboard 208 6.43 22.00 29.24 002 PANEL C-8 GE Pass LV Panelboard 208 3.27 22.00 14.88 002 PANEL C-9 SIEMENS Pass LV Panelboard 208 8.09 10.00 80.88
VA Battle Creek 2-7
002 PANEL D-1 SIEMENS Fail LV Panelboard 208 *14.70 10.00 *146.98 002 PANEL D-2 SIEMENS Fail LV Panelboard 208 *14.70 10.00 *146.98 002 PANEL D-3 SIEMENS Pass LV Panelboard 208 6.23 10.00 62.25 002 PANEL D-4 GE Pass LV Panelboard 208 19.65 22.00 89.32 002 PANEL EP-CB1 SQUARE D Fail LV Panelboard 208 *12.11 10.00 *121.10 002 PANEL EP-CB2 SQUARE D Pass LV Panelboard 208 9.87 10.00 98.70 002 PANEL EP-CB3 SQUARE D Pass LV Panelboard 208 8.42 10.00 84.18 002 PANEL PP-P WESTINGHOUSE Pass LV Panelboard 480 10.13 (*N1) 14.00 72.33 002 RP-CB1 SIEMENS Pass LV Panelboard 208 9.09 10.00 90.86 002 RP-CB2 SIEMENS Pass LV Panelboard 208 9.87 10.00 98.65 002 RP-CB4 EATON Fail LV Panelboard 208 *13.76 10.00 *137.62 002 RP-CB5 EATON Fail LV Panelboard 208 *10.53 10.00 *105.31 002 RP-CB6 EATON Fail LV Panelboard 208 *32.00 (*N1) 10.00 *320.01 002 RP-CB7 EATON Fail LV Panelboard 208 *19.75 (*N1) 10.00 *197.55 002 SWBD-B2A SIEMENS Pass LV Switchboard 208 13.60 22.00 61.82 003 ATS ASCO Pass Automatic Transfer Switch 208 12.12 65.00 18.65 003 EMDP-3 EATON Pass LV Switchboard 208 7.00 65.00 10.77 003 MDP-3 EATON Pass LV Panelboard 208 10.81 22.00 49.12 003 MDP-3 NORM DISC EATON Pass LV Enclosed Breaker 208 13.45 100.00 13.45 003 PANEL 3-1 EATON Pass LV Panelboard 208 1.27 10.00 12.74 003 PANEL A SQUARE D Pass LV Panelboard 208 6.69 10.00 66.87 003 PANEL B WESTINGHOUSE Pass LV Panelboard 208 8.13 10.00 81.28 003 PANEL D SQUARE D Pass LV Panelboard 208 4.18 10.00 41.81 004 4PPH GE Pass LV Panelboard 208 4.62 22.00 20.98 004 ATS-4-1 KOHLER Pass Automatic Transfer Switch 208 5.25 (*N1) 10.00 52.52 004 ATS-4-2 KOHLER Pass Automatic Transfer Switch 208 5.39 (*N1) 10.00 53.85 004 EMDP-4 EATON Pass LV Switchboard 208 15.64 65.00 24.06 004 MDP SQUARE D Pass LV Switchboard 208 4.76 42.00 11.34 004 PANEL A SQUARE D Pass LV Panelboard 208 3.52 10.00 35.24
VA Battle Creek 2-8
004 PP-0 WESTINGHOUSE Pass LV Panelboard 208 4.93 (*N1) 10.00 49.30 004 PP-1 WESTINGHOUSE Pass LV Panelboard 208 4.23 (*N1) 10.00 42.25 004 PP-2 SQUARE D Pass LV Panelboard 208 5.18 (*N1) 10.00 51.78 004 PP-3 GE Pass LV Panelboard 208 3.98 (*N1) 10.00 39.82 005 ATS-5 CUMMINS Fail Automatic Transfer Switch 208 *34.02 (*N1) 10.00 *340.22 005 CH-1 EATON Pass LV Panelboard 208 15.20 65.00 23.39 005 CH-2 EATON Pass LV Panelboard 208 15.20 65.00 23.39 005 DP-A EATON Pass LV Panelboard 208 7.08 10.00 70.85 005 LP-AA GE Pass LV Panelboard 208 9.54 10.00 95.39 005 LP-BB GE Pass LV Panelboard 208 9.57 10.00 95.70 005 LP-CC GE Pass LV Panelboard 208 8.96 10.00 89.65 005 LP-DD GE Fail LV Panelboard 208 *11.78 10.00 *117.76 005 LP-FF GE Fail LV Panelboard 208 *12.41 10.00 *124.10 005 LP-HH GE Fail LV Panelboard 208 *11.69 10.00 *116.89 005 LP-JJ GE Pass LV Panelboard 208 9.57 10.00 95.70 005 LP-MM GE Fail LV Panelboard 208 *17.13 (*N1) 10.00 *171.32 005 LPE-11 GE Pass LV Panelboard 208 9.60 10.00 96.03 005 LPE-22 GE Pass LV Panelboard 208 9.94 10.00 99.35 005 LPE-33 GE Pass LV Panelboard 208 8.19 10.00 81.85 005 LPE-GG GE Fail LV Panelboard 208 *10.26 10.00 *102.59 005 MCC-1 WESTINGHOUSE Pass MCC 208 21.81 100.00 21.81 005 MDP-1 WESTINGHOUSE Fail LV Panelboard 208 *29.97 (*N1) 10.00 *299.72 005 MDP-1A WESTINGHOUSE Pass LV Panelboard 208 28.23 (*N1) 42.00 67.21 005 MDP-2 SIEMENS Pass LV Switchgear 208 19.18 22.00 87.17 005 MDP-3 FEDERAL PACIFIC Fail LV Switchboard 208 *24.64 (*N1) 10.00 *246.41 005 PP-22 SQUARE D Pass LV Panelboard 208 9.00 10.00 89.98 005 PP-33 GE Fail LV Panelboard 208 *14.21 (*N1) 10.00 *142.05 005 PP-34 SQUARE D Fail LV Panelboard 208 *11.52 10.00 *115.19 005 PP-44 GE Fail LV Panelboard 208 *15.57 (*N1) 10.00 *155.68
VA Battle Creek 2-9
005 PP-55 GE Pass LV Panelboard 208 8.19 10.00 81.85 005 PP-66 GE Fail LV Panelboard 208 *10.29 10.00 *102.91 005 SWBD-1 WESTINGHOUSE Pass LV Switchboard 208 32.31 65.00 49.71 006 LPA GE Pass LV Panelboard 208 9.04 (*N1) 10.00 90.42 006 LPB GE Pass LV Panelboard 208 5.25 10.00 52.46 006 LPC GE Pass LV Panelboard 208 9.00 10.00 90.04 006 MDP-1 SQUARE D Pass LV Switchboard 208 14.41 42.00 34.31 006 MDP-2 WESTINGHOUSE Pass LV Switchboard 208 11.38 22.00 51.74 006 PNL 6PPH GE Pass LV Panelboard 208 13.94 22.00 63.37 007 1C1 EATON Pass LV Panelboard 208 4.27 10.00 42.75 007 1L1 EATON Pass LV Panelboard 208 1.28 22.00 5.82 007 1N1 EATON Pass LV Panelboard 208 6.06 10.00 60.62 007 1N2 EATON Pass LV Panelboard 208 6.05 10.00 60.46 007 1N3 EATON Pass LV Panelboard 208 7.31 (*N1) 10.00 73.14 007 1N4 EATON Pass LV Panelboard 208 7.29 (*N1) 10.00 72.86 007 2N1 EATON Pass LV Panelboard 208 5.66 10.00 56.57 007 2N2 EATON Pass LV Panelboard 208 5.64 10.00 56.43 007 2N3 EATON Pass LV Panelboard 208 6.89 (*N1) 10.00 68.87 007 2N4 EATON Pass LV Panelboard 208 6.86 (*N1) 10.00 68.63 007 A1 EATON Pass LV Panelboard 208 4.74 10.00 47.44 007 A2 GE Pass LV Panelboard 208 6.72 (*N1) 10.00 67.16 007 A4 GE Pass LV Panelboard 208 6.77 10.00 67.74 007 ATS-1 UNKNOWN Fail Automatic Transfer Switch 208 *10.90 (*N1) 10.00 *108.98 007 ATS-2 UNKNOWN Fail Automatic Transfer Switch 208 *10.90 (*N1) 10.00 *108.98 007 B-3 GE Pass LV Panelboard 208 5.53 10.00 55.35 007 B-4 GE Pass LV Panelboard 208 5.53 10.00 55.35 007 C1 GE Pass LV Panelboard 208 6.12 (*N1) 10.00 61.22 007 DISC MDP-B1 UNKNOWN Pass LV Disconnect Switch 208 9.45 100.00 9.45 007 DP2 EATON Pass LV Panelboard 480 9.80 14.00 69.98
VA Battle Creek 2-10
007 ELEV A GE Pass LV Panelboard 208 4.11 10.00 41.13 007 ELEV B DISC UNKNOWN Pass LV Disconnect Switch 480 6.26 100.00 6.26 007 EMDP-7 EATON Pass LV Switchboard 208 24.89 65.00 38.29 007 FF-1 GE Pass LV Panelboard 208 6.08 10.00 60.84 007 L1 EATON Fail LV Panelboard 208 *10.36 (*N1) 10.00 *103.61 007 MDP WESTINGHOUSE Pass LV Switchboard 208 10.61 (*N1) 14.00 75.78 007 NSB EATON Pass LV Switchboard 480 15.13 35.00 43.23 007 P-6 SQUARE D Pass LV Panelboard 208 4.94 10.00 49.37 007 P1 EATON Fail LV Panelboard 208 *10.36 (*N1) 10.00 *103.61 007 PANEL DD GE Pass LV Panelboard 208 8.25 (*N1) 10.00 82.52 007 PANEL L FEDERAL PACIFIC Fail LV Panelboard 208 *10.25 (*N1) 10.00 *102.54 007 PANEL P SQUARE D Fail LV Panelboard 208 *10.25 (*N1) 10.00 *102.54 007 PANEL XX GE Pass LV Panelboard 208 5.22 10.00 52.17 007 PNL 1 (ACC 4) GE Pass LV Panelboard 208 4.21 10.00 42.12 008 ATS-B8 UNKNOWN Fail Automatic Transfer Switch 208 *12.50 (*N1) 10.00 *124.95 008 EMDP GE Pass LV Panelboard 208 11.06 42.00 26.33 008 MDP-8 EATON Pass LV Panelboard 208 12.66 65.00 19.48 008 PANEL B GE Pass LV Panelboard 208 7.13 10.00 71.26 008 PANEL LP1 GE Pass LV Panelboard 208 8.18 10.00 81.76 008 PANEL LP2 GE Pass LV Panelboard 208 8.18 10.00 81.76 008 PANEL LP3 GE Pass LV Panelboard 208 8.18 10.00 81.76 008 PANEL LP4 GE Pass LV Panelboard 208 8.18 10.00 81.76 008 PNL A1 EATON Pass LV Panelboard 208 9.12 10.00 91.18 009 ATS-B9 UNKNOWN Fail Automatic Transfer Switch 208 *15.18 (*N1) 10.00 *151.77 009 EMDP WESTINGHOUSE Pass LV Panelboard 208 3.42 (*N1) 42.00 8.13 009 MDP-9 EATON Pass LV Panelboard 208 14.30 65.00 22.00 009 PP-1 WESTINGHOUSE Pass LV Panelboard 208 10.19 65.00 15.68 009 PP-2 EATON Pass LV Panelboard 208 6.63 10.00 66.28 009 RP-AC1 EATON Pass LV Panelboard 208 7.19 10.00 71.94
VA Battle Creek 2-11
009 RP-AC2 EATON Pass LV Panelboard 208 7.19 22.00 32.70 009 TRAINING RM EATON Pass LV Panelboard 208 4.56 22.00 20.74 010 MDP-1 EATON Pass LV Panelboard 208 5.22 18.00 29.00 010 MDP-10 EATON Pass LV Switchboard 208 11.33 18.00 62.93 010 MDP-2 EATON Pass LV Panelboard 208 5.95 10.00 59.48 010 PANEL A-1 SIEMENS Pass LV Panelboard 208 3.45 10.00 34.53 010 PANEL A-2 SIEMENS Pass LV Panelboard 208 9.54 10.00 95.37 010 PANEL B-1 GE Pass LV Panelboard 208 5.69 10.00 56.86 010 PANEL C-1 SIEMENS Pass LV Panelboard 208 5.95 10.00 59.48 012 ATS-12-1 KOHLER Pass Automatic Transfer Switch 208 8.07 (*N1) 10.00 80.67 012 EMDP-12 EATON Pass LV Switchboard 208 22.93 65.00 35.28 012 MDP-12 GE Pass LV Panelboard 208 6.86 22.00 31.20 012 PANEL 1 GE Pass LV Panelboard 208 6.98 (*N1) 10.00 69.79 012 PANEL 2 GE Pass LV Panelboard 208 5.50 10.00 54.99 012 PANEL A EATON Pass LV Panelboard 208 6.89 (*N1) 10.00 68.92 013 ATS-13-1 UNKNOWN Fail Automatic Transfer Switch 208 *24.28 (*N1) 10.00 *242.81 013 B13-1 EATON Pass LV Panelboard 208 8.61 10.00 86.10 013 KITCHEN SQUARE D Pass LV Panelboard 208 4.06 10.00 40.62 013 LP-A SQUARE D Fail LV Panelboard 208 *13.86 (*N1) 10.00 *138.59 013 LP-B SQUARE D Pass LV Panelboard 208 8.14 10.00 81.41 013 LP-E SQUARE D Fail LV Panelboard 208 *13.86 (*N1) 10.00 *138.59 013 LP-F SQUARE D Pass LV Panelboard 208 8.14 10.00 81.41 013 MDP-13 WESTINGHOUSE Fail LV Panelboard 208 *22.90 (*N1) 10.00 *228.99 013 PANEL 013-2 GE Pass LV Panelboard 208 4.25 10.00 42.45 013 PANEL 013-3 GE Pass LV Panelboard 208 6.14 10.00 61.36 013 PANEL 013-4 SQUARE D Pass LV Panelboard 208 6.21 22.00 28.24 013 PANEL A1 SQUARE D Pass LV Panelboard 208 6.53 10.00 65.27 013 PANEL A2 SQUARE D Pass LV Panelboard 208 9.03 10.00 90.30 013 PANEL A3 SQUARE D Pass LV Panelboard 208 8.23 10.00 82.34
VA Battle Creek 2-12
013 PANEL LP-C SQUARE D Pass LV Panelboard 208 4.06 10.00 40.62 013 PANEL LP-D SQUARE D Pass LV Panelboard 208 4.06 10.00 40.62 013 PANEL LP-G SQUARE D Pass LV Panelboard 208 4.06 10.00 40.62 013 PANEL LP-H SQUARE D Pass LV Panelboard 208 4.06 10.00 40.62 013 PP-TV GE Pass LV Panelboard 208 8.61 22.00 39.14 013 RM 200 PNL EATON Pass LV Panelboard 208 2.24 10.00 22.42 014 CH DISC SQUARE D Pass LV Disconnect Switch 208 10.35 100.00 10.35 014 DISC ELEV UNKNOWN Pass LV Disconnect Switch 208 9.34 100.00 9.34 014 ELEV GE Fail LV Panelboard 208 *10.03 10.00 *100.30 014 EMDP-14 EATON Pass LV Switchboard 208 8.31 100.00 8.31 014 EMG SIEMENS Pass LV Panelboard 208 5.90 10.00 58.97 014 EP-B WESTINGHOUSE Pass LV Panelboard 208 19.48 65.00 29.97 014 LP-A WESTINGHOUSE Pass LV Panelboard 208 18.36 65.00 28.25 014 LP-L GE Fail LV Panelboard 208 *18.35 10.00 *183.48 014 PANEL 014-2 SQUARE D Fail LV Panelboard 208 *13.19 10.00 *131.88 014 PANEL 014-3 GE Pass LV Panelboard 208 7.84 10.00 78.40 014 PANEL 014-4 GE Pass LV Panelboard 208 8.97 10.00 89.74 014 PANEL 014-5 GE Pass LV Panelboard 208 8.37 10.00 83.71 014 PANEL 1 GE Pass LV Panelboard 208 4.74 10.00 47.42 014 PANEL 1C EATON Pass LV Panelboard 208 4.21 10.00 42.11 014 PANEL 1N GE Pass LV Panelboard 208 7.61 10.00 76.09 014 PANEL 1S GE Pass LV Panelboard 208 6.66 10.00 66.62 014 PANEL 2 SQUARE D Pass LV Panelboard 208 4.56 10.00 45.59 014 PANEL 2C EATON Pass LV Panelboard 208 4.72 22.00 21.45 014 PANEL 2N GE Pass LV Panelboard 208 8.27 10.00 82.71 014 PANEL 2S GE Pass LV Panelboard 208 7.31 10.00 73.07 014 PANEL 3 GE Pass LV Panelboard 208 5.06 10.00 50.63 014 PANEL 3C SQUARE D Fail LV Panelboard 208 *10.51 10.00 *105.07 014 PANEL PP-P GE Fail LV Panelboard 208 *20.92 (*N1) 10.00 *209.16
VA Battle Creek 2-13
014 PANEL SB EATON Pass LV Panelboard 208 4.27 22.00 19.40 014 PNL SL EATON Pass LV Panelboard 208 5.44 10.00 54.35 014 SWBD A WESTINGHOUSE Fail LV Switchboard 208 *25.38 22.00 *115.35 017 MDP-17 MAIN GE Pass LV Panelboard 240 8.04 (*N1) 10.00 80.41 020 MDP-20 MAIN GE Pass LV Panelboard 240 7.69 (*N1) 10.00 76.95 021 PANEL 21-1 WESTINGHOUSE Pass LV Panelboard 208 3.54 22.00 16.11 022 ATS-B22 UNKNOWN Pass Automatic Transfer Switch 208 9.13 (*N1) 10.00 91.30 022 EMDP EATON Pass LV Panelboard 208 8.91 65.00 13.70 022 LP-1E SQUARE D Pass LV Panelboard 208 8.84 10.00 88.40 022 LP-1W SQUARE D Pass LV Panelboard 208 3.65 10.00 36.51 022 LP-1WA SQUARE D Pass LV Panelboard 208 6.51 10.00 65.06 022 LP-2E SQUARE D Pass LV Panelboard 208 6.62 10.00 66.18 022 LP-2WA SQUARE D Pass LV Panelboard 208 6.30 10.00 63.04 022 LP-EG22 SQUARE D Pass LV Panelboard 208 5.48 10.00 54.81 022 MDP-22 EATON Pass LV Panelboard 208 9.41 65.00 14.47 022 PP-KIT SQUARE D Pass LV Panelboard 208 7.09 10.00 70.85 022 RP-AC1 EATON Pass LV Panelboard 208 6.77 10.00 67.66 022 RP-AC2 EATON Pass LV Panelboard 208 5.62 10.00 56.19 024 ATTIC A SQUARE D Pass LV Panelboard 208 3.65 10.00 36.53 024 PANEL A SQUARE D Pass LV Panelboard 208 5.09 10.00 50.94 024 PANEL B GE Pass LV Panelboard 208 5.44 10.00 54.45 024 PANEL C GE Pass LV Panelboard 208 4.91 10.00 49.13 025 MDP-25 WESTINGHOUSE Pass LV Panelboard 208 7.50 25.00 29.99 025 PANEL A SIEMENS Pass LV Panelboard 208 6.76 (*N1) 10.00 67.64 025 PANEL B GE Pass LV Panelboard 208 5.56 10.00 55.64 025 PANEL C SIEMENS Pass LV Panelboard 208 8.05 (*N1) 10.00 80.45 026 MDP SQUARE D Pass LV Switchgear 208 19.36 25.00 77.43 026 PNL A SQUARE D Fail LV Panelboard 208 *11.40 10.00 *113.98 026 PNL B SQUARE D Pass LV Panelboard 208 9.48 10.00 94.82
VA Battle Creek 2-14
026 PNL B1 SQUARE D Pass LV Panelboard 208 8.88 10.00 88.82 026 PNL B2 SQUARE D Pass LV Panelboard 208 8.88 10.00 88.82 026 PNL C SQUARE D Pass LV Panelboard 208 6.50 10.00 65.00 026 PNL D SQUARE D Pass LV Panelboard 208 5.51 10.00 55.12 026 PNL E SQUARE D Pass LV Panelboard 208 4.78 10.00 47.83 026 PNL G SQUARE D Pass LV Panelboard 208 1.66 10.00 16.64 026 PNL H SQUARE D Pass LV Panelboard 208 1.44 10.00 14.38 027 E85 FUEL STN SQUARE D Pass LV Panelboard 208 1.93 10.00 19.29 027 LP1 EATON Fail LV Panelboard 208 *13.93 (*N1) 10.00 *139.34 027 MDP-27 SQUAR E D Pass LV Switchboard 208 13.04 65.00 20.06 027 PANEL 1 BIO MED GE Pass LV Panelboard 208 9.93 (*N1) 10.00 99.31 027 PNL JMJ EATON Pass LV Panelboard 208 5.26 10.00 52.58 027 PP1 IN 117E SQUARE D Pass LV Panelboard 208 9.80 (*N1) 10.00 97.97 028 AC SHOP PNL EATON Pass LV Panelboard 208 1.16 10.00 11.61 028 PANEL A DISC UNKNOWN Pass LV Disconnect Switch 208 4.17 100.00 4.17 028 PNL A CARP SHOP SIEMENS Pass LV Panelboard 208 3.79 10.00 37.91 028 PNL A PIPE SHOP GE Pass LV Panelboard 208 4.14 10.00 41.39 028 PNL B CARP SHOP EATON Pass LV Panelboard 208 3.77 10.00 37.71 028 PNL C KEY SHOP EATON Pass LV Panelboard 208 2.97 10.00 29.65 030 ATS-30-1 UNKNOWN Fail Automatic Transfer Switch 208 *11.12 (*N1) 10.00 *111.16 030 ATS-30-2 UNKNOWN Fail Automatic Transfer Switch 208 *12.04 (*N1) 10.00 *120.38 030 DISC 030-1 GE Pass LV Panelboard 208 9.60 22.00 43.62 030 DISC FWP UNKNOWN Pass LV Disconnect Switch 208 8.08 (*N1) 100.00 8.08 030 DISC INCIN UNKNOWN Pass LV Disconnect Switch 208 10.92 100.00 10.92 030 INCINERATOR PANEL SQUARE D Pass LV Panelboard 208 2.39 10.00 23.88 030 MDP 2A-1 EATON Pass LV Panelboard 208 4.66 10.00 46.57 030 MDP-2A EATON Fail LV Panelboard 208 *10.87 (*N1) 10.00 *108.66 030 MDP-30 WESTINGHOUSE Pass LV Switchboard 208 14.42 42.00 34.34 030 MDP-B EATON Pass LV Panelboard 208 9.93 (*N1) 10.00 99.35
VA Battle Creek 2-15
030 PANEL 030-1 GE Pass LV Panelboard 208 7.37 10.00 73.73 030 PANEL 030-2 SQUARE D Fail LV Panelboard 208 *11.31 (*N1) 10.00 *113.08 030 PANEL E-1 EATON Pass LV Panelboard 208 8.96 10.00 89.58 030 PANEL I EATON Pass LV Panelboard 208 8.04 10.00 80.39 030 PNL JJ EATON Pass LV Panelboard 208 4.92 10.00 49.16 039 ATS-CH 1 ASCO Pass Automatic Transfer Switch 208 28.59 50.00 57.17 039 ATS-CR ASCO Pass Automatic Transfer Switch 208 31.37 65.00 48.27 039 ATS-EQ ASCO Pass Automatic Transfer Switch 208 39.14 50.00 78.29 039 ATS-LS ASCO Pass Automatic Transfer Switch 208 33.05 65.00 50.84 039 CH DISC EATON Pass LV Disconnect Switch 208 23.88 100.00 23.88 039 CR-1NA EATON Pass LV Panelboard 208 8.17 10.00 81.66 039 CR-1SA EATON Pass LV Panelboard 208 9.08 10.00 90.75 039 CR-2NA EATON Pass LV Panelboard 208 4.58 10.00 45.82 039 CR-2SA EATON Pass LV Panelboard 208 6.27 10.00 62.72 039 DP-CR EATON Fail LV Panelboard 208 *26.77 (*N1) 10.00 *267.69 039 DP-EQ EATON Fail LV Panelboard 208 *40.39 (*N1) 10.00 *403.89 039 DP-LS EATON Fail LV Panelboard 208 *27.80 10.00 *278.03 039 ELEV GE Fail LV Panelboard 208 *11.83 10.00 *118.32 039 ELEV 480V DSIC EATON Pass LV Disconnect Switch 480 1.72 22.00 7.80 039 EMDP EATON Pass LV Switchboard 208 30.16 65.00 46.39 039 EQ-1NA EATON Fail LV Panelboard 208 *12.34 10.00 *123.41 039 EQ-1SA EATON Fail LV Panelboard 208 *13.64 10.00 *136.37 039 EQ-2NA EATON Pass LV Panelboard 208 7.10 10.00 71.01 039 EQ-2SA EATON Pass LV Panelboard 208 9.60 10.00 96.01 039 EXIT PANEL GE Fail LV Panelboard 208 *20.44 10.00 *204.38 039 LP-A WESTINGHOUSE Fail LV Panelboard 208 *36.67 22.00 *166.67 039 LP-B GE Fail LV Panelboard 208 *31.17 (*N1) 10.00 *311.67 039 LS-1NA EATON Pass LV Panelboard 208 4.24 10.00 42.44 039 LS-1SA EATON Pass LV Panelboard 208 4.24 10.00 42.44
VA Battle Creek 2-16
039 LS-2NA EATON Pass LV Panelboard 208 1.99 10.00 19.90 039 LS-2SA EATON Pass LV Panelboard 208 2.68 10.00 26.79 039 MDP-2 EATON Pass LV Switchboard 208 53.35 100.00 53.35 039 MDP-39 EATON Pass LV Switchboard 208 53.27 100.00 53.27 039 ME-1 EATON Fail LV Panelboard 208 *20.60 (*N1) 10.00 *206.02 039 ME-1B EATON Fail LV Panelboard 208 *17.99…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .